EIM Controlinc 320B Quick Start-up Guide (Rev A) Quick Start Guide

Controlinc® Quick Startup Guide
Quick Startup Guide
ECL-4005-1017 Rev. D
October 2017
Preface
DCM320B is an upgrade of DCM320A. It is a t, form, and function replacement for the DCM320A. The DCM320B may be used as a direct replacement of the DCM320A in existing installations. The primary difference is the DIP switch conguration method. The DCM320B provides more range and resolution of most conguration parameters. This handy reference is a guide to help you get your system up and running quickly. Refer to the EIM wiring diagram supplied with the actuator for detailed wiring information. The rst section of this guide will help you get your Controlinc actuators hooked-up and set-up correctly. If you need to change conguration of the unit, we recommend using our Windows based Conguration and Control Utility (CCU) rather than setting conguration DIP switches shown in this guide. Setting network station address DIP switches is required. The second section of this manual is the Modbus memory map reference to help congure your host database. If you are using EIM Controlinc Network Master, then refer to the manual supplied with that unit for memory maps. Section three of this manual is a brief system startup guide to help you do things in the proper order to achieve a successful system startup. This last section also covers optional phase monitor module.
WARNING
Failure to follow instructions for proper electrical wiring, storage, setup, and maintenance may cause serious injury, damage equipment, or void the warranty. Refer to Manual E796 for instructions on storage, electrical hook-up, and maintenance.
Revision D
for Revision F and later revision boards
Copyright © 2017
All rights reserved.
EIM
13840 Pike Road
Missouri City, Texas 77489
1-800-679-1561
(281) 499-1561 FAX (281) 499-8445
www.emerson.com/eim
Section 1: Quick Start Guide
October 2017
Section 1: Quick Start Guide
Step 1: Identify network topology
Identify network topology from Figures 2 and 3 on page 5 and note the ports being used (Ports A,B,C,D). Refer to page 23 for guidance on network planning and installation.
Step 2: Set network jumpers and switches
If network topology is parallel bus, then remove network termination and bias by turning OFF S1 and S2 of SW4 on the DCM 320B card. Remove jumpers JP1 and JP2 on the CAM05, if installed. Terminations must be left in the most distant unit on the network. If E>Net is selected, all ports must be terminated. Baudrate range selection is not required on DCM 320B but is required on CAM05. Refer to Figure 5 on page 5 for jumper and DIP switch locations.
Step 3: Connect network wiring (Refer to page 23 for guidance)
Wire network ports selected in Step 1. Refer to Figure 4 when wiring Ports A and B on TBM 320A module. Refer to Figure 5 when wiring Ports C and D on the CAM05 module.
Quick Startup Guide
ECL-4005-1017 Rev. D
Step 4: Connect auxiliary I/O wiring
Refer to Figure 4 on page 6 when connecting discrete auxiliary I/O wiring. Note that some functions must be jumpered between screw terminals if not wired to external contacts. Analog I/O wiring is connected to the DCM 320B module as shown in Figure 5.
Step 5: Set network station address
Each node (valve actuator) on the network must have a unique station address. Locate DIP switch SW1 on the DCM 320B card shown in Figure 5. Locate the desired station address on pages 6 and 7. Set the DIP switches of SW1 to the corresponding pattern shown beside the selected address. Press execute button to store address.
1
Quick Start Guide
Quick Startup Guide
ECL-4005-1017 Rev. D
NOTE:
We highly recommend using EIM's Windows based Conguration and Control Utility (CCU) to congure the actuators. CCU is available at www.emerson.com/eim or your local Actuation Technologies distributor.
If using CCU,you may skip step 6 below.
Figure 1 Configuration and Control Utility (CCU)
Section 1: Quick Start Guide
October 2017
Quick Start Guide
Step 6: Select configuration parameters
The actuator may be congured using the 5 DIP switches of SW2 and 8 DIP switches of SW1. This is a back-up means of conguring the unit if CCU is not available. The actuator is normally shipped with factory default settings. These settings may be changed by the following procedure. Locate DIP switches SW1, SW2, and Setup Execute Button on the DCM 320B module shown in Figure 5. Place the Selector Switch in the "OFF" position. Select the feature or conguration parameter from the conguration tables in this manual. Set the DIP switches per the corresponding switch pattern and then press the execute button. If the conguration parameter is valid, the green (setup data good) LED will ash. If error data is entered, the red (setup data error) LED will light until the error is corrected. Repeat this procedure for each parameter to be revised. Return all 5 DIP switches of SW2 to the OFF position and return the 8 DIP switches of SW1 to the network station address when conguration is complete. With all SW2 switches OFF and the address switches set, press the execute button to store the network address to nonvolatile conguration memory.
2
Section 1: Quick Start Guide
October 2017
Figure 2 Controlinc Model 320B RS485 Network Topology Options
Quick Startup Guide
ECL-4005-1017 Rev. D
Figure 3
3
Quick Start Guide
Quick Startup Guide
ECL-4005-1017 Rev. D
Figure 4 TBM 320A Hook-up Diagram
Section 1: Quick Start Guide
October 2017
NOTE:
TBM320A is used with both DCM320A and DCM320B.
Figure 5
Quick Start Guide
4
Section 1: Quick Start Guide
October 2017
Figure 6 Configuration Data and Network Station Address (SW1)
Quick Startup Guide
ECL-4005-1017 Rev. D
5
Quick Start Guide
Quick Startup Guide
ECL-4005-1017 Rev. D
Figure 6 Conguration Data and Network Station Address (SW1) continued.....
Section 1: Quick Start Guide
October 2017
Quick Start Guide
6
Section 1: Quick Start Guide
October 2017
1.1 Setup Instructions
The DCM 320B is factory congured as specied by the customer purchase order. If eld setup changes are required, follow setup instructions below. If unsure about setup of a module, known factory default settings may be reloaded as shown under "Direct Command Mode". When executed, the module loads known parameters from program memory to EEPROM conguration memory. Default parameters are highlighted in this manual by a box around the default or the value is listed
1.2 Entering Setup Mode
Locate DIP switches SW1, SW2, Setup Execute Button and LED indicators on the DCM 320B (See Figure 5 on page 5). SW2 switches select mode and SW1 switches select setup parameters and network station address.
1) Record network station address of SW1. These switches must be returned to the same setting before exiting setup.
2) Place selector switch in the OFF position.
3) Select desired setup mode by setting SW2 as indicated on this and following
pages.
4) Verify the DCM320B has entered setup mode by a rapid ashing CPU GOOD light.
Quick Startup Guide
ECL-4005-1017 Rev. D
4.1 Changing Setup Parameters
The ve switches (S1 - S5) of SW2 select the parameter/mode to be congured. The eight switches of SW1 (S1-SB) are used to select desired setup data.
1) Locate the desired setup parameter to be revised on pages 9 through 22.
2) Set the ve switches of SW2 per the switch pattern shown for desired mode.
3) Set SW1 switches as shown or refer to the switches on pages 6 and 7 for desired value. Selected values are multiples of the stated resolution for each parameter.
4) When both SