EIM Guide: Network Master User Guide for Allen Bradley Series SLC-500 Programmable Controller Manuals & Guides

User’s Guide
AB1746-C
Network Master
(Version 5.21)
For
(Date: 2004-11-18)
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
User’s Guide
Controlinc Network Master … AB1746-C (Version 5.21)
For
Allen-Bradley Series SLC-500 Programmable Controllers
Table of Contents
0. Quick Start Information...............................................................................1
1. Introduction...................................................................................................2
1.1. Overview of 1746-C System ................................................................................... 2
1.2. Overview of Changes in Version 5.21 ................................................................... 4
1.3. Reference Manuals ................................................................................................. 5
1.4. EIM Equipment Compatibility .............................................................................6
1.5. Firmware ................................................................................................................. 6
2. 1746-C Hardware..........................................................................................7
2.1. Hardware Setup ...................................................................................................... 7
2.2. LED Utilization ....................................................................................................... 8
2.2.1. Green (PRT1 & PRT2) and Yellow (LED1 & LED2) LED Usage ........................... 8
2.2.2. Red “BA LOW” LED Usage .................................................................................10
3. Network Setup and Connecting to the NIU ..............................................11
3.1. Field Connections at the Actuator....................................................................... 13
3.1.1. Step 1. Plan the Network Topology ................................................................... 13
3.1.2. Step 2. Select Network Cable............................................................................13
3.1.3. Step 3. Route Cable away from Electrical Interference ..................................... 14
3.1.4. Step 4. Observe Polarity and Network Grounding ............................................. 14
3.1.5. Step 5. Wire Preparation and Connections........................................................ 14
3.1.6. Step 6. Test Network ......................................................................................... 14
3.2. Field Network Cable Connection to the NIU ..................................................... 15
3.3. Cable Connection Between the NIU and the Network Master ........................ 15
4. 1746-C General Theory of Operation .......................................................16
4.1. Operational Overview ..........................................................................................16
4.1.1. Diagram Describing Relationship Between Process Time Slices ........................ 16
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page i
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
4.1.2. Diagram Describing Network Scanning & Actuator Writing Logic........................17
4.1.3. Diagram Demonstrating Adding Additional Valves in Valve Scan Time-Slice...... 18
4.1.4. Diagram Describing Relationship Between Scan Period & Diagnostic Scan....... 19
4.1.5. 1746-C System Operations at Power Up.............................................................20
4.2. Network Interface (Scan) Time-Slice (1746-C Network Communication) 21
4.2.1. Operation: Network Scanning to Gather Valve Actuator Data ............................ 21
4.2.2. Operation: The Network Communication Diagnostic Scan................................. 22
4.3. PLC Interface Time-Slice (1746-C PLC Communication)..........................24
4.3.1. Operation: PLC (Write Data Tables To) or (Read Tables From) the 1746-C...... 26
4.3.2. Operation: PLC Commands to Write Data to the Actuators................................ 29
4.3.3. RLL Example … Manually Send New Table … Auto Read Response ................ 31
5. System Tables..............................................................................................33
5.1. Table Arrangement............................................................................................... 35
5.2. Standard Header Format (All Tables) … Words [0 3] ................................37
5.2.1. Word [0]: Table ID............................................................................................. 37
5.2.2. Word [1]: Read / Write Command Indicator ......................................................37
5.2.3. Word [2]: Reserved / Firmware ID..................................................................... 37
5.2.4. Word [3]: Emergency Shut Down (ESD) Command Word & Indication ............ 38
5.3. Table [0] … System Information Table.............................................................. 39
5.3.1. Table [0] Overview............................................................................................... 39
5.3.2. Table [0] Configuration Words … Words [4 17]................................................ 42
5.3.3. Table [0] Run-Time Information Words … Words [47 63] ................................47
5.3.4. Table [0] … RSLOGIX-500 Examples ................................................................. 48
5.3.4.1. Example RSLOGIX-500 Screen: ..........................................................................48
5.3.4.2. Table [0] … The Configuration Values (RSLOGIX-500). .....................................49
5.3.4.3. Table [0] … The Configuration Values – Writing Table [0] (RSLOGIX-500) ........50
5.3.4.4. Table [0] … The Run-Time Feedback Values From 1746-C (RSLOGIX-500).....51
5.4. Tables [1 20] … Actuator Information Tables..............................................52
5.4.1. Table [1]: Communication Error Status............................................................... 52
5.4.2. Table [2]: Actuator Operational Status................................................................ 54
5.4.3. Table [3]: Discrete Control Mode (Open/Close/Stop) .........................................56
5.4.4. Table [4]: Valve Position Indication … 0 – 100.0% ............................................. 58
5.4.5. Table [5]: Valve Position Setpoint … 0 – 4095 ...................................................59
5.4.6. Tables [6 & 7]: User Analog Inputs #1 & 2.......................................................... 61
5.4.7. Table [8]: Analog Output #1................................................................................62
5.4.8. Tables [9 & 10]: Digital Input Accumulators (Totalizers) #1 & 2..........................64
5.4.9. Table [11]: Valve Position Indication … 0 – 4095 ............................................... 66
5.4.10. Table [12]: Discrete Input Statuses................................................................... 67
5.4.11. Table [13]: Solid State Relay (SSR) Configuration Table .................................69
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page ii
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
5.4.12. Table [14]: Additional Register Being Polled From Entire Network...................71
5.4.13. Table [15]: Additional Block of Registers Being Polled From 1 Actuator........... 73
5.4.14. Tables [16 & 17]: Monitor & Control Discrete Digital Outputs ........................... 76
5.4.15. Table [18]: Actuator System Type ID................................................................ 81
5.4.16. Table [19]: Actuator Firmware Version ID.........................................................83
5.4.17. Table [20]: Modbus Exception Message Response.......................................... 84
5.4.18. Tables [21-24]: TEC2000 Status Inputs............................................................ 86
6. Application Notes ........................................................................................88
6.1. App Note: Performance Tuning ......................................................................... 88
6.1.1. General Practices to Ensure Better Performance................................................88
6.1.2. Reading Run-Time Information from Table [0]..................................................... 88
6.1.3. Loading Table [0] with Configuration Information ................................................89
6.1.4. Behavior if a Delay in Loading Table [0] Configuration Information ..................... 90
6.1.5. Using the “Scan Period” Value ............................................................................91
6.2. App Note: 1746-C Operation – Additional Detailed Information .................. 92
6.2.1. Scan Operation: Determining & Exiting “Network Down” Condition.................... 92
6.2.2. Detailed Description of 1746-C Operation ........................................................... 93
6.2.3. Time Allocated Process Control (Allocated Time Slices)..................................... 94
6.2.4. Preferred Communication Port Operation............................................................ 96
6.2.5. Communication Failure Indications (Low-Level & High-Level)............................. 97
6.2.6. Bringing Units On-Line After a Power Cycle ...................................................... 100
6.2.7. Toggling the Preferred Port to Assist Diagnostics ............................................. 101
6.3. App Note: For Diagnostics - Know the Physical Network Wiring ...............102
6.4. App Note: Memory Maps ................................................................................. 103
6.4.1. Specific Holding Registers Referenced by the Network Master......................... 103
6.4.2. Specific Coils & Inputs Referenced by the Network Master............................... 104
6.4.3. 320A Memory Map … Table for Coils & Inputs (Version 2.0) ............................105
6.4.4. 320A Memory Map … Addressable Holding Registers (Version 2.0) ................ 106
6.4.5. 320B Memory Map … Table for Coils & Inputs.................................................. 108
6.4.6. 320B Memory Map … Addressable Holding Registers...................................... 109
6.4.7. TEC2000 Memory Map … Table for Coils & Inputs........................................... 111
6.4.8. TEC2000 Memory Map … Table for Holding Registers..................................... 112
6.5. App Note: Modbus Message Formats..............................................................117
6.5.1. Modbus RTU Functions (Command Codes) Implemented ................................ 117
6.5.2. Modbus Function (Command) Code Descriptions ............................................. 118
6.5.2.1. Modbus Function Code 01 … Read Coil Status .................................................118
6.5.2.2. Modbus Function Code 03 … Read Holding Register........................................119
6.5.2.3. Modbus Function Code 05 … Set (Force) Single Coil........................................120
6.5.2.4. Modbus Function Code 06 … Set Single Register .............................................121
6.5.2.5. Modbus Function Code 15 (0x0F) … Set (Force) Multiple Coils ........................122
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page iii
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
6.5.3. Modbus Exception Messages Supported .......................................................... 123
6.6. App Note: Install the 1746-C Network Master Firmware............................. 124
6.6.1. Configure the Module for a Firmware Upload .................................................... 124
6.6.2. Upload the 1746-C Firmware............................................................................. 125
6.6.3. Reset the 1746-C Module for Normal Operations.............................................. 126
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page iv
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
0. Quick Start Information
1. As a minimum, you should have access to the following reference documents:
This manual (1746-C User’s Guide)
Allen-Bradley SLC-500 BASIC User's Manual (1746-BAS & 1746-BAS-T)
Publication No. 1746-UM004A-US-P 2000
EIM Controlinc 320A Quick Startup Guide, Rev. F or later
EIM Controlinc 320B Quick Startup Guide, Rev. A or later
2. Refer to Section 2 of this manual on how the jumpers should be set on the BASIC module.
3. The 1746-C module comes from EIM pre-programmed with the network master program in it. However, if for some reason the module needs to be flashed again (ex: a field upgrade) then refer to Section 5 on installing the firmware in the module.
Note: Remember, you will need to connect a serial cable between the 1746-C and the computer. The
correct cable is a Null Modem Cable the module) and the serial communications port on the computer used for the upload.
4. Ensure the PLC rack power is turned off. Install the module in the correct slot in the PLC rack. Connect all cables and power the system up.
5. The PLC-RLL will start interfacing with the 1746-C after the 1746-C performs initial scans of the network on power up.
NOTES: To ensure optimal performance, some things the PLC should do …
1. Ensure table [0] is set correctly and repeated in a timely manner. Allow for frequent table [0] read backs.
2. Restrict the rate of data writes to the actuators … only write as fast as required to adequately control the valve. (cuts down on the interruptions to scanning the network … gathering data)
3. Expedite responses to M1 transfer requests made by the 1746-C. Delaying them can slow 1746-C operations.
4. Only activate writing to or reading from tables if actually in use (or when needed). (ex: do not write to the analog output table if analog outputs are not used) (ex: do not read totalizer data if its not being used) (ex: only poll for “static” [non-changing] data one time and stop)
(prevents unnecessary delays to gathering the more important data from the network)
Remember:
The 1746-C uses explicit read/write commanding of the tables such that if word [1] in any table is
zero (0) then it is a table read request by the PLC. Otherwise, the command is a table write command.
connected between the PRT1 port (top DB9 connector on
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 1
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
1. Introduction
1.1. Overview of 1746-C System
This document is intended for end users as a Guide in applying an EIM AB 1746-C Network Master.
The software that enables network operation is called a communication driver. It is used in conjunction with an Allen-Bradley 1746-BAS module thereby creating the 1746-C network master module. The 1746-C allows an AB SLC-500 controller to acquire data from and send information to an EIM Controlinc Actuator Network.
GENERAL SYSTEM PURPOSE:
The EIM 1746-C network master serves as a data concentrator for applications that use an AB SLC-500 Programmable Logic Controller (PLC). The 1746-C module must be located in a slot in the local chassis (it cannot be mounted in a chassis that is remote from the SLC CPU).
In general, the network master off-loads network communication and management tasks from the actual controlling equipment. The main function of the 1746-C is to provide the interface between a PLC and its network of valve actuators. Acting as a Host, the PLC controls the network by sending data to the 1746-C for routing to a particular actuator. The 1746-C network master polls the individual actuators for information and makes it available to the PLC when requested.
A typical ring topology network and network master are illustrated in Figure 1. The 1746-C module serves as a master within this Modbus (Modbus RTU) master/slave network. The module will manage network operation by keeping an orderly cycle of data transfers between itself and each slave (valve actuator).
SLC-500 with
1746-C installed
1746-C
Figure 1
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 2
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
The 1746-C master will handle network communication, error detection, alarming, and network recovery. Other features include:
Reporting of inaccessible actuators
Reporting of network faults
Emergency shutdown broadcasting
Minimal Interfacing with the Relay Ladder Logic (RLL) program in the PLC CPU module
Each 1746-C module can support a single network of up to 60 valve actuators. Multiple modules can be installed in an SLC-500 system rack to provide support for multiple networks (up to 60 actuators each).
Note 1: It is important to note that the 1746-C Network Master may be used in any slot of the 1746
rack, not just slot 1 next to the SLC-500 CPU.
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 3
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
1.2. Overview of Changes in Version 5.21
For the 1746-C system, there is no previous version of the product to reflect functional changes to.
However, any later releases of this document for this version of the product (5.21) are to only correct entries in this document … primarily grammatical or “typos” that are discovered in the future. Major ideas will be documented with a separate “line entry”.
Major document changes:
1. This document: 2004-11-18 Previous document: 2004-08-17 Major Change: Memory Maps adjusted.
2. New document: 2004-08-17 Previous document: 2004-08-06 Major Changes: Memory Maps adjusted and this section added.
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 4
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
1.3. Reference Manuals
Allen-Bradley SLC-500 BASIC User's Manual (1746-BAS & 1746-BAS-T) Publication No. 1746-UM004A-US-P 2000
This manual is required for installing the module and for proper uploading of this driver into the hardware.
EIM … Controlinc 320A Quick Startup Guide, Rev. F or later Publication No. ECL-4004-0102
This manual is used for specific information on the Controlinc 320A Controller card located in the valve actuator. This includes networking, setup and available options.
EIM … Controlinc 320B Quick Startup Guide Publication No. ECL-4005-0404
This manual is used for specific information on the Controlinc 320B Controller card located in the valve actuator. This includes networking, setup and available options.
EIM … TEC2000 “Document … TBD” Publication No. ?????????
At the time of this printing, this TEC2000 publication had not been made available.
Other Allen-Bradley manuals specific to the SLC-500 being applied. These may be required to
implement the necessary Relay Ladder Logic (RLL) for application of the driver. For instance, this may include:
o Allen Bradley SLC-500 Instruction Set Reference,
Publication 1747-RM001D-EN-P (November-2003)
This reference includes information in Appendix E on the M0 & M1 File Data Transfer handling.
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 5
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
1.4. EIM Equipment Compatibility
The 1746-C is compatible with the following EIM equipment:
320A … version 1.17 and later.
320B … all
TEC2000 … all
Other points:
The 1746-C derives the system type of each actuator during the diagnostic scan and stores the
results in table [18].
The 1746-C derives the firmware Version ID for the 320A & 320B systems during the diagnostic
scan and stores the results in table [19].
Since the TEC2000 system has several micro-controllers with firmware, a special request must
be made to them to derive the firmware version ID for each controller in the unit.
The SSR bit is only checked and set on 320A actuators.
Note: For maximum compatibility with the TEC2000 systems, it is recommended that you enable
monitoring the TEC2000 Status Inputs (tables [21-24]). This way, you can ensure you have all critical status information for any TEC2000 system on the network. For more information, refer to the section on Tables [21-24].
Note: This document references the addressable memory ranges (“Memory Maps”) of several EIM
actuators (ex: M2CP–320B, TEC2000). This is only for the reader’s convenience. The specific details in the memory maps are only correct as of the date this manual was published. Therefore, to ensure you have the most current memory information, please refer to the technical information for that particular actuator.
1.5. Firmware
The firmware is a “driver program” which is a compiled application program (not an interpreted one). It is loaded and stored in the module's 32K EEPROM (A-B P/N 1747-M2). The user is required to provide configuration information from the PLC Relay Ladder Logic (RLL) for each specific application (the RLL must load table [0] with appropriate configuration information).
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 6
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
2. 1746-C Hardware
2.1. Hardware Setup
Refer to Chapter 1 of the 1746-BAS manual. The following hardware jumper settings are required. If the 1746-BAS module was supplied by EIM, jumpers are already set and no other settings are required.
For the 1746-C to run, the jumper settings should be set as follows:
JW1 - enable RS232
JW2 - enable RS232
JW3 - M2 EEPROM
JW4 - PRT1 = ASCII
- PRT2 = ASCII
- DH485 = PGM
This jumper configuration is normally performed by EIM before shipping the 1746-C.
JW1
JW2
JW1
JW3
JW4
JW2
JW4
JW3
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 7
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
2.2. LED Utilization
2.2.1. Green (PRT1 & PRT2) and Yellow (LED1 & LED2) LED Usage
There are 2 “Yellow” LED lights on the front of the 1746-C module
LED1.
LED2.
There are currently 3 general functions operating these LEDs:
1. After CPU restart, both LED1 & LED2 are ON until the 1746-C finishes initialization and starts polling the network.
2. After initialization, LED1 is used as a “starting a new scan” indicator by toggling on/off at the start of each scan. Ex: Starting scan 1: LED1 is ON. Starting scan 2: LED1 toggles to the OFF state. Starting scan 3: LED1 toggles to the ON state.
3. After initialization, LED2 is used as an “entire network is down” indicator. If the 1746-C ever detects zero (0) actuators on the network, it will turn LED2 on and immediately enter a diagnostic scan and remain there until an actuator is found to be on-line and communicating.
There are 2 communication LED lights (green LED lights) on the 1746-C module:
PRT1: Port 1 Transmit … lights up when transmissions are going out port 1.
PRT2: Port 2 Transmit … lights up when transmissions are going out port 2.
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 8
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
PRT1 & PRT2 (Green) LED App Note: Green LED Lights & System Initialization with Table [0]
After startup, if table [0] is not initialized shortly after the 1746-C finishes its initial diagnostic scan, the program starts running with factory default settings. This means that unless the network actually has 60 actuators on it, the 1746-C will believe the “other valves” are just off line. Plus, an operator can often determine when the PLC-RLL actually writes to table [0] (configures the system) by watching the green LED lights.
For instance …
On a network that actually has 25 valves on it (addressed 1-25), until table [0] – word [4]
gets initialized with 25, the program thinks that there are still supposed to be 60 actuators on the network … only the last 35 happen to be “off line”.
Then (if viewing the green LED lights) when a scan starts (LED1 changes state), you will
see the green LEDs “flash” while the 1746-C communicates with valves 1-25.
Then you will observe a “dead space” in time when the program is trying to determine if any of the final 35 valves “it believes to be connected” are available (
are because the network only has 25 valves on it
).
and of course none
As soon as a new scan starts (all “60” valves have been checked and ready to scan the
network again … LED1 changes state) then the green LEDs will start flickering again while the 1746-C communicates with valves 1-25.
Then the “dead space” time will be observed again.
This sequence will repeat until the PLC program initializes the 1746-C by writing to table [0].
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 9
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
2.2.2. Red “BA LOW” LED Usage
The red “BA LOW” LED indicates low battery status. The purpose of the battery in the BASIC module is to back up portions of RAM and other resources. For guaranteed long-term repeatability of operations, the EIM 1746-C program does not utilize any of these resources. Therefore, it doesn’t matter what state the battery is in (installed and fully charged, inline and dead or totally removed from the unit), the EIM network master program will always run the same.
This also means that a new 1746-C module might run with the BA LOW LED off for a while and then turn on when the battery dies. This is normal and has NO effect on the system. However, if for some reason you want to replace the battery, you can order it directly from Allen-Bradley.
“BA LOW”
LED
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 10
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
3. Network Setup and Connecting to the NIU
In general, the EIM NIU (“Network Interface Unit”) is a “beefed up” and configurable RS232 converter.
The ports on the 1746-C, Port1 (PRT1) and Port 2 (PRT2), are configured for serial communication using RS-232.
SLC-500 with
1746-C installed
1746-C
The network communication parameters are pre-configured and fixed at 9600 baud – 8 bit – no parity – 1 stop bit.
The NIU isolates and protects the 1746-C and the PLC from the network and is powered by its own 120 AC circuit. Its primary function is to convert RS232 communications to RS485 communications. The RS485 connection then communicates to a ring or ring network.
Note: To help with isolation, there are two
(2) entirely separate boards in the NIU. However, because of this, there are two (2) 120 VAC connections to the NIU. Ensure
Figure 1
that both are connected (you can jumper the circuits together).
The Controlinc network is connected to the 1746-C module via the Network Interface Unit (NIU). It doesn’t matter if you connect:
Port 2 (PRT2) (bottom DB9 connector): connects to the NIU at the port labeled “HOST A”.
Port 1 (PRT1) (top DB9 connector): connects to the NIU at the port labeled “HOST B”.
or
Port 1 (PRT1) (top DB9 connector): connects to the NIU at the port labeled “HOST A”.
Port 2 (PRT2) (bottom DB9 connector): connects to the NIU at the port labeled “HOST B”.
However, it is recommended that you remain consistent.
NOTE: You can always connect a PC to the network at the NIU if you …
Disconnect the cable connecting the 1746-C and NIU.
Connect the PC using a (serial cable + NULL modem) to the DB9 connector on the NIU.
 RS485
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 11
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
A typical E>Net network connection format is in a ring …
It starts from Port 1 (PRT1) (the top DB9 connector) on the 1746-C as RS232 and connects to
the NIU at the port labeled “Host A”.
It exits the NIU at the port labeled “Port A” as an RS485 circuit and proceeds to the first valve
actuator, normally addressed as #1, in port A.
It exits the actuator from Port B and proceeds to the port A next actuator (address #2) and on
until the last actuator on the network is connected.
The RS485 network then exits port B on the last actuator returns to the NIU at the port labeled
“Port B”.
The network connection is then transformed back to an RS232 format and exits the NIU via the
port labeled “Host B”
It connects to the 1746-C via port2 (PRT2) (the bottom DB9 connector).
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 12
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
3.1. Field Connections at the Actuator
Communication connections and wiring are important for the network and the master.
(
3.1.1. Step 1. Plan the Network Topology
Before connecting actuators, the entire network layout should be planned. Topologies may be bus, redundant bus, E>Net, redundant E>Net, E>Net ring, and redundant E>Net rings. Planning should include node addressing, wire routing, terminations, and grounding.
3.1.2. Step 2. Select Network Cable
Ensure correct cable is being used.
The following are acceptable Belden or equivalent cables for most network applications.
The following information was primarily derived from the Controlinc Quick Startup Guide)
Networks require twisted pair and shielded cable with characteristic impedance between 50 and
120 Ohms.
Capacitance between conductors must be less that 30 pF/Ft (98 pF/M); 10-15pF/Ft is ideal.
Shielding maybe aluminum foil with drain wire.
If cable has multiple pairs, then individual pair shielding is required.
Only cables with stranded conductors are recommended.
Insulating and outer jacket materials must be selected for the application environment.
AWG 20 18 16 14 Beldon # 8762 8760 8719 8720 Rating 12.8 Pf/fT 12.8 Pf/fT 12.8 Pf/fT 12.8 Pf/fT
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 13
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
3.1.3. Step 3. Route Cable away from Electrical Interference
Network cables should enter the electrical enclosures and the bottom or lowest point (on 320A systems, this is near the transformer end and normally in a counter clockwise direction to the topside of the TBM). Never install network cable in the same conduit with power conductors. Never route the network cable through the high voltage contactor area. On 320A systems, the cable should never lie across the TBM or hinder the protective cover of the TBM. Always use the shortest distance and keep access cable to a minimum.
See Figure 3-1
3.1.4. Step 4. Observe Polarity and Network Grounding
Each network connection is polarized + and - on wiring diagrams. Always use consistency in wiring and the use of wire colors to track polarity. The cable shield (or “drain wire”) must be connected to the designated “shield” terminal at each port of each actuator. The shield must be connected to earth ground at only one point. Some networks require a jumper between the shield connections on ports A & B of the actuator to carry the shielding through the network. The shield connection of each actuator is isolated from earth ground. Do not allow the shield to touch other circuits or the metal enclosure.
Figure 3-1
Correct termination of the Network
to a Controlinc 320A Actuator
3.1.5. Step 5. Wire Preparation and Connections
Screw terminal connections on the TBM and in the TEC2000 terminal chamber have wire clamps, which will accept conductors with out terminals. Wire terminals may be applied if desired but are not required. Strip conductor insulation back 3/8” when connecting directly to the TBM screw terminals. Do not allow wire clippings to fall on the TBM or into the enclosure. Protect the conductors and shield to prevent them from contacting any other circuits or earth ground. Use plastic electrical tape or heat shrink tubing to prevent bare conductors from contacting other circuits or earth ground.
See Figure 3-1
3.1.6. Step 6. Test Network
Use EIM’s Configuration and Control Utility (CCU) to test the network prior to connecting to the host or network master. The CCU is a Windows application, which will run on a laptop. Use a RS232 to RS485 adapter or EIM’s Network Interface Unit (NIU) to connect the laptop to the network. Test each actuator, one at a time, to determine that all network connections are good and each actuator is functional via the network in remote.
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 14
W
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
3.2. Field Network Cable Connection to the NIU
Refer to Figure 3-2 for terminals on the EIM Network Interface Unit (NIU). The NIU is a dual port RS232 to RS485 converter specifically designed for ring networks.
Connect the twisted shielded pair cable of the field network to NIU Terminals 1 (-), 2 (Shield), 3 (+) of J1 of Port A.
The network shield must be connected to a good earth ground at only one shield terminal point on the NIU.
The network cabling should use recommended cabling for an RS-485 network able to handle the distance desired.
There should be little, if any, electrical noise on the network for the entire length of the network.
Ne twor k Por t
J1
+
+
Shield
sh
-
-
1
SW1
RXD
TXD
Ground
DB-9 Female
Connector
(1746-C Side)
2
3
5
R S - 2 3 2
R
P
P o r t
2 V A C / D C
1
J3
1
RS232 Cable
J 2
P W R
N I U 8 4 3 2 0
(#37121)
Shield
Figure 3-2
DB-9 Male Connector (NIU Side)
Chassis
1
RXD
2
TXD
3
Ground
7
PWR
TxD
RxD
3.3. Cable Connection Between the NIU and the Network Master
Refer to the “
No. 1746-UM004A-US-P 2000”
used for network ports one and two.
Jumpers JW1 & JW2 must be set for RS-232 when connecting with EIM's Network Interface Unit (NIU) P/N 84320 or a user-supplied modem.
Refer to Figure 3-2 for the pin-out of the DB-9 female connector.
Allen-Bradley SLC-500 BASIC User's Manual (1746-BAS & 1746-BAS-T) Publication
for additional information on the pin-out of the male DB9 connections
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 15
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
4. 1746-C General Theory of Operation
4.1. Operational Overview
The interface for the PLC with the actuators (through the 1746-C module) is with an array of 25 tables … 64 words per table with the table number (command) in Word # [0] of each. This is based on the M0/M1 interface protocol established by Allen-Bradley for the SLC-500 systems.
The 1746-C operates using a “Non-Interruptible Time-Slice Process Allocation methodology. This means that it must finish executing the process that is executing in its allocated time-slice before another process can operate. The two processes being scheduled are:
Scanning the network for data.
Interfacing with the PLC.
This means that the 1746-C will ignore any new commands from the PLC while scanning the network (during the network scan time-slice) and no network scanning will take place while processing a command from the PLC (during the PLC interface time-slice).
” communication
4.1.1. Diagram Describing Relationship Between Process Time Slices
Process time slicing is how the 1746-C divides its time when performing its 2 primary communication tasks … communicating with the PLC and communicating with the actuator network.
This diagram helps demonstrate the relationship between the two communication processes.
PLC
PLC  1746-C
Communications
(PLC Interface Time Slice)
1746-C
1746-C Actuators on
Network Communications
(Network Scan Time Slice)
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 16
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
4.1.2. Diagram Describing Network Scanning & Actuator Writing Logic
This example demonstrates how a normal scan cycle gets elongated with data writes to the actuators. The more writes being performed the longer it will take to complete data scans. This is where the PLC/HMI must make a value decision for the best fit for their application:
Fast enough repetitive writes to control the system
Slow enough repetitive to ensure effective feedback to control the system.
Polling
for data
Time to poll 30
actuators for
data … without
any writing to
actuators
Polling
for data
actuators for data …
Performing 3 sets of
interspaced within
the single scan loop
Time to poll 25
data writes
Polling
for data
Polling
for data
Polling data …
“Network Scan
Time-Slice”
Writing
data
Writing data to the network … “PLC Interface
Time-Slice”
Writing
data
Writing
data
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 17
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
4.1.3. Diagram Demonstrating Adding Additional Valves in Valve Scan Time-Slice
This example demonstrates how increasing the additional number of valves to be scanned before servicing the PLC communication task decreases the total network scan time.
This is where the PLC/HMI must make a value decision for the best fit for their application:
Increasing the number: Speeds up data collection Lowers PLC control capabilities.
Decreasing the number: Slows down data collection Increases PLC control capabilities.
Example of scale for time to scan network … different values for Additional valves in scan time slice:
Network size: 8 Network size: 8 Additional valves: 0 Additional valves: 3
(Note the relative time differences are for illustration purposes only … not to any exact scale.)
Poll 1 valve for data
Service PLC cmd
Poll 1 valve for data
Service PLC cmd
Poll 1 valve for data
Service PLC cmd
Poll 1 valve for data
Service PLC cmd
Poll 1 valve for data
Service PLC cmd
Poll 1 valve for data
Service PLC cmd
Poll 1 valve for data
Service PLC cmd
Poll 1 valve for data
Service PLC cmd
Poll 4 valves for data
Service PLC cmd
Poll 4 valves for data
Service PLC cmd
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 18
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
4.1.4. Diagram Describing Relationship Between Scan Period & Diagnostic Scan
This example demonstrates the relationship between the diagnostic scans, scan periods, the current scan period, the previous scan period.
This example: a scan period value of 10 and 25 valves on the network. This means that all the valves on the network will be scanned 10 times before the scan period is over … and before the next diagnostic scan is performed.
(all 10 network scans of 25
Previous
Scan Period
valves completed)
Diagnostic
scan
Individual
network scans
Diagnostic
scan
Current
Scan Period
(so far, 5 network scans
completed)
Current time History
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 19
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
4.1.5. 1746-C System Operations at Power Up
The 1746-C software boots up on a power up of the 1746-C module. The general sequence is:
1. Illuminate LED1 & LED2 as an indication that the software is initializing itself and the network.
2. Perform basic internal initializations.
3. Perform the initial diagnostic scan of the network and identify all actuators on the network.
4. Finish internal initializations.
5. Turn off LED1 & LED2.
6. Start standard scanning of the network. Initialization is finished. Normal operations (scanning) have commenced and are allowing PLC communications. (LED1 toggles ON during the start of this first scan)
Note 1: Remember that the PLC cannot perform any block transfers until after the network master has
finished polling the network for status information and LED2 has been turned off and the 1746-C starts indicating that it is ready for data (after scanning starts).
Note 2: Even though LED1 turns off immediately after the initial scan after power up and then toggles
back on after normal operations start, the user will not normally see this … at the most it would be a small flicker. Therefore, to the user that is observing the LED behavior after restart on a system that has actuators communicating, it will appear that …
During the initial scan when the PLC cannot talk to the 1746-C … LED1 == ON LED2 == ON.
Immediately after the initial scan when normal operations start (start of 1 LED1 == ON LED2 == OFF.
st
normal scan):
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 20
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
4.2. Network Interface (Scan) Time-Slice (1746-C ↔ Network Communication)
4.2.1. Operation: Network Scanning to Gather Valve Actuator Data
The Network Master polls and controls up to 60 valves on the network by sequentially polling (scanning) each device in sequence from slave actuator address #1 to the last slave address (#n) on its network. This polling gathers information from the actuators (including alarms, discrete information and actuator position) and places it in tables that can be transmitted to the PLC.
The scan operation cannot stop in the middle of a request for data from a particular actuator. Therefore, the 1746-C can only interface with the PLC once it has finished all required communications with the actuator it is currently getting data from. Network scanning resumes with the next actuator after interfacing with the PLC and processing any requests made by the PLC (writes to tables, writes to actuators, table reads, …).
For example, if the 1746-C is currently scanning actuator [5] and the PLC wants to write a new valve position setpoint to 22 actuators then the 1746-C will …
1. Finish getting data from actuator [5]
2. Get the new command table from the PLC.
3. Write the new valve position setpoint to all 22 actuators.
4. Restart network scanning where it left off … the next actuator [6] after the last one polled [5].
Standard data is gathered from the actuators by a single Modbus 03 command. However, a 2
If requesting totalizer data
If requesting a specific holding register
If requesting a block of holding registers from this actuator
If requesting to monitor the discrete outputs on this actuator
If requesting TEC2000 input data.
This is one reason why additional data should only be requested when needed … it will slow the entire scan time of the system (by a minimum of 30-50 ms each time an actuator is polled for this data). For instance, if all 5 of the above are requested for each actuator, an extra 30-50 ms is required for EACH … meaning that the scan time could be increased by almost a factor of 5! … dramatically slowing down the system!
A typical scan time (time to scan all the actuators on the network) to gather “standard” information on 60 actuators is less than 10 seconds … depending upon the 1746-C configuration.
When gathering data, the data is stored in the appropriate tables in the 1746-C. Values in the table for a particular actuator will not be overwritten if there is an error communicating (on both ports) with the actuator.
nd
Modbus 03 command is generated if any of the following are true …
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 21
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
4.2.2. Operation: The Network Communication Diagnostic Scan
After a predetermined number of loops through the network scanning the actuators (the “scan period”), the 1746-C performs a communication diagnostic scan to determine if any “off-line” actuators can come back on line. If there are any that are ready, the 1746-C will bring them back on line without human intervention. This is the only time an off-line system can come back on-line.
The number of loops around the network is determined by the “scan period this value to accommodate site requirements and current operating environments.
Unlike the other operations that access the actuators on the network, the diagnostic scan checks both ports when communicating with the actuators. Because of this, it also always takes longer to execute than standard data gathering scans. However, normal data is still gathered during a diagnostic scan.
The only major difference in data gathering between a standard scan and a diagnostic scan is
In the diagnostic scan, the 1746-C determines actuator system type and actuator firmware
version ID (tables [18 & 19]).
Both ports are explicitly tested when getting the system type information.
The diagnostic scan ensures that the hardware ports are set correctly … 9600 - 8N1.
Otherwise, all other data gathering activities are the same as in a normal network scan.
Communication error indications may only be cleared during this scan.
The “scan loop counter
” is always zero (0) during a diagnostic scan … the diagnostic scan does not count as part of the scans in the scan period. This is the only time the loop counter is zero … during the diagnostic scan.
The diagnostic scan time increases as you increase the discrepancy between the
(number of valves actually on line and talking
) VS (the number of valves configured to be on line)
Below shows a sample of diagnostic scan times empirically taken on a network when there was no network “writes to the actuators” (Table [0] was configured for 60 valves). As you can see, as you increase the number of “off line” units, you increase the diagnostic scan time.
# Nodes “Talking” … On-Line
60 of 60 (#1 – 60) 15 54 of 60 (#7 – 60) 16 48 of 60 (#13 – 60) 17 42 of 60 (#19 – 60) 18 36 of 60 (#25 – 60) 19 30 of 60 (#31 – 60) 20 24 of 60 (#37 – 60) 21 12 of 60 (#49 – 60) 23 6 of 60 (#55 – 60) 23 3 of 60 (#58 – 60) 24 2 of 60 (#59 – 60) 25 1 of 60 (#60) 25
Diagnostic Scan Times (secs)
Version 5.21
” value. The PLC adjusts
The values in this table
“rounded values” and
have a precision of (+/-) 1
second.
Because of this, these
numbers are only
appropriate for estimates
and trend analysis.
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 22
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
Notes:
Though not much, the diagnostic scan time can also vary with the number of valves in the valve
scan time slice.
The greater the number of valves configured to be on line, the longer the diagnostic scan time
… more valves to check.
During normal operations, an operator can use the HMI to force the system into a diagnostic
scan by temporarily changing the “scan period” value in table [0] to a value lower than the current scan loop counter. This will cause the program to enter a diagnostic scan as soon as this scan loop has finished.
Because the diagnostic scan detects faulty communication ports and flags them, there can be a
perceived increased performance in the normal network scans because “off-line” actuators have already been flagged and will be skipped.
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 23
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
4.3. PLC Interface Time-Slice (1746-C ↔ PLC Communication)
The primary interface for the PLC with the 1746-C module is with an array of 25 tables (labeled 0 24) stored in the 1746-C RAM. Each table is 64-words long and each word is 16-bits. From the perspective of the PLC interfacing with the network, some of the tables are “read only” and some are “read/write” (depending upon a command word).
Relative to M0/M1 transfers, from the 1746-C perspective, there is no difference in handling “table reads” or “table writes” … they both require a M0/M1 file transfer command.
The Relay Ladder Logic (RLL) in the PLC CPU interfaces with the 1746-C module with the M0/M1 file transfer mechanism and transferring fixed blocks of 64 words (a table) with the table number (command) in Word # [0] of each transfer.
To send a table to the 1746-C (either as a write table command or to indicate a particular table
to read back), the PLC must send the desired table in the data portion of the M0 file.
To read back a table, the PLC must read the M1 file sent from the 1746-C.
Note: Since the 1746-C must be mounted in the local chassis (in the same chassis as the CPU), the
RLL cannot use the BTR/BTW block transfer command set (BTR/BTW commands cannot be used over the back plane in the SLC systems). Therefore, the RLL must implement the transfer using the “copy file” command … copying the M0/M1 files back and forth.
Note: Refer to the following Allen Bradley Documents:
Allen Bradley SLC-500 Instruction Set Reference, Publication 1747-RM001D-EN-P (November-2003)
Allen-Bradley SLC-500 BASIC User's Manual (1746-BAS & 1746-BAS-T) Publication No. 1746-UM004A-US-P 2000
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 24
p
k
uffer (BOB)
r
uffer (
)
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
The interfacing between the PLC and the 1746-C is performed in the 1746-C module in a section of RAM that is used as an exchange buffer area. To prevent potential overwriting problems when performing transfers, there are two separate buffers in this exchange area:
M0 file … Basic Input Buffer (BIB): PLC fills to send 64 words to the 1746-C.
M1 file … Basic Output Buffer (BOB): 1746-C fills to send 64 words to the PLC.
This is the only address accessed by the PLC when executing the M0/M1 transfer commands (meaning that all reads & writes by the PLC are to and from these buffers).
PLC must read the
M1 file in timely
manner as to not
slow down networ
scanning
PLC
M0 File Transfer
commands
executed by the
PLC
PLC
The PLC must ensure the M0 file is there fo
the 1746-C to read in
a timely enough
manner as to not
slow down network
scanning
M1 File Transfer
commands
executed by the
1746-C
64-Word M1 File Transfer
B
The 1746-C looks
for an M0 file
transfer at the start
of the PLC Interface
time slice
64-Word M0 File Transfer
BIB
B
1746-C
1746-C driver
erations
o
Standard RAM
(Tables)
MODBUS RTU
commands
executed by the
1746-C and
actuators
ACTUATOR
Figure 3-1 Concept Diagram of Command Operations
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 25
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
4.3.1. Operation: PLC (Write Data Tables To) or (Read Tables From) the 1746-C
Relative to M0/M1 transfers, from the 1746-C perspective, there is no difference in handling
Writing a value to any table in the 1746-C memory.
Writing a value to a table in the 1746-C memory that is also passed on to the specified actuator
on the network.
They both require a M0 file transfer command. The only difference is in the 2 transferred (word [1]).
If word [1] == 0, then this M0 transfer is a command to read a table from the 1746-C.
If word [1] =/= 0, then this M0 transfer is a command to write data to a table in the 1746-C.
To perform a transfer of table data:
1. The PLC interface time-slice has now started.
2. The 1746-C looks to see if a new M0 file has arrived from the PLC. If not, this operation terminates and must be restarted on the next PLC interface time slice. Otherwise, continue.
3. Since a new M0 file is here, the 1746-C copies the table into its own memory.
4. If word [3] indicates an ESD command sequence (start or stop the ESD condition) then that is outputted to the entire network of actuators on both ports.
5. If word [1] == 0, then a read-only request command was made and the appropriate table is copied into the M1 exchange buffer.
If word [1] =/= 0, then this was a write command and this table is copied into 1746-C memory. A final “resultant” table (what will be stored in the 1746-C and potentially sent out onto the network) is then copied into the exchange buffer to be fed back to the PLC.
6. The new M1 file is prepared to be transferred to the PLC such that if the received M0 file indicated
A read command – the data the PLC requested in a read table command.
A write command – the immediate feedback of the command structure the 1746-C is
about to execute.
7. The 1746-C looks to see if the last M1 file was already read.
8. The new M1 file is transferred after the PLC indicates that the previous M1 file was read or the 1746-C system times waiting for the previous M1 to be read. Note that if the 1746-C times out waiting, the previous M1 file will be overwritten.
9. After the M1 file is sent, if the command was to write data to the actuators, the 1746-C will now loop through and write to all “appropriate” actuators on the network.
10. The PLC interface time-slice is now finished.
nd
word in the block being
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 26
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
As per affecting network performance,
unless the command is to write data to the actuators, the
PLC does not have to limit the rate in which these commands are sent to the 1746-C because the 1746-C only sends back the table information it already has stored in memory. Conceptually, these do delay the overall scan time. However, the amount of delay is very minor from a global perspective.
Obviously, the PLC must still ensure all appropriate M0/M1 TRANSFER handshaking is performed)
(
As per writes that send data to the actuators, the rate should be limited. Please refer to the section that discusses writing data to the actuators on the network.
Note 1: All tables can be read by the PLC. To ensure you only read from a read/write table, access it
with the command word set to “0” (zero).
Note 2: An invalid table ID sent to the 1746-C will default to a read request for table [0] data.
Note 3: If the 1746-C times out waiting for the previous M1 file to be read by the PLC, the previous M1
file will be over-written.
Note 4: On write commands from the PLC, reading the immediate feedback is optional for the PLC. In
other words, if the PLC has no need to inspect this table, then it can read it back but just throw it out. However, servicing the M1 transfer request is important to overall system throughput.
For instance, the PLC program might be architected such that it treats an output pipe (“command”) as just that … a one-way pipe that has no feedback. In this case, the PLC would use other mechanisms for feedback (ex: other tables) and does not require the redundant feedback on write commands.
Note 5: When a request for an M1 transfer is made by the 1746-C, the 1746-C program waits (in the
respective request function) until either the transfer completes or until a timeout is triggered (currently set at 2 seconds).
This extended timeout time is to assist a PLC program that is having other (hopefully temporary) difficulties and might take a while to return to normal behavior.
Therefore, to not slow down 1746-C network scanning activities, the PLC-RLL needs to service these requests as soon as possible … even if it is to only throw away the table read back. Servicing the request for an M1 transfer made by the 1746-C is critical for overall timing efficiency.
Note 6: One main point to remember on M0/M1 transfer timing is that once the 1746-C responds to an
M0 transfer, the 1746-C will not return to process (setup for) another M0 file from the PLC until it:
responds with an immediate feedback M1 file transfer request containing the table being addressed.
finishes writing the entire table of values to the valves (if a write command).
completes the set of scans in the next network scan time slice
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 27
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
Note 7: Once the 1746-C reads in a table from the M0 file, the 1746-C will always deliver the
feedback table almost immediately … whether or not it was a read or write table command. Therefore, the best practice to maintain synchronization between the PLC and 1746-C is for the PLC to “conceptually” wait for a feedback response from the 1746-C before continuing … even if only to throw away the table. This will also increase the 1746-C overall speed because it waits for an acknowledgement of the feedback before continuing with command execution.
REMEMBER … Speed in servicing of the M1 transfer requests expedites system throughput.
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 28
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
4.3.2. Operation: PLC Commands to Write Data to the Actuators
When valve control commands (change setpoint, open, stop or close) are generated by the PLC, the Network Master sends the appropriate command(s) over the network to the addressed slave device (actuator).
However, if the command for a particular valve has not changed (value in the table is the same as before), then nothing is sent to the particular valve (it is skipped). Basically, when the 1746-C starts acting on a command to write data to the actuators, it compares the current value in the table with the new one. If the values are different, then the actuator is flagged as one to write information to.
When writing discrete output control commands (directly controlling coils [3-5] or [100-1011]), the 1746-C does NOT compare the value to the last one. When commanded to write to the coils, it is performed ONE TIME and then turned off for that actuator (however, monitoring the status of those outputs is left on for that actuator).
When the 1746-C starts writing data to the actuators, is starts with the lowest address number and proceeds through to the highest address number. This write operation is completed after all “appropriate” actuators have been written to.
In general, there is one Modbus command/response set issued for EACH PLC command to write data to a particular actuator (ex: writing analog output data).
However, as per the specification, when a position control command is issued, the 1746-C is required to ensure that a “SSR” contactor configuration bit is set on any 320A system prior to receiving a control command. Therefore, there are up to 3 Modbus command/response sets issued for EACH PLC command to write position data in any particular 320A actuator: If the actuator is configured to have an SSR in it (table [13]):
1. A Modbus command is sent to the actuator requesting status information to verify the SSR configuration coil is set.
2. If the coil is not set, a Modbus command is sent to set it.
3. The Modbus command is sent to indicate the new setpoint.
Note 1: Discrete OPEN / CLOSE / STOP commands.
The discrete OPEN / CLOSE / STOP commands (in table 3) are handled exactly the same as if a setpoint was sent.
OPEN (send a 100% open setpoint)
CLOSE (send a 0% open setpoint)
STOP (send a setpoint matching the last position read)
(For more information on how this works, refer to the actuator’s operation manual)
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 29
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
Note 2: If writing to a valve and the write fails, then the internal flag to write the value REMAINS
ACTIVE. This means that even though the communication process will prevent the program from trying to transmit when there is an error, the program will keep this value identified as one to send out until it is actually sent out or cleared by the PLC.
This also means that the write to this particular actuator will be attempted the next time the PLC sends this table in with a “write table” command associated with it. For example … If this was a value in table [5], the 1746-C will retry writing the value to the actuator the next time the PLC sends table [5] in as a write command.
The 1746-C cannot “cancel” this command because it is not in its scope of responsibility to directly change process control commands. Therefore, it is the PLC’s responsibility to write whatever “safe” value is appropriate for the particular actuator/application at any time in case the actuator “comes back online”.
Note 3: The PLC should limit the rate in which these commands are sent to the 1746-C … only write
as fast as required to adequately control the valve. The faster the PLC requests changes to valve setpoint positions in the valves, the longer it takes the 1746-C to complete the write operation and continue scanning the network for data … decreasing the overall performance concerning updating status information for all actuators on the network.
For example
: Sending write commands once per second might still afford good control and still update all status information. However, sending write commands 4 times a second might write the information out faster but delay the response (status) information for the entire network to a point where it is too difficult to control.
Warning: If the valve has been moved while the PLC is down or the valve was moved while in local
mode, then as soon as the valve is communicating and accepting remote commands, it will move according to values in tables [3] and [5]. Please adjust the PLC RLL accordingly.
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 30
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
4.3.3. RLL Example … Manually Send New Table … Auto Read Response
Below is a simple example of an RLL that will manually send a table in a BTW and read back the resulting feedback table using a BTR.
On the next page is an example of the M0 & M1 files (tables) sent and received.
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 31
r
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
Control & Feedback via the N10 & N11 files … (table [19] requested … only 3 actuators on network)
Table
sent in
with the
M0 file
Table Number
Sent in
Table
read back
with the
M1 file
4-word
heade
3 Nodes on
Network
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 32
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
5. System Tables
From the perspective of the PLC, all tables can be read but only some can be written to. If the PLC attempts to perform a write to a “read-only” table, the 1746-C ignores it and treats it as a read command/request.
In general, when writing data to be transmitted to the actuators over the network, the Network Master will differentiate which values change in tables being received from the PLC and will only send new command information to the actuators that require a change.
The tables have the following PLC (“user”) access:
Table [0]: read / write
Table [1]: read only
Table [2]: read only
Table [3]: read / write
Table [4]: read only
Table [5]: read / write
Table [6]: read only
Table [7]: read only
Table [8]: read / write
Table [9]: read / write
Table [10]: read / write
Table [11]: read only
Table [12]: read only
Table [13]: read / write
Table [14]: read / write
Table [15]: read / write
Table [16]: read / write
Table [17]: read / write
Table [18]: read only
Table [19]: read only
Table [20]: read / write
Table [21]: read / write
Table [22]: read / write
Table [23]: read / write
Table [24]: read / write
Table [0] is a “system focused” table. It is focused on information about the network system and network master. All the rest of the tables are focused on information about individual actuator “units”.
NOTE: In tables [1 24 … except 15], the last 60 words hold information for particular actuators.
Words [4 actuator is represented by its end of the header). For instance, Word [7] in all tables will always have valve #4 information.
63] are in sequence with valve actuator network node addresses. A particular
POSITION in the table as an offset starting from word [3] (the
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 33
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
There are two parts to a table:
General Header Information: Words [0 3]
Table Specific Information: Words [4 63]
In table [0], words [4
63] are divided into three parts:
Words [4 17]: System Configuration Information
Words [18 46]: -reserved- … currently not used.
Words [47 63]: Run-time information inserted by the 1746-C.
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 34
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
5.1. Table Arrangement
Table [0]
System
Info Table
Word offset
into
table
Read / Write
Table #
0
R / W
1
Command
Reserved
2
(F/W ID
3 ESD ESD ESD ESD ESD ESD ESD ESD ESD ESD ESD ESD ESD ESD ESD ESD
# Valves
4
Network
5
Period
6
Totalizers
7
~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~
See table [0]
63
Command to Monitor
Word
offset into
&/or Control Discrete
table
0 1 R / W 0 0 0 R / W R / W R / W R / W R / W
2
3 ESD ESD ESD ESD ESD ESD ESD ESD ESD
4
Discrete Output Cmd
5
Discrete Output Cmd
6
Discrete Output Cmd
7
Discrete Output Cmd
~ ~ ~ ~ ~ ~ ~ ~ ~ ~
63
Discrete Output Cmd
Table [1]
---­Comm.
----
Status
Table #
0x00
Reserved
(F/W ID)
Valve #1
on
Comm Status
Scan
Valve #2
Comm
Size
Status
Valve #3
Poll
Comm Status
Valve #4
Comm Status
Run-Time
Valve #60
Information
Comm
Configuration &
Status
Table [16]
----
Digital Outputs
Read / Write
Table #
0x10
Reserved
(F/W ID)
Valve #1
Valve #2
Valve #3
Valve #4
Valve #60
Table [2]
---­Interpreted
Error
Status Bits
---­Reg [06]
Read Only
Table #
0x01
0 0 R / W 0 R / W 0 0 R / W R / W R / W 0 0 R / W R / W R / W
Reserved
(F/W ID)
Valve #1
Valve #2
Valve #3
Valve #4
Status of Discrete
Discrete Out Status
Discrete Out Status
Discrete Out Status
Discrete Out Status
Discrete Out Status
Table [3]
----
Valve
Read
Status
Status
Status
Status
Valve
Status
Digital Outputs
Discrete
---­(O / C / S)
Only
Table #
0x02
Reserved
(F/W ID)
Valve #1
Valve #2
Valve #3
Valve #4
#60
Table [17]
----
Read / Write
Table #
0x11
Reserved
(F/W ID)
Valve #1
Valve #2
Valve #3
Valve #4
Valve #60
Control
Control
Read /
----
Valve
----
----
----
Write
0x03
AOCS
AOCS
AOCS
AOCS
Valve
#60
AOCS
Table [4]
----
Valve
Position
Feedback
----
0 – 100%
in 0.1%
increments
----
Read
Only
Table #
0x04
Reserved
(F/W ID)
Valve #1
POS
0 – 100.0%
Valve #2
POS
0 – 100.0%
Valve #3
POS
0 – 100.0%
Valve #4
POS
0 – 100.0%
Valve
#60
POS
0 – 100.0%
Table [18]
----
System Type
Read Only
Table #
0x12
Reserved
(F/W ID)
Valve #1
System Type
Valve #2
System Type
Valve #3
System Type
Valve #4
System Type
Valve #60
System Type
Table [5]
----
Valve
Control
----
Valve
Setpoint
----
0 - 4095
----
Read /
Write
Table #
0x05
Reserved
(F/W ID)
Valve #1
STPT
Valve #2
STPT
Valve #3
STPT
Valve #7
STPT
Valve
#60
STPT
Table
[6]
----
Analog
Input #1
----
Read
Only
Table #
0x06
Reserved
(F/W ID)
Valve #1
AIN-1
Valve #2
AIN-1
Valve #3
AIN-1
Valve #4
AIN-1
Valve
#60
AIN-1
Table [19]
----
Firmware
Version ID
Read Only
Table #
0x13
Reserved
(F/W ID)
Valve #1
Firmware ID
Valve #2
Firmware ID
Valve #3
Firmware ID
Valve #4
Firmware ID
Valve #60
Firmware ID
Table
Table [8]
[7]
----
----
Analog
Analog
Output #1
Input #2
Read
Only
Table #
0x07
Reserved
(F/W ID)
Valve #1
AIN-2
Valve #2
AIN-2
Valve #3
AIN-2
Valve #4
AIN-2
Valve
#60
AIN-2
Table [20]
Modbus Exception
Response
Indications
Read / Write
Reserved
Exception Code
Exception Code
Exception Code
Exception Code
Valve #60
Exception Code
----
----
Table #
0x14
(F/W ID)
Valve #1
Valve #2
Valve #3
Valve #4
----
Read /
Write
Table #
0x08
Reserved
(F/W ID)
Valve #1
AOUT
Valve #2
AOUT
Valve #3
AOUT
Valve #4
AOUT
Valve
#60
AOUT
Table [9]
----
Totalizer
#1
----
Read /
Write
Table #
0x09
Reserved
(F/W ID)
Valve #1
TTL - 1
Valve #2
TTL - 1
Valve #3
TTL – 1
Valve #4
TTL - 1
Valve
#60
TTL - 1
Table [21]
TEC2000 Inputs
[1000 – 1015]
Reg [1000]
Read / Write
Table #
0x15
Reserved
(F/W ID)
Valve #1
Inputs [1000-1015]
Valve #2
Inputs [1000-1015]
Valve #3
Inputs [1000-1015]
Valve #4
Inputs [1000-1015]
Valve #60
Inputs [1000-1015]
----
Table [10]
----
Totalizer
#2
----
Read /
Write
Table #
0x0A
Reserved
(F/W ID)
Valve #1
TTL - 2
Valve #2
TTL - 2
Valve #3
TTL - 2
Valve #4
TTL - 2
Valve
#60
TTL - 2
Table [11]
Reserved
TEC2000 Inputs
[1016 – 1031]
Inputs [1016-1031]
Inputs [1016-1031]
Inputs [1016-1031]
Inputs [1016-1031]
Inputs [1016-1031]
----
Valve
Position
0 – 4095
reg [14]
----
Read
Only
Table #
0x0B
(F/W ID)
Valve #1
POS
0 – 4095
Valve #2
POS
0 – 4095
Valve #3
POS
0 – 4095
Valve #4
POS
0 – 4095
Valve
#60
POS
0 – 4095
Table [22]
----
Reg [1001]
Read / Write
Table #
0x16
Reserved
(F/W ID)
Valve #1
Valve #2
Valve #3
Valve #4
Valve #60
Table [12]
Status Bits
Discrete
Digital
Input s
reg [05]
Read
Only
Table #
0x0C
Reserved
(F/W ID)
Valve #1
Status
Valve #2
Status
Valve #3
Status
Valve #4
Status
Valve
#60
Status
Table [13]
----
for
----
Table #
Reserved
(F/W ID)
Valve #1
Valve #2
Valve #3
Valve #4
Table [23]
TEC2000 Inputs
[1032 – 1047]
Reg [1002]
Read / Write
Reserved
Inputs [1032-1047]
Inputs [1032-1047]
Inputs [1032-1047]
Inputs [1032-1047]
Valve #60
Inputs [1032-1047]
----
SSR
Config
----
Read /
Write
0x0D
SSR
SSR
SSR
SSR
Valve
#60
SSR
----
Table #
0x17
(F/W ID)
Valve #1
Valve #2
Valve #3
Valve #4
Table [14]
----
Additional
Register to
Poll from
All Valves
on Network
Read /
Write
Table #
0x0E
Reserved
(F/W ID)
Valve #1 Add Reg
Value
Valve #2 Add Reg
Value
Valve #3 Add Reg
Value
Valve #4 Add Reg
Value
Valve
#60
Add Reg
Value
TEC2000 Inputs
Inputs [1048-1063]
Inputs [1048-1063]
Inputs [1048-1063]
Inputs [1048-1063]
Inputs [1048-1063]
polled from a
Table [24]
[1048 – 1063]
Reg [1003]
Read / Write
Table #
Reserved
(F/W ID)
Valve #1
Valve #2
Valve #3
Valve #4
Valve #60
Table [15]
----
Block of
Registers
particular
valve.
Read /
Write
Table #
0x0F
Reserved
(F/W ID)
Valve #
Valve
(Actuator)
Type
Starting
Register
Number
Number of
Registers
See
Table [15]
Description
----
0x18
Figure 5-1 Table Arrangement
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 35
t
t
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
EXAMPLE OF GENERAL TABLE FORMAT …
Characteristics:
48 node network
Table [1] feedback from the 1746-C (what is given to the PLC)
Shaded area …
Standard 4-word
header in front of
any table
s
1
word in
buffer …
Table ID
Last data word
used in this data-
table …
for valve #48
s
1
actual data
word in table
… for valve #1
Shaded area … Unused
part of 60-word data-table
because only 48 nodes on
network
(unused network locations
marked with a “-99”)
Last data word
possible in any
data-table …
for valve #60 …
not used here.
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 36
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
5.2. Standard Header Format (All Tables) … Words [0  3]
The header is the first four (4) words in the data block. Please refer to the list of tables in Figure 3-2.
5.2.1. Word [0]: Table ID
As in the first word in the block data transfers, this first word is the Table ID. This can also be considered the “Command ID”.
5.2.2. Word [1]: Read / Write Command Indicator
(If a Read/Write Table):
If word [1] == 0 this is a command from the PLC to the 1746-C to read the specified table
from 1746-C memory and place it into the exchange buffer so the PLC can read it out … words [0
If this is table [0], then this read back will include all current configuration information (at the front of the table) and current system run-time information (at the back of the table).
If word [1] =/= 0 (any non-zero value) … this is a command from the PLC to the 1746-C to
remove the supplied table of data from the exchange buffer and place it into the 1746­C standard memory (tables).
- If this is table [0], then the configuration information is written.
- Otherwise, the table information is written to the 1746-C.
- If this is the type of table that actually writes data to the actuators, then that data is outputted to the actuators.
(If a Read Only Table):
This word is ignored and the table is only read.
63].
5.2.3. Word [2]: Reserved / Firmware ID
When received by the 1746-C from the PLC, this word is ignored (reserved for future use).
When transmitted from the 1746-C to the PLC, this word contains the firmware ID. This is a decimal number representing the 1746-C firmware ID. For instance, if the value in table [0] … word [2] is 400, the firmware version number is 4.00
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 37
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
5.2.4. Word [3]: Emergency Shut Down (ESD) Command Word & Indication
The ESD command is a command broadcasted to all actuators connected to the network that an emergency is in effect and the actuator should start performing the ESD actions its pre-configured for. The 1746-C broadcasts an ESD on both channels with a 200-millisecond delay between them.
If the PLC wishes to engage the ESD for the network, it writes a 255 (0x00FF) to this word location (Word [3]) using a write to any table. The Network Master then broadcasts the appropriate ESD command to all valves on the network (on both channels with about a 200ms delay between each).
When the PLC wants to end the ESD, it writes a 170 (0x00AA) into this word into any table. The Network Master will then broadcast the appropriate “Stand-Down from ESD” command to all valves on the network on both channels with about a 200ms delay between each.
Later, after the PLC is satisfied that the ESD is over and normal operations have resumed (stand down from ESD has completed), it is recommended that the PLC clear this stand-down value (and all aspects of ESD) by resetting it to zero (again, in any table).
Summary: The appropriate values for the ESD command word from the PLC are:
255 (0x00FF) = Engage ESD
170 (0x00AA) = Stand down from ESD
0 = Emergency shut-down (ESD) control is not active
Once any ESD command is written to any table, the value is propagated throughout all tables. Therefore, the RLL does not have to remember which one it wrote to.
Warning: Since the ESD is actually a function of the actuator control cards; if an actuator is reset then
that actuator will probably not be in ESD. This also means that if the 1746-C loses power or is reset, it has no prior knowledge of any valves in ESD. It can turn off ESD once initialization of the software has occurred. It is the responsibility of the RLL to repeat the ESD broadcast under the possibility of these circumstances.
Warning: If any or some of the actuators are configured to move on ESD, consider the electrical
power required in performing a network ESD. A large electrical power drop can possibly create a reset in the actuator by affecting the control voltage.
Note 1: Remember, an ESD command from the PLC will inform the actuators to do what ever they
were configured to do during an ESD condition. Therefore, this could easily override any other control commands already sent to them or about to be sent (ex: commands placed in any write Tables [3, 5, 8,] might be rejected by the actuator because of the ESD condition).
Note 2: If monitoring the network, the values of 0xAA & 0xFF are not the values transmitted to the
actuators. The program actually uses a Modbus command 05 to set/clear a bit (coil) in the register map in the actuators. From then on, the actuators do what ever they are configured to do when ESD is either started or ended.
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 38
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
5.3. Table [0] … System Information Table
5.3.1. Table [0] Overview
This table is a read/write table in that is used for “system level” configuration and run-time status/diagnostic information. Basically, it is not “actuator” focused but more focused on the entire network of actuators.
When told to write this table, the information is not sent out onto the network. Also, only the configuration words are written into the table. The run-time status information is supplied by the 1746­C.
Table [0] has 4 parts to it:
1. Words [0
2. Words [4
3. Words [18
4. Words [47
3]: Standard header information … common in all tables.
17]: System Configuration/Control words (set by the PLC)
46]: Not currently used … Reserved for future use … zeroed out.
63]: Run-time feedback of real-time values (set by the 1746-C).
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 39
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
Words [4 17] (control/configuration parameters set by the PLC)
1. Word [4]: Set the Number of Valves on the Network.
2. Word [5]: Set the Scan Period value (# scans before a communication diagnostic scan)
3. Word [6]: Set the T/F control flag whether or not to poll for totalizers on network scans.
4. Word [7]: Set the additional number of valves to poll in the network-scan time slice.
5. Word [8]: Set the Additional Message response delay to expect from actuators (10ms increments)
(FUNCTION: Poll specified additional register from all actuators on network)
6. Word [9]: Set the specified additional register to poll from all actuators on the network.
7. Word [10]: Set the T/F control flag whether or not to start polling all actuators for the additional register.
(FUNCTION: Poll block of registers from one specific actuator on the network)
8. Word [11]: Set the specific actuator to get the block of holding registers from
9. Word [12]: Set the starting register number in the block of holding registers to be requested
10. Word [13]: Set the total number of holding registers being requested
11. Word [14]: Set the T/F control flag whether or not to start polling the specific actuator for the block of registers.
(FUNCTION: Reset Scan Period Counter/Accumulator)
12. Word [15]: Set the T/F control flag whether or not to manually reset the Scan Period Counter.
13. Word [16]: Value that will always reset the scan period counter.
(FUNCTION: Poll TEC2000 Input Registers 1000 – 1003)
14. Word [17]: Set the T/F control flag whether or not to poll the input registers if the system is determined to be a TEC2000 system.
Remember …
Currently, Words [18
should be considered “reserved” for future use.
46] in table [0] are unused and
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 40
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
Words [47 63] (Run-time feedback of real-time values set by the 1746-C)
1. Word [47]: Rollover Counter for Scan Period Counter (Accumulator).
2. Word [48]: Scan Period Counter (Accumulator).
-------------------------------------------
3. Word [49]: The port number for the currently “preferred port”.
4. Word [50]: Total number of valves polled during last network-scan time slice
(before servicing the PLC communications).
-------------------------------------------
5. Word [51]: This scan period: Last Network Scan Time (0.1 sec increments).
6. Word [52]: This scan period: Total elapsed time (0.1 sec increments).
7. Word [53]: This scan period: Average scan time (0.1 sec increments).
8. Word [54]: This scan period: Shortest scan time (0.1 sec increments).
9. Word [55]: This scan period: Longest scan time (0.1 sec increments).
-------------------------------------------
10. Word [56]: Last scan period: Average scan time last period (0.1 sec increments).
11. Word [57]: Last scan period: Total scan time last period (0.1 sec increments).
12. Word [58]: Last scan period: Shortest scan time last period (0.1 sec increments).
13. Word [59]: Last scan period: Longest scan time last period (0.1 sec increments).
-------------------------------------------
14. Word [60]: Duration of last diagnostic scan. (0.1 sec increments).
15. Word [61]: Duration of previous diagnostic scan (0.1 sec increments).
-------------------------------------------
16. Word [62]: Current period scan loop counter.
17. Word [63]: Current number of actuators “online” and communicating.
Note: All real-time timing information reported (reported back by the 1746-C module) has an accuracy
of (+/-) 50ms.
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 41
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
5.3.2. Table [0] Configuration Words … Words [4 17]
The following words in table [0] are a configuration and control parameters set by the PLC for the 1746­C to run as expected.
Word [4]: Number of Actuators on the network.
This is value indicates of the number of actuators on the network. If this number ever changes, all tables [1-20 … except for 15] are reset to ensure valid values get filled for each valve on the network.
The minimum number of actuators is one (1). The maximum is 60 (which is also the default).
Note to Remember with PLC Interfacing:
The 1746-C only fills in tables with data from the actuators during the “network scan time slice”.
If the PLC changes the Number of Actuators on the Network
after initial power up, the 1746-C will only be filling in the new data “X” actuators at a time (where “X” is the number of valves scanned per network scan time slide … see word [7] for more information on this). This means that it can take several network scan time slices for the 1746-C to fill in new data for all actuators on the network.
The 1746-C will not attempt to fill in all data before interfacing with the PLC again because of the time it takes to poll the entire network … this could lead to “starving the PLC” with a lack of communication.
The PLC RLL needs to be constructed to take this into consideration.
Word [5]: Number of Scans in Scan Period … Scan Period “Size”.
The scan period is the number of network scans before the network is retested for network failures (before the next diagnostic scan).
The default is 50 scans. If there is a communication error, such as a broken communication cable, then the system will look for a change (such as a repair to the cable) every 50 scans. The diagnostic scan resets all communication error indicators so that both ports can be checked
The minimum scan period number is five (5). The maximum number is 200.
Note: If your system requires highest performance and speed, then you may want to raise this
value (200 is max). If the system does not require performance but requires high reliability and early communication fault detection, you might want to lower this number (5 is minimum).
Note:
For more information on using the scan period value and the diagnostic scan; refer to
the Application Note at the end of this document.
at some point in time
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 42
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
Word [6]: FUNCTION: Poll for Accumulator (Totalizer) Data
This is a flag that indicates whether or not the 1746-C should request accumulator (totalizer) data from the actuators when scanning. The totalizer values are stored in tables [9 & 10].
This data is retrieved with a separate Modbus read command when the particular actuator is being polled (scanned).
If word [6] == 0 do not poll for totalizer data. If word [6] =/= 0 (any non-zero value) … poll for totalizer data.
By default, word [6] == 0 … do not poll for totalizer data.
Word [7]: Additional Valves to Poll in the scan time-slice.
The process scheduler has 2 primary processes to monitor:
1. Scanning the network (polling valves)
2. PLC communication & service.
Each process is given a particular time slice to operate in/with.
By program architecture, it is guaranteed that after servicing a PLC request, one valve (the next on the network after the previous one polled) will be polled for data. The number in word [7] allows the operator to allocate additional valves to be polled before servicing the PLC again. The larger this number is, the shorter the network scan time but the fewer interactions with the PLC. The lower the number, the more service given to the PLC (for control and feedback) but the slower the network scan time (because we are servicing the PLC commands to read/write tables).
This number should be adjusted for the most optimal fit for the application. The default value is 2. The minimum value is zero (0). The maximum value is the lesser of
9
1 less than the number of valves on the network.
Word [8]: Additional Message Response Delay
Word [8] offers the operator the chance to enter a desired ADDITIONAL expected delay when receiving messages from the network. The value is in 10 ms increments and can have a range of 0-30 (0 – 300 ms).
The default value is 0.
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 43
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
Words [9 & 10]: FUNCTION: Poll Additional Holding Register From Entire Network
This operation allows the operator the chance to poll the entire network for any particular holding register. The register values polled are stored in table [14]. This data is retrieved with a separate Modbus read command when the particular actuator is being polled (scanned).
This data is retrieved with a separate Modbus read command each time an actuator is polled (scanned).
FORMAT:
Word [9] … The holding register desired. Word [10] … This is a flag that indicates whether or not to start requesting that register from the actuators when scanning.
If Word [10] == 0 do not poll for the register.
If Word [10] =/= 0 (any non-zero value) … poll for the register specified in word [9].
By default, Words [9 & 10] == 0 … do not poll.
Words [11
14]: FUNCTION: Poll Additional Block of Registers From Single (Specified) Actuator
This operation allows the operator the chance to poll a single actuator for a block of registers. The register values returned are stored in table [15] such that …
Table [15] – words [4-7] … header information about information returned.
Table [15] – words [8-13] … not used … reserved.
Table [15] – words [14 - 63] … register information returned.
This data is retrieved with a separate Modbus read command when the particular actuator is being polled (scanned).
FORMAT:
Word [11] … The actuator address to get the block of registers from. Word [12] … The register number for the 1
st
holding register in the block to retrieve. Word [13] … The total number of registers to retrieve. Word [14] … This is a flag that indicates whether or not to start requesting that block of registers from that actuator when polling it.
If Word [14] == 0 do not poll for the block of registers.
If Word [14] =/= 0 (any non-zero value) … poll for the block of registers.
By default, Words [11
14] == 0 … do not poll.
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 44
Words [15
This operation allows the operator the chance to reset the scan period counter/accumulator
The scan period counter is located in table [0] – words [47 & 48] such that
Both have a high end max value of 32,000.
Word [48] is incremented at the start of scan #1(after the previous diagnostic scan). Whenever word [48] rolls over,
If the counter is reset in the middle of a scan period (which is most likely), it must wait until after that scan period is finished (and the accompanying diagnostic scan) before it starts counting again.
Note: that to determine the time for the rollover counter to rollover one time …
Rollover increment time = (time for the scan period) + (diagnostic scan time)
FORMAT:
Word [15] … This is a flag that indicates whether or not to reset the Scan Period Counter. Word [16] … The value used to reset the Scan Period Counter.
By default, Words [15 & 16] == 0 … do not reset the counter.
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
16]: FUNCTION: Reset Scan Period Counter (Accumulator)
When desired … word [15] =/= 0.
With the value desired … word [16] value.
Word [47] … Rollover counter for the Scan Period Counter.
Word [48] … Scan Period Counter
Word [48] is automatically filled with the value in word [16].
Word [47] is incremented
If Word [15] == 0 do not reset the counter.
If Word [15] =/= 0 (any non-zero value) …
Word [47] = 0
Word [48]    Word [16]
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 45
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
Word [17]: FUNCTION: Poll for Input Registers [1000-1003] on TEC2000 Systems
This is a flag that indicates whether or not the 1746-C should request the input registers on any TEC2000 system detected when scanning. The input register values are stored in tables [21 ­24] such that …
Table [21] contains register [1000] status bits.
Table [22] contains register [1001] status bits.
Table [23] contains register [1002] status bits.
Table [24] contains register [1003] status bits.
This data is retrieved with a separate Modbus read command when the particular actuator is being polled (scanned).
If word [17] == 0 do not poll for input registers. If word [17] =/= 0 (any non-zero value) … poll for input registers.
By default, word [17] == 0 … do not poll.
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 46
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
5.3.3. Table [0] Run-Time Information Words … Words [47 63]
The following words in table [0] are a run-time feedback of real-time values set by the 1746-C.
1. Word [47]: Rollover Counter for Scan Period Counter (Accumulator).
2. Word [48]: Scan Period Counter (Accumulator).
-------------------------------------------
3. Word [49]: The port number for the currently “preferred port”.
4. Word [50]: Total number of valves polled during last network-scan time slice (before servicing the PLC communications).
-------------------------------------------
5. Word [51]: This scan period: Last Network Scan Time (0.1 sec increments).
6. Word [52]: This scan period: Total elapsed time (0.1 sec increments).
7. Word [53]: This scan period: Average scan time (0.1 sec increments).
8. Word [54]: This scan period: Shortest scan time (0.1 sec increments).
9. Word [55]: This scan period: Longest scan time (0.1 sec increments).
-------------------------------------------
10. Word [56]: Last scan period: Average scan time last period (0.1 sec increments).
11. Word [57]: Last scan period: Total scan time last period (0.1 sec increments).
12. Word [58]: Last scan period: Shortest scan time last period (0.1 sec increments).
13. Word [59]: Last scan period: Longest scan time last period (0.1 sec increments).
-------------------------------------------
14. Word [60]: Duration of last diagnostic scan. (0.1 sec increments).
15. Word [61]: Duration of previous diagnostic scan (0.1 sec increments).
-------------------------------------------
16. Word [62]: Current period scan loop counter.
17. Word [63]: Current number of actuators “online” and communicating.
This information is updated at the end of each scan. If the information is scan-period based, then the information is updated only at the end of the last scan for the particular scan period.
Note: All real-time timing information reported (reported back by the 1746-C module) has an accuracy
of (+/-) 50ms.
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 47
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
5.3.4. Table [0] … RSLOGIX-500 Examples
5.3.4.1. Example RSLOGIX-500 Screen:
In this example, memory locations N10 & N11 show the entire data exchange area for M0/M1 transfer commands …
Table sent
out with the
M0 file
Table read
back with
the M1 file
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 48
r
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
5.3.4.2. Table [0] … The Configuration Values (RSLOGIX-500).
In this example, the memory areas:
N10:0 N10:63: Indicates the 64-word table the PLC sends to the 1746-C.
N11:0 N11:63: Indicates the 64-word table the 1746-C sends back to the PLC.
Interesting & Important Note in this example:
Table sent
out with the
M0 file
Table read
back with
the M1 file
In this example, the configuration the PLC would like to have (N10:0 agree with the configuration information the 1746-C actually has and is being read back (N11:0
N11:16). Also notice the configuration values being reflected back by the 1746-C … they
are all factory default values.
This screen reflects a state in which the PLC has not sent a “write table [0]” command to the 1746-C to set configuration values. Therefore, this 1746-C is currently running and “thinking” that
There are 60 actuators on the network.
The scan period should be 50 scans long
However, the PLC actually “wants”
48 actuators on the network.
A scan period 10 scans long
To remedy this disparity of operation … the PLC needs to send the “write table [0]” command to the 1746-C to set configuration values (word [1] =/= 0).
Table
Table ID
Read/Write
ID
Flag to Start
Polling
Additional
Register from
all Network
Devices
Command
Read/Write
Command
Reserved
Actuator
Address to
Poll Block of
Registers
Firmware
ID (5.02)
ESD
Command
Starting
Register in
Block of
Registers
Current ESD
Command
Specified #
actuators on
Total Number
of Registers in
Block of
Registers
Flag to Start
Polling for
Block of
Registers
Specified #
actuators on
Scan Period
Value
Scan
Period
Value
Flag to Poll
Totalizers
Flag to
Reset
the Scan
Period
Counter
Flag to Poll
Totalizers
Value to
the Scan
Counte
N10:16) does NOT
Additional
Valves in
Network Scan
time-slice
Flag to
Reset
Period
Poll
TEC2000
Additional
Valves in
Network Scan
-
Additional
Message
Response
Delay from
Actuators
Additional
Register to Poll
from All Network
Devices
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 49
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
5.3.4.3. Table [0] … The Configuration Values – Writing Table [0] (RSLOGIX-500)
State prior to writing table [0] configuration values …
Table sent
out with the
M0 file
Table read
back with
the M1 file
State after writing table [0] configuration values …
Table read
back with
the M1 file
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 50
f
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
5.3.4.4. Table [0] … The Run-Time Feedback Values From 1746-C (RSLOGIX-500)
This screen demonstrates examples of the run-time information that the 1746-C reports back to the PLC.
Table read
back with
the M1 file
Last Network
Scan:
Total number o
valves polled
during
Valve Scan
time slice (2)
Duration of
Last
Diagnostic
Scan
(17.3 sec)
Last Network
Scan:
Time
(4.3 sec)
Duration of
Previous
Diagnostic
Scan
(17.3 sec)
This Scan
Period:
Total Elapsed
time
(427 sec)
Current
scan loop
counter (0)
Diagnostic
Scan
This Scan
Period:
Average
Scan Time
(4.3 sec)
Current
Number of
Valves
Online (48)
This Scan
Period:
Shortest
Scan Time
(4.2 sec)
Last Scan
Period:
Average
Scan Time
(4.2 sec)
This Scan
Period:
Longest
Scan Time
(4.3 sec)
Last Scan
Period:
Total Elapsed
time
(41.9 sec)
Rollover Counter for Scan
Period
Counter
Last Scan
Period:
Shortest
Scan Time
(4.2 sec)
Scan
Period
Counter
This Scan
Period: Current
“Preferred”
Port
Last Scan
Period:
Longest Scan
Time
(4.2 sec)
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 51
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
5.4. Tables [1  20] … Actuator Information Tables
5.4.1. Table [1]: Communication Error Status
Words [4
The “Communication Error Status Table” is used by the network master to track communication faults with each actuator. This data is totally derived by the 1746-C. These are considered “Low-Level” communication errors.
The value of the word gives the following status:
This table can be used by the PLC system to diagnose valve actuators that are not communicating. If a network requires maintenance, then information in this table can help trace the problem. During a network fault, this information can help point to the section that’s in fault.
During communication with the actuators, a time-out value is implemented to flag network errors. The network master will try to communicate with the valve from the currently “preferred port” three (3) times. If the valve does not respond within those three times, the valve is flagged to communicate on the current “backup port” and the 1 The backup port immediately tries to communicate with the valve three more times. If the valve still fails to respond, the particular actuator is flagged as having a general communication error by having
The data in this table is always updated … any time the 1746-C tries to communicate with the network. However, this table is only reset (errors cleared) during a diagnostic scan.
63] PLC access: Read Only.
0 = good communication through both ports
1 = error communicating through Port 1 … but success on Port 2
2 = error communicating through Port 2 … but success on Port 1
3 = No communication to the valve actuator at all. In this case, bit-14 in Table [2] will also
be set.
st
port is identified as having a problem with that valve (in table [1]).
Its table [1] entry set = “3”.
Its bit-14 in table [2] set = “1”.
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 52
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
Example Table [1] Feedback (48-node network) …
Characteristics:
Total COM faults on units [1-4] … they have a value of 3 … an error communicating on both
ports.
No COM faults on any other units (5 – 48 have a value of 0 … no problems communicating).
Note that this would happen if units [1-4] were turned off.
First Node
on Network
Last Node
on 48 Node
Network
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 53
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
5.4.2. Table [2]: Actuator Operational Status
Words [4
This data is primarily derived from holding register [6] in the actuator. It is retrieved with the “standard data request” - Modbus read command when the particular actuator is being polled (scanned). However, bit-14 is adjusted by the 1746-C.
This status word can be “bit parsed” to give:
Note: Bit-0 is the LSB in the word. Bit-15 is the MSB in the word.
Some of these bit indications are repeats of those in table [12]. However, not all.
63] PLC access: Read Only.
Bit-0: LSO is tripped (valve is at the end of its OPEN travel limits)
Bit-1: LSC is tripped (valve is at the end of its CLOSE travel limits)
Bit-2: Valve is moving in the OPENING direction
Bit-3: Valve is moving in the CLOSING direction
Bit-4: Selector Switch is in the Local position
Bit-5: Selector Switch is in the Remote position
Bit-6: Open Torque ALARM is active.
Bit-7: Close Torque ALARM is active.
Bit-8: Valve Stall Alarm is active (valve not moving on command)
Bit-9: Power Monitor Alarm is active (loss of control voltage alarm)
Bit-10: Motor Overload Alarm is active
Bit-11: Phase Monitor Alarm is active (only if Phase Sentry is Installed)
Bit-12: Local (Hardwired) Alarm is active.
Bit-13: Fail Alarm Self-diagnostics Alarm is active.
Bit-14: Comm Alarm … Valve not communicating with the network
(Same as the value “3” in Table [1])
Bit-15: Unit Alarm … Set when any actuator alarm is set.
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 54
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
Example Table [2] Feedback (48-node network) …
Characteristics:
The format is displayed in HEX because HEX is easier to interpret “bit indicator” data.
Units [1, 3, 4] …
o Communication Alarm exists … bit [14] = 1
Unit [2] …
o Selector switch in the remote position … bit [5] = 1
The rest of the network is all the same …
o LSO is tripped … bit [0] = 1
First Node
on Network
Table [2] in HEX
because this
table represents
bit indications
Last Node
on 48 Node
Network
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 55
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
5.4.3. Table [3]: Discrete Control Mode (Open/Close/Stop)
Words [4 63] PLC access: Read / Write
This table commands the actuator to move the valve either OPEN / CLOSED / STOP.
There are three discrete valve control commands available:
1. 1 (0x0001) for Open
2. 2 (0x0002) for Close
3. 3 (0x0003) for Stop now at the current location.
The 1746-C will only react to these values.
The mechanism used to execute these commands is:
If (OPEN) command: a setpoint of 4095 is transmitted to the actuator.
If (CLOSE) command: a setpoint of 0 is transmitted to the actuator.
If (STOP) command:
o A Modbus command is sent to the actuator to read the current position. o That “current” position is sent to the actuator as the setpoint to go to.
A read back of Table [3] will
If a write command issued: reflect the write command accepted by the 1746-C
If a read command issued: reflect the last status of the discrete commands (unless changed by
a new table [5] entry).
Note 1: While the table will accept any value, any illegal data will be ignored.
Note 2: Any NEW discrete control command in this table will change the corresponding setpoint
control value in Table [5] to either 0 / 4095 / or “current position”.
Note 3: If a NEW change setpoint command is issued in Table [5] for a particular valve, then the
corresponding discrete control command in this table (Table [3]) will be zeroed out.
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 56
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
Example Table [3] Feedback (48-node network) …
Characteristics:
There are no discrete commands waiting for execution.
Last Node
on 48 Node
Network
First Node
on Network
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 57
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
5.4.4. Table [4]: Valve Position Indication … 0 – 100.0%
Words [4
The Network Master receives the valve position from the actuator as an integer representing 0 open in 0.1% increments. In other words, it receives a value from 0 – 1000 and each increment indicates a 0.1%
This data is derived from holding register [13] in the actuator. It is retrieved with the “standard data request” - Modbus read command when the particular actuator is being polled (scanned).
Example Table [4] Feedback (48-node network) …
Characteristics:
63] PLC access: Read Only.
0 Full Closed ( 0.0% open)
1000 Full Open (100.0 % open)
Units [1, 3, 4] indicated position is 0% open … probably not operating.
Unit [2] indicated position is 70.6% open
The rest of the network’s indicated position is fully open at 100.0% open
Last Node
on 48 Node
Network
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 58
100%
First Node
on Network
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
5.4.5. Table [5]: Valve Position Setpoint … 0 – 4095
Words [4 63] PLC access: Read / Write
This table commands the actuators to move to a setpoint position designated by the PLC. When the 1746-C sends the new value to the actuators (telling them to move), it uses the Modbus function 6 command to write to holding register [11] in the actuator.
By sending a numeric value from 0 based on:
0 (0x0000) = 0% Open (closed)
4095 (0x0FFF) = 100% Open
A read back of Table [5] will
If a write command issued: reflect the write command accepted by the 1746-C
If a read command issued: reflect the current value of the setpoint register in the actuators.
Notes:
Only values 0
4095 are allowed to be written by the PLC … all others are ignored.
Any EIM actuator may use position control via setpoint values. For the tightest position possible with minimal overshoot or undershoot, the actuator must have the solid-state or VFD control option. Please read the Controlinc Quick Startup Guide for more information.
If the actuator position has been moved while the PLC is down or the valve was moved while in local control, then as soon as the PLC and actuators are communicating and accepting remote commands, it will move according to the existing value in this Table.
Issuing a command in Table [5] will “zero out” any discrete (block) mode command issued on Table [3] for the particular valve.
Any NEW discrete control command in table [3] will change the corresponding setpoint control value in Table [5] to either 0 / 4095 / or “current position”
If the 1746-C ever returns a value of 0xFFFF for a setpoint indication in this table, it means that the particular actuator is returning the standard “invalid setpoin waiting for a new command to move the valve.
4095, the actuator will be commanded to move to a position
t” and is currently stopped and
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 59
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
Example Table [5] Feedback (48-node network) …
Characteristics:
Units [1, 3, 4] setpoint position is 0 (out of 4095) … 0% open … either fully closed or not
operating.
Unit [2] setpoint position is 2892 (out of 4095) … ~~ 70.6% open
The rest of the network’s setpoint position is fully open … 4095 out of 4095
First Node
on Network
Last Node
on 48 Node
Network
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 60
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
5.4.6. Tables [6 & 7]: User Analog Inputs #1 & 2
Words [4
These tables contain 12-bit numbers (0 channels. This data is derived from holding registers [16 & 17] in the actuators and is retrieved with the “standard data request (scanned).
Example Table [6] Feedback (48-node network) …
Characteristics:
63] PLC access: Read Only.
4095) representing the current value for analog input
” - Modbus read command when the particular actuator is being polled
Table [6]: Value for User Analog Input #1 (holding register [16] in the actuators)
Table [7]: Value for User Analog Input #2 (holding register [17] in the actuators)
There are no values on User Analog Input #1 on any unit on the network … all zero.
First Node
on Network
Last Node
on 48 Node
Network
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 61
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
5.4.7. Table [8]: Analog Output #1
Words [4 63] PLC access: Read / Write
This table/command tells the actuator to place an appropriate 4-20 mA signal on its analog output channel. This data is derived from holding register [10] in the actuators and is retrieved with the “standard data request” - Modbus read command when the particular actuator is being polled (scanned).
When the 1746-C sends a new value to the actuators, it uses the Modbus function 6 command to write to holding register [10] in the actuators.
The output is a linear scaling based on:
0 (0x0000) = 4 mA
4095 (0x0FFF) = 20 mA
Note: Only values 0  4095 are allowed … all others are ignored.
A read back of Table [8] will
If a write command issued: reflect the write command accepted by the 1746-C
If a read command issued: reflect the current value of the analog output register in the
actuators.
Note: Please read the Operators Manual the particular actuator for more information. Note: This is an option that must be installed on the actuator.
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 62
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
Example Table [8] Feedback (48-node network) …
Characteristics:
On this network, none of the analog output values have been activated … a “-1” value recorded
there (valid values are 0 – 4095).
First Node
on Network
Last Node
on 48 Node
Network
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 63
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
5.4.8. Tables [9 & 10]: Digital Input Accumulators (Totalizers) #1 & 2
Words [4 63] PLC access: Read / Write
These tables contain 16-bit accumulator (totalizer) numbers stored in holding registers [66 & 67] in the actuators. This data is retrieved with a separate Modbus read command when the particular actuator is being polled (scanned).
Table [9]: Value for Accumulator (Totalizer) #1
Table [10]: Value for Accumulator (Totalizer) #2
These tables are not polled for unless the 1746-C is configured to allow it …
if Table [0] – Word [7] == 0: The accumulator/totalizer information is NOT requested when
actuators are polled (
if Table [0] – Word [7] =/= 0: The accumulator/totalizer information is requested when
actuators are polled.
The PLC may reset these tables (and the counters in the actuators) with any value is prefers. All it needs to do is insert the new value in the table and send it to the 1746-C as a write command. The 1746-C will then send the value to the actuator.
A read back of Tables [9 & 10] will
If a write command issued: reflect the write command accepted by the 1746-C
If a read command issued: reflect the last known values of the totalizer registers in the
actuators.
the default).
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 64
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
Example Table [9] Feedback (48-node network) …
Characteristics:
Totalizer #1 has not engaged for any unit on the network. This means that the digital input(s)
assigned to this totalizer/accumulator have not toggled low/high since the last power up on any unit on the network.
o On 320A/B systems … user input #1. o On TEC2000 systems … it depends upon the configuration.
This also means that the feature is probably not implemented on the actuators.
First Node
on Network
Last Node
on 48 Node
Network
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 65
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
5.4.9. Table [11]: Valve Position Indication … 0 – 4095
Words [4
This table contains the 0-4095 representation of the valve position for the actuators. This data is derived from holding register [14] in the actuators and is retrieved with the “standard data request Modbus read command when the particular actuator is being polled (scanned).
Example Table [11] Feedback (48-node network) …
Characteristics:
63] PLC access: Read Only.
Units [1, 3, 4] position indication is 0 (out of 4095) … 0% open … either fully closed or not
operating.
Unit [2] position indication is 2892 (out of 4095) … ~~ 70.6% open
The rest of the network’s position indication is fully open … 4095 out of 4095
” -
Last Node
on 48 Node
Network
First Node
on Network
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 66
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
5.4.10. Table [12]: Discrete Input Statuses
Words [4
This table contains the status indications of the discrete inputs on 320A/B systems. Each bit in each word in the table indicates the status of a particular discrete (hardwired) digital input for a particular actuator. This data is derived from holding register [05] in the actuators and is retrieved with the “standard data request (scanned).
If a TEC2000 was polled, the TEC2000 system correlates appropriate values to the bits being returned.
This status word can be “bit parsed” to give:
Note: Bit-0 is the LSB in the word. Bit-15 is the MSB in the word.
Some of these bit indications are repeats of those in table [2]. However, not all.
63] PLC access: Read Only.
” - Modbus read command when the particular actuator is being polled
Bit-0: LSO (Limit Switch – Open) switch input is active (is tripped)
Bit-1: LSC (Limit Switch – Close) switch input is active (is tripped)
Bit-2: AUX Open Contactor input is active (is engaged)
Bit-3: AUX Close Contactor input is active (is engaged)
Bit-4: SS in Local Position input is active (is tripped)
Bit-5: SS in Remote Position input is active (is tripped)
Bit-6: TSO (Torque Switch – Open) input is active (is tripped) … not the alarm!
Bit-7: TSC (Torque Switch – Close) input is active (is tripped) … not the alarm!
Bit-8: Power Monitor Alarm input is active.
Bit-9: Thermal Overload Alarm input is active
Bit-10: Phase Monitor Alarm input is active (only if Phase Sentry is Installed)
Bit-11: Local (Hardwired) Alarm input is active
Bit-12: AUX Alarm input is active
Bit-13: User Input #1 is active
Bit-14: User Input #2 is active
Bit-15: Reserved … no operation.
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 67
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
Example Table [12] Feedback (48-node network) …
“C” HEX … 12 Decimal
Last Node
on 48 Node
Network
First Node
on Network
Table [12]
because this
table represents
bit indications
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 68
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
5.4.11. Table [13]: Solid State Relay (SSR) Configuration Table
Words [4 63] PLC access: Read / Write
This is a read/write table that is used to help configure the actuators on the network. It is intended to work with actuators that are setup for modulating control mode. If a 320A actuator has an SSR installed the network master must ensure the actuator knows it is configured with an SSR.
By writing a non-zero
POSITIVE value to these positions in table [13], tells the network master to tell
the particular 320A actuator to configure itself to use an SSR … set coil [37] = 1 on the actuator. If not a 320A actuator, this table value has no purpose.
SUMMARY:
If word [n] == 0 (where “n” is 4 63) … this actuator does not have a SSR.
If word [n] > 0 (any non-zero POSITIVE value) … this actuator has a SSR.
An example would be a network of actuators in which 3 are 320A systems that have SSCs … lets say on valves 2, 4 and 10 by Modbus address. The corresponding words for these actuators are:
Valve 2: Word [5] … ( 2 + 3)
Valve 4: Word [7] … ( 4 + 3)
Valve 10: Word [13] … (10 + 3)
A read back of Table [13] will verify the write command being accepted by the 1746-C.
Note: If an actuator
has an SSR installed AND
it is NOT configured for SSR control AND
it is placed in modulating mode
then the remote host will be unable to control the valve via setpoint control. The actuator will read the desired setpoint positions but will not be able to send the valve to the position and effectively stop it there.
Note: Remember, setting this configuration bit is only necessary if the unit is a 320A system … 320B
and TEC2000 systems do not need this configuration assistance.
OPTIONAL
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 69
Example Table [13] Feedback (48-node network) …
Characteristics:
None of the units are configured for an SSR … probably either because they just don’t have one
or because they are not 320A systems.
Last Node
on 48 Node
Network
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
First Node
on Network
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 70
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
5.4.12. Table [14]: Additional Register Being Polled From Entire Network
Words [4 63] PLC access: Read / Write
This operation allows the operator the chance to poll the entire network for any particular holding register. The register values polled are stored in this table. This data is retrieved with a separate Modbus read command when the particular actuator is being polled (scanned).
This table is not polled for unless the 1746-C is configured to allow it …
Table [0] – Word [10] … contains the register number to poll for.
Table [0] – Word [10] … is a flag that indicates whether or not to start requesting that register
from the actuators when scanning such that …
o if Table [0] – Word [11] == 0: The register is not polled (the default).
o if Table [0] – Word [11] =/= 0: The register information is requested when actuators are
polled.
The PLC may reset this table with any value is prefers. To do this, the PLC must insert the new value into the table and send it to the 1746-C as a write command. The values in this table are not sent out to the actuators on the network.
A read back of Table [14] will
If a write command issued: reflect the write command accepted by the 1746-C
If a read command issued: reflect the last known values of the specified register polled in the
actuators.
If the PLC is utilizing table [14], it is recommended that the PLC also poll table [20]. If an exception message is returned, then the value won’t be inserted into table [14] but the exception message indicator will be inserted into table [20].
If detected, and the PLC wants to try again, it should initialize table [14] to some known value and either explicitly clear table [20] or wait until after the next diagnostic scan (which automatically clears table [20]) before trying again.
Example Scenario: If there are multiple types of EIM equipment on the network and the table [14]
command requests data from an actuator that is “not supported by that type of actuator” (but is on the others), the actuator will return a Modbus Exception for that message and the values will NOT be loaded into tables [14 or 15]. However, the exception codes will be loaded into table [20].
For example, if requesting register [1010] from a
320A system … an exception code is returned.
TEC2000 system … the register containing coils [1069 – 1111] is returned.
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 71
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
Example Table [14] Feedback (48-node network) …
Characteristics:
(register [00] read back from the entire network … cannot tell from here … in table [0])
To make it more meaningful, table [14] is in hex because register [00] is bit indications.
Units [1,3,4] have a value of 0 … coils [0-15] all off … units probably off line.
Unit [2] has a value of 0x10C4 … Coils set: [12, 7, 6, 2]
Units [5-48] have a value of 0x10C4 … Coils set: [12, 7, 6, 2]
“E” HEX … 14 Decimal
Last Node
on 48 Node
Network
First Node
on Network
Table [14] in
HEX because
register
requested (00) is
in bit indications
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 72
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
5.4.13. Table [15]: Additional Block of Registers Being Polled From 1 Actuator
Words [4 63] PLC access: Read / Write
TABLE FORMAT: This operation allows the operator the chance to poll a single actuator for a block of registers. The register values returned are stored in table [15] such that …
Words [4 - 7] … header information about information returned …
Word [4] … Valve address where block of data came from. Word [5] … Valve (actuator) type id. Word [6] … Starting holding register number. Word [7] … Total Number of registers in block.
Words [8 - 13] … not used … reserved.
Words [14 - 63] … register information returned.
TABLE CONTROL: Control of this operation is via 4 words in table [0] such that …
Table [0] – Word [11] … The actuator address to get the block of registers from.
Table [0] – Word [12] … The register number for the 1
Table [0] – Word [13] … The total number of registers to retrieve.
Table [0] – Word [14] … This is a flag that indicates whether or not to start requesting that block
of registers from that actuator when polling it.
If Table [0] – Word [14] == 0 do not poll for the block of registers. If Table [0] – Word [14] =/= 0 (any non-zero value) … poll for the block of registers.
By default, Table [0] – Words [11
14] == 0 … do not poll.
OPERATIONAL OVERVIEW: This data is retrieved with a separate Modbus read command when the particular actuator is being polled (scanned).
The PLC may reset this table with any value is prefers. To do this, the PLC must insert the new value into the table and send it to the 1746-C as a write command. The values in this table are not sent out to the actuators on the network. A read back of Table [15] will
If a write command issued: reflect the write command accepted by the 1746-C except words [4
– 13] are zeroed out.
If a read command issued: reflect the last known values in the table.
st
holding register in the block to retrieve.
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 73
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
Words [4 – 7] are only filled with non-zero values if the block of data in words [14 – 63] table are actually values retrieved from the actuator at the address specified in word [4]. Therefore, if a read of table [15] indicates that
Word [4] == 0, then the data is not valid (there are not valves with address 0 that can respond
with data).
Word [4] =/= 0, then the data in the table came from a valve.
If the PLC is utilizing table [15], it is recommended that the PLC also poll table [20]. If an exception message is returned, then the block of data won’t be inserted into table [15] but the exception message indicator will be inserted into table [20].
If detected, and the PLC wants to try again, it should initialize table [15] to some known value and either explicitly clear table [20] or wait until after the next diagnostic scan (which automatically clears table [20]) before trying again.
Example Scenario: If there are multiple types of EIM equipment on the network and the table [15]
command requests a block of data from an actuator that is “not supported by that type of actuator” (but is on the others), the particular actuator will return a Modbus Exception for that message and the block of data will NOT be loaded into tables [15]. However, the exception codes will be loaded into table [20].
For example, if requesting a block of registers [15 - 30] from unit #5 and it is a
320A system … the block of registers is returned.
TEC2000 system … an exception code is returned.
Notes on table [15] use:
It is recommended that the PLC only keep this operation active until the data is received and
then deactivate it (setting table [0] – word [14] = 0).
When the PLC writes data to this table, the 1746-C only overwrites the last 50 words with the
data sent in. The rest of the table is zeroed out.
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 74
t
[00]
[49]
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
Example Table [15] Feedback (48-node network) …
Characteristics …
From actuator node #5
Which happens to be 320B EIM equipment … type 2
Starting from register [00] and
50 registers were read back.
From actuator node #5
Which happens
to be 320B EIM
equipment …
type 2
Starting
from
register
[00]
50
registers
were read
back
s
1
data
byte read
back … register
Last data
byte read
back … register
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 75
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
5.4.14. Tables [16 & 17]: Monitor & Control Discrete Digital Outputs
Words [4 63] PLC access: Read / Write
The entire operation to monitor and control the discrete outputs requires 2 tables ...
Table [16] ... CONTROL --- store commands (desired states) for discrete outputs (coils).
Table [17] ... MONITORING --- feedback (actual states) of discrete outputs (coils).
Table [16] allows the operator the ability to monitor (poll) and control the discrete outputs on an actuator. All discrete output control is performed via this table (no table [0] entries are required).
Table [17] is the feedback information for polling the discrete outputs.
This data is retrieved with a separate Modbus read command when the particular actuator is
being polled (scanned).
This data is only polled for when the matching valve entry in table [16] indicates that the 1746-C
should start monitoring these coils. Once polling (monitoring) has started, it must be explicitly turned off.
This table will only reflect the status of bits representing coils. All others are either ignored or
zeroed out.
The PLC may reset this table with any value is prefers. All it needs to do is insert the new
value in the table and send it to the 1746-C as a write command. The table will be reset even though nothing will be sent out to any actuator.
TEC2000 DISCRETE OUTPUTS (COILS) On a TEC2000 system, there are 12 outputs and they are addressed as coils [1000 - 1011] in register [1004] such that …
Coil [1000] … RO1 … Relay Output # 1
Coil [1001] … RO2 … Relay Output # 2
Coil [1002] … RO3 … Relay Output # 3
Coil [1003] … RO4 … Relay Output # 4
Coil [1004] … RO9 … Relay Output # 9
Coil [1005] … RO10 … Relay Output # 10.
Coil [1006] … RO11 … Relay Output # 11
Coil [1007] … RO12 … Relay Output # 12.
Coil [1008] … SO6 … Solid State Output # 6
Coil [1009] … SO7 … Solid State Output # 7
Coil [1010] … SO8 … Solid State Output # 8
Coil [1011] … RO9 … Relay Output # 9
Ordering is such that
Coil [1000] is the LSB and located in the “bit-0” position … the right most position.
Coil [1011] is the MSB and located in the “bit-11” position.
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 76
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
320A/B DISCRETE OUTPUTS (COILS) On a the other system types (320A and 320B), there are 3 outputs and they are addressed as coils [3­5] in register [00] such that …
Coil [3] … ESD / monitor relay.
Coil [4] … User Output Relay #1
Coil [5] … User Output Relay #2
Ordering is such that
Coil [3] is the “bit-3” position … the 4
Coil [4] is the “bit-4” position … the 5
Coil [5] is the “bit-5” position … the 6
th
position in from the right.
th
position in from the right.
th
position in from the right.
FORMAT There are 2 distinct areas in each word in table [16] …
Command / Control bits … bits [15-13] in the upper most nibble.
Desired coil (output) states …
o Bits [11 – 0] for TEC2000 systems o Bits [5-3] in other systems.
Only these bits are set in this table. All others are zeroed out.
COMMAND / CONTROL There are only 3 valid control values (upper nibble in the word) the PLC can send to the 1746-C concerning this operation …
1000 (binary): Setting the upper nibble = 1000 … (top 1 bit set) tells the 1746-C to start
1. monitoring the status of the output coils and recording them in table [17]. The 1746-C will also clear the desired state bits … set table [16] – bits [3-5] = 000.
1110 (binary): Setting the upper nibble = 1110 … (top 3 bits set) tells the 1746-C to
2.
Start monitoring the status of the output coils and recording their states in table [17].
ONE TIME … write the desired states of the output coils to the particular actuator.
Once successful, bit [13] is set = 0 to prevent further (excess) writes.
3. 0xxx (binary): Setting the bit = 0 … (bit [15] = 0 and don’t care about the others) tells the 1746-C to terminate monitoring and writing. Essentially, clear the command. The 1746-C will also clear the bits representing the desired state of all output coils in table [16].
The 1746-C will only react to these values from the PLC in the upper nibble. All others are ignored.
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 77
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
DESIRED STATES The desired states of the digital outputs are directly reflected in the bits in the table … which directly reflect the coils (bits) in the holding registers in the actuator. This means that the bits still maintain their original position in all the registers …
For example,
Coil [3] … is in register [00] – bit [3] … and in tables [16 & 17] in bit position [3]
Coil [4] … is in register [00] – bit [4] … and in tables [16 & 17] in bit position [4]
Coil [5] … is in register [00] – bit [5] … and in tables [16 & 17] in bit position [5]
Therefore, the PLC must set/clear bits [3-5] to control the outputs.
For example,
Coil [1000] … is in register [1004] – bit [0] … and in tables [16 & 17] in bit position [0]
Coil [1005] … is in register [1004] – bit [5] … and in tables [16 & 17] in bit position [5]
Therefore, the PLC must set/clear bits [0,1,5] to control these outputs.
Since a single command is sent to the actuator that affects all discrete outputs on a system at one time, it is important that the PLC be aware of the “state” of all coils on the particular valve before sending a command because ALL OUTPUTS ON THE VALVE will be affected EVERYTIME one of these commands is sent. This is why
Monitoring can be activated without writing values.
Monitoring remains active after a write until explicitly turned off.
By monitoring table [17], the PLC can ensure correct behavior.
IMPORTANT NOTE
A read back of Table [16] will
If a write command issued: reflect the status of the network write & network monitor commands
accepted by the 1746-C.
If a read command issued: reflect the last status of the network write & network monitor
commands issued out to the network.
Notes on table [16] use:
1. The PLC can monitor when a write happened by viewing the upper nibble of the word for the particular valve. When it changes from (1110 … 0xE)
 (1100 … 0xC) the write has
happened and the system is still monitoring the states of the relays.
2. The PLC can activate/deactivate monitoring these relays any time by setting/clearing bit [15]
see the “Command / Control” section above).
( However, anytime the PLC writes a value to the coils in an actuator, monitoring is automatically started … and will not terminate until the PLC terminates it. Therefore, the PLC needs to monitor this and deactivate the operation when not needed anymore … otherwise, the additional polling will slow (lengthen) network scan times.
3. The 1746-C uses a Modbus Command 05 to write multiple coils when writing values to the actuators.
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 78
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
Example Tables [16 & 17] Feedback (48-node network) …
Characteristics:
To make it more meaningful, tables [16 & 17] are in hex because of bit indications.
Monitoring is being performed on unit [1]
(bit [15] = 1 in table [16])
The PLC commanded the 1746-C to set all the coils on units [2 – 6]
(bits [15-13] = 111 … 0xE0xx in table [16] … the value prior to the 1746-C acting upon the command) (bits [5-3] = 111 in table [16])
The 1746-C processed the command and wrote the new coil states to actuators [2-6].
(bits [15-13] = 110 … 0xC0xx in table [16])
Units [2-6] all have all 3 discrete outputs on.
(bits [5-3] = 111 … 0x0038 in table [17])
TABLE EXAMPLES ARE ON NEXT PAGE …
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 79
Table
[16]
Sent
out
Table
[16]
Feed
back
Tables [16 & 17] … with
commands loaded but not sent
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
Tables [16 & 17] … after
commands sent
Table
[17] Feed back
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 80
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
5.4.15. Table [18]: Actuator System Type ID
Words [4
This data is primarily derived from holding registers [44] & [100] in the actuator. These registers are retrieved with 2 separate Modbus read commands when the particular actuator is being polled (scanned) during a diagnostic scan.
There are currently 4 types of EIM equipment identified. There are 6 system type values that can be entered into table [18]:
63] PLC access: Read Only.
If EIM equipment type = 320A … value in table [18] = “1”
If EIM equipment type = 320B … value in table [18] = “2”
If EIM equipment type = TEC2000 … value in table [18] = “3”
If non-EIM equipment type … value in table [18] = “0” or “255”
NOTE: There are 2 possible values if the unit is identified as non-EIM:
0 … If failed identification … method 1.
255 … If failed identification … method 2.
The 1746-C uses these values internally.
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 81
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
Example Table [18] Feedback (48-node network) …
Characteristics:
Unit [1] is an EIM TEC2000 system … type 3
Units [2 – 48] are EIM 320B systems ... type 2
First Node
on
Network
Last Node
on 48 Node
Network
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 82
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
5.4.16. Table [19]: Actuator Firmware Version ID
Words [4
This data is derived from holding register [44] in the actuator. It is retrieved during a diagnostic scan when the system type ID is being determined. This table is filled the same time table [18] is filled. For more information, see table [18].
Example Table [19] Feedback (48-node network) …
Characteristics:
Note: TEC2000 systems do not store their version ID in register [44]. What you will see from a
63] PLC access: Read Only.
Unit [1] is an EIM 320A system … firmware version: 2.00
Units [2 – 48] are EIM 320B systems … firmware version: 3.02
First Node
on
Network
Last Node on
48 Node Network
TEC2000 system is the upper bit set to “1” and the rest zero … 0x8000 hex (-32768 decimal). For more information relating to TEC2000 version identification, see the TEC2000 manual.
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 83
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
5.4.17. Table [20]: Modbus Exception Message Response
Words [4 63] PLC access: Read / Write
This data is filled anytime a communication error is detected due to the remote system sending a 5-byte Modbus Exception Response message. These are “High-Level” Communication Errors … Application Level. This table is cleared at the start of a diagnostic scan. Format:
Table [20] - Hi-byte: Error’d function code as returned by the remote system.
Table [20] - Lo-byte: Modbus Exception Type (1 3)
The PLC may reset this table with any value is prefers. To do this, the PLC must insert the new value into the table and send it to the 1746-C as a write command. The values in this table are not sent out to the actuators on the network.
A read back of Table [20] will
If a write command issued: reflect the write command accepted by the 1746-C
If a read command issued: reflect the current values in the table.
If the PLC is utilizing tables [14 or 15], it should also poll this table. There are many reasons for this. For example … if there are multiple types of EIM equipment on the network and the PLC requests data from an actuator that is “not supported by that type of actuator” (but is on the others), the actuator will return a Modbus Exception for that message and the values will NOT be loaded into tables [14 or 15]. However, the exception codes will be loaded into table [20].
Note: The intention of this table is not to identify (and maintain) this status in “real-time”. It is to only
serve as a general flag to the PLC/operator that an exception has occurred with this actuator and that the PLC/operator might want to investigate more thoroughly later.
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 84
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
Example Table [20] Feedback (48-node network) …
Characteristics:
Table [20] is displayed hex to make it easier to interpret Modbus Exception messages returned
from the actuators.
No actuators have responded with a Modbus Exception message so far this scan period.
“14” HEX … 20 Decimal
First Node
on Network
Table [20] in HEX
because it is easier
to read exception
messages returned
by the actuators
Last Node
on 48 Node
Network
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 85
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
5.4.18. Tables [21-24]: TEC2000 Status Inputs
Words [4 63] PLC access: Read / Write
The purpose of these tables is to afford the end user all critical status information from TEC2000 systems. TEC2000 systems are backwards compatible with the 320A/B systems. However, there are more “things that can be checked” in the TEC2000. For instance, in the TEC2000, the Unit Alarm is also tripped by a “Valve Drift” Alarm. The “Valve Drift” alarm is not available in the 320A/B systems.
Therefore: For maximum compatibility with the TEC2000 systems, it is recommended that you
enable monitoring the TEC2000 Status Inputs (tables [21-24]). This way, you can ensure you have all critical status information for any TEC2000 system on the network.
This data is derived from holding registers [1000 - 1003] in the TEC2000 actuator. These table entries are only filled in if
The particular valve is a TEC2000 system.
The 1746-C is configured to poll these additional registers.
This data is retrieved with a separate Modbus read command when the particular actuator is being polled (scanned).
These tables are not polled for unless the 1746-C is configured to allow it …
if Table [0] – Word [17] == 0: The TEC2000 status input information is NOT requested when
actuators are polled (
if Table [0] – Word [17] =/= 0: The TEC2000 status input information is requested when
actuators are polled.
The PLC may reset these tables with any value is prefers. All it needs to do is insert the new value in the table and send it to the 1746-C as a write command. The table will be reset even though nothing will be sent out to any actuator.
A read back of Tables [21 - 24] will
If a write command issued: reflect the table write command accepted by the 1746-C
If a read command issued: reflect the last known values of the status input registers in the
TED2000 actuators.
the default).
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 86
g
]
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
Example Tables [21-24] Feedback (48-node network) …
Characteristics:
Only 1 TEC2000 system on the network … unit address #1
Tables [21 - 24] are displayed hex because they represent bit indications … easier to read.
Table ID is 15 hex …
21 Decimal
Node #1 is only TEC2000 … This is re
ister [1000
Table ID is 16 hex …
22 Decimal
Register [1001]
Last node on
48-node
Table ID is 17 hex …
23 Decimal
Register [1002]
Table ID is 18 hex …
24 Decimal
Register [1003]
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 87
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
6. Application Notes
6.1. App Note: Performance Tuning
6.1.1. General Practices to Ensure Better Performance
To ensure optimal performance, the PLC should at least:
1. Ensure quick responses to the 1746-C requests for an M1 transfer.
(
2. Ensure table [0] is set correctly and repeated in a timely manner. Allow for frequent table [0] reads.
3. Only control & monitor discrete outputs (tables [16 & 17]) if and when needed.
(
4. Only read additional registers if and when the application program requires them.
(
5. Restrict the rate of data writes to the actuators … only write as fast as required to adequately control the valve.
(
6. Only write to or read tables if actually in use. (
(
cuts down 1746-C delaying other operations while waiting for the PLC)
cuts down on the time to gather data from each actuator)
cuts down on the time to gather data from each actuator)
cuts down on the interruptions to scanning the network … gathering data)
ex: do not write to the analog output table if analog outputs are not used)
prevents unnecessary delays to gathering the more important data from the network)
6.1.2. Reading Run-Time Information from Table [0]
The PLC should perform a read of table [0] in a timely enough manner so that an operator can “view” the run-time changes in a manner that makes sense. For example, the operator should be able to watch the scan counter increment by 1 or 2 … if it appears to “jump” by 15 or so (because the PLC is not reading table [0] enough) then it is a lot more difficult to use the information.
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 88
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
6.1.3. Loading Table [0] with Configuration Information
To maximize system performance, the RLL must load configuration information that includes:
The Number of Actuators on the network
The Scan Period (number of network scans before a diagnostic scan).
Whether or not to poll actuator totalizers.
The number of additional valves to scan in the scan time-slice (before servicing the PLC).
Table [13] … Which 320A actuators have Solid State Contactors for modulating control
Any additional response delay for messages returning from actuators.
Any specific register to poll from all nodes on the network.
Any block of registers to get from a specified actuator (node) on the network.
The value to reset the scan period counter.
Any direct monitoring and control of discrete outputs on specific actuators on the network …
- coils [1000 – 1011] on TEC2000 systems.
- coils [3-5] on the other systems.
Whether or not to poll input registers on TEC2000 systems.
The RLL is responsible for all configuration each time the system is reset. Except for 2 circumstances, all configuration is performed in table [0]. Exceptions:
1. The RLL must identify which 320A actuators require SSR control and load table [13] with the data. The optional “Solid State Relay” (SSR) is required to be in an actuator if the actuator is to receive modulating control commands from any controller. If an actuator is supposed to have an SSR installed, the network master will check, and if necessary, set the actuator internal configuration bit (indicating an SSR is installed) before sending it a modulation command.
2. The RLL must identify which actuators (if any) the network master will poll and control the discrete outputs on the actuator. This configuration information is loaded into table [16].
Upon reset, the 1746-C default configuration will assume:
That there are 60 actuators on the network
A Scan Period of 50 scans before a diagnostic scan.
Do not poll the actuator totalizers.
2 additional valves to scan (making a total of 3 valves scanned) in the scan time-slice before
servicing the PLC.
No 320A solid-state relays contactors installed in any actuators.
No additional response delay for messages returning from actuators.
No specific register to poll from all nodes on the network.
No block of registers to get from a specified actuator (node) on the network.
The scan period reset value is zero but do not reset the counter now.
No direct monitoring or control of discrete outputs on specific actuators on the network.
Do not poll TEC2000 input registers.
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 89
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
6.1.4. Behavior if a Delay in Loading Table [0] Configuration Information
The 1746-C does not store configuration information if power is cycled. When the 1746-C restarts, it reverts to factory default values (60 actuators, 50-Scan Period, …).
It is the responsibility of the PLC to ensure that system configuration information is written to the 1746­C. The PLC should periodically read the configuration back to ensure that the 1746-C still has the correct configuration in it (the 1746-C module was not reset).
Example:
Assume a network of 25 actuators.
If power is cycled on the PLC, the 1746-C will revert to factory default values (60 actuators, …). The sooner the PLC can reload the correct Table [0] configuration, the sooner the 1746-C will start polling the correct number of units.
Until this happens, the operator will see what appears to be a “dead space” in the transmitting and receiving of data when watching the tx/rx LEDs on the 1746-C module. What happens is that:
1. A diagnostic scan has determined that only 25 of 60 actuators are on line.
2. A new scan starts.
3. 25 actuators are communicated with.
4. The 1746-C steps through the next 35 actuators … preventing communication to them because they are “off line”. This is the “dead space” when watching the LEDs.
5. The scan ends … go back to step #2 if not at the end of the scan period.
In this situation, the operator will see a very regular pattern of “dead space” on each scan (each time LED1 changes state).
Solution: Ensure the PLC writes the configuration information and periodically ensures it stays correct.
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 90
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
6.1.5. Using the “Scan Period” Value
The “Scan Period behavior to the needs of the application. This value indicates the size of the “Scan Period” … the number of network scans before the 1746-C performs a diagnostic scan to try and “bring back on-line" any units that had stopped communicating.
During normal operations, the 1746-C will skip any actuator that it has already determined is "off line" (this is to save time when trying to gather data from the other actuators that are running). The only time it will bring any "off line" systems back on-line is
During the diagnostic scan
After reset.
If the end-user (application, HMI, ...) believes that allowing off-line units to come back on-line it is less important than normal data gathering (or just not something to be concerned with), then it should increase the scan period size (200 is the maximum ... indicating that a diagnostic scan will happen after every 200 network scans for data).
If however, the speed of units coming back on line is more critical than the increased interruption due to increasing the rate of diagnostic scans, then the HMI should lower the scan period number (5 is the minimum ... indicating that a diagnostic scan will happen after every 5 network scans for data).
In other words, recovery time to get an actuator back on line increases as the scan period value increases. Therefore, to speed up the recovery time, make the scan period value low. To lengthen the recovery time, make the scan period value high.
RECOMMENDATIONS: Typically, EIM will not recommend any particular value for the scan period value … EIM cannot make that type of decision for any end user. However, EIM will work with a user to explain what happens if a value is chosen. The user must then make the choice of value that best suits their application. Basically, they need to evaluate the priority levels (and effects of) the time period of having an actuator off-line vs. the interruptions in the normal data gathering to perform system diagnostics (allowing off-line systems the chance of coming back on-line).
” value is placed in table [0] for the end user (HMI) to dynamically adjust the network
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 91
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
6.2. App Note: 1746-C Operation – Additional Detailed Information
6.2.1. Scan Operation: Determining & Exiting “Network Down” Condition
If the 1746-C ever detects “network down” (no actuators communicating) then LED2 will come on and the program enters the diagnostic scan mode and remains there until at least one actuator responds.
After scanning the “down” network, if any actuator responds and the number of actuators that responded is not the same as the number configured in table [0], then the 1746-C will perform one more network scan in the diagnostic mode to afford the opportunity to “simultaneously” bring as many actuators on line as possible – as soon as possible – within the same scan and not have to wait an entire scan period.
This scenario happens when “total power on a network is restored at once and the network master happened to be in the middle of a scan period when power was restored” … which is the most common scenario. In this case, the repeat diagnostic scan allows the network master the opportunity to bring “as many systems as possible on line at one time as soon as possible” and not have to wait until the end of the scan period for the next diagnostic scan.
In other words, without this feature of repeating the diagnostic scan, if the network went down and came back up in the middle of a diagnostic scan (which was most probable), then the program would usually detect only a portion of the network and would wait until the end of the scan period to check for the rest. This is a relatively long time if we are considering the network "going up/down" due network wiring and not actual powering of actuators (which was most common). Therefore, to speed up getting most of the network on-line early, if the entire network goes down, the program repeats the diagnostic scan one more time in an attempt to get more units "on-line".
LED2 will remain on until the diagnostic scan finishes and normal scan operations resume.
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 92
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
6.2.2. Detailed Description of 1746-C Operation
1. Power up and self-initialization … LED1 & LED2 both on.
2. Perform the initial diagnostic scan to determine which actuators are actually on the network.
3. Turn LED1 & LED2 off.
4. Stay in a loop performing the following activities: I. Setup to start new scan of network.
If diagnostic scan:
- Ensure the communication ports are setup correctly.
- The previous scan period (group of scans) has finished.
- Toggle the preferred communication port.
Toggle the state of LED1 … on or off.
II. Perform the Network Scan: Using a time-slice time sharing methodology, loop through all the
actuators on the network (starting from #1 and going through #n [the highest number on the network]) such that:
--- (the valve scan time-slice) -----------
a. If a diagnostic scan …
- Clear any communication failure indications for the particular valve to be polled.
- Get system type ID … try on both ports.
- If an EIM system, get the firmware version ID. b. If supposed to get totalizer data for the valve, do it. c. If supposed to request a specific holding register, do it. If supposed to request a block of
holding registers from this actuator, do it. d. If supposed to monitor or control the discrete user relay outputs on this actuator, do it. e. If supposed to get TEC2000 input data, do it. f. Get the rest of the “standard data” from the valve.
Note: If the 1746-C can’t communicate with this particular actuator that is supposed to be
on-line, it marks that actuator as “off-line” … to skip on the next scan cycle. If there are
problems communicating on any particular channel to the actuator, this is also recorded.
--- (the PLC interface time-slice) -----------
g. If ready to interface with the PLC (ready for the PLC time-slice) then do it. When
finished with this PLC interface time-slice, if the number of valves changed in table [0],
end this loop, reset the rest of the tables and setup to enter a diagnostic scan … restart
with new data.
Otherwise still in the valve scan time-slice … If not at the last valve on the network, loop
back (to step “a” above) and get data from the next actuator.
III. Network Scan cleanup
Label Non-Used Actuator Operation. Mark all “non-used” actuator entries in the tables with an invalid value (“-99”).
Determine if the network is “down” by counting the number of actuators that did not communicate with the 1746-C. If the network is down, then turn LED2 on and force the next scan to be a diagnostic scan. Otherwise ensure LED2 is off.
Account for network scan timings to be displayed in table [0].
IV. Loop back to the top and start another network scan.
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 93
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
6.2.3. Time Allocated Process Control (Allocated Time Slices)
Time Allocation Process Control” operation acts as a process scheduler. There are two primary
The “ processes (scanning the network and servicing the PLC) and each one gets a dedicated “ The 1746-C uses this to ensure the primary processes are serviced in a deterministic and controllable manner.
The user adjustable configuration parameter in table [0] – word [7] determines the number of
Additional Valves to Scan in the Network Scan Time-Slice” before starting the PLC process time slice
” (before interfacing with the PLC … servicing the PLC interface process).
Values for the parameter …
The default value is 2.
This means 2 additional valves (3 total) will be scanned in the scan time slice before the PLC process is serviced in its time slice (when a M0/M1 transfer sequence from the PLC can be handled).
The minimum number is 0 (maximize the amount of PLC interfacing time).
The maximum number is the lesser of
o 9 o 1 less than the max number of valves on the network
(
can’t scan more valves than are on the network)
The larger the number, the faster the scan period but the fewer interfaces with the PLC. The smaller the number, the scan period is slower but there are more frequent interfaces with the PLC.
If the number is too large, it will take too long to service the PLC and control capabilities by the HMI may fall off (ex: they could generate a “control/placement” error in which the process control can’t move a modulating valve to a specified position within a specified time frame). In other words, if too much time is allocated for scanning valves before servicing the PLC, then the PLC might not be serviced often enough for adequate control. However, servicing the PLC too often is a waste of time if it can’t adequately process any differences between the services. That waste of time could be better spent polling more valves for data.
This parameter is end-user adjustable in Table [0] and is 100% dependent upon the application. Therefore, the operator must adjust (tune) this parameter to the specific application to get the best fit of
best scan rate
best service rate for the PLC block transfers
control via the PLC
the PLC getting table information (not skipping tables)
NOTE: To help prevent accidental delays to servicing the PLC due to taking too long to scan the
desired number of valves in the valve-scan time slice, a 650ms timer is in place. This timer is reset every time the 1746-C finishes servicing the PLC process. In between polling individual actuators during the valve scan time slice, if the 650ms timer ever expires then the PLC process will get serviced. In other words, there is a time-based limit to how long the network can be scanned before servicing the PLC.
time slice”.
Copyright © 2004 EIM COMPANY, INC. • 13840 PIKE ROAD • MISSOURI CITY, TX. 77489
Page 94
Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
Below is a table of empirical values demonstrating the difference in network performance when changing the number of additional valves to scan in the scan time slice.
This network scan scenario is for base readings with
No Network Writes – Only Polling
Zero M0/M1 transfer delays waiting for the RLL to interface with the 1746-C.
60 … Number of nodes configured to be on network
25 … Scan Period
Polling base scan data … no additional registers.
No additional delay time for Modbus response messages from the actuators.
Average Network Scan Time (seconds) after changing the
# Nodes “Talking”
… On-Line
“Additional Valves to Scan in the Network Scan Time Slice”
0 1 2 3 5 7 9
1 of 60 (#60) 0.2 0.2 0.2 0.2 0.2 0.2 0.2 2 of 60 (#59 – 60) 0.3 0.3 0.3 0.3 0.3 0.3 0.3 3 of 60 (#58 – 60) 0.4 0.4 0.4 0.4 0.4 0.4 0.4 6 of 60 (#55 – 60) 0.7 0.6 0.6 0.6 0.6 0.6 0.6 12 of 60 (#49 – 60) 1.3 1.2 1.1 1.1 1.0 1.0 1.0 24 of 60 (#37 – 60) 2.6 2.4 2.2 2.1 2.0 2.0 2.0
30 of 60 (#31 – 60) 3.2 3.0 2.7 2.7 2.6 2.5 2.5 36 of 60 (#25 – 60) 3.8 3.5 3.2 3.1 3.0 2.9 2.9 42 of 60 (#19 – 60) 4.4 4.1 3.8 3.7 3.6 3.5 3.4 48 of 60 (#13 – 60) 5.1 4.7 4.4 4.2 4.4 3.9 3.9 54 of 60 (#7 – 60) 5.7 5.3 4.9 4.7 4.5 4.4 4.3 60 of 60 (#1 – 60) 6.3 5.6 5.4 5.2 4.9 4.8 4.8
number of
The values in this table
“rounded values” and
have a precision of (+/-) 0.2 seconds.
Because of this, these
numbers are only
appropriate for estimates
and trend analysis.
Note: For the most accurate scan period timing, do not use the 1
environment change) … wait until the 2
nd
scan period or beyond.
st
scan period after a power cycle (or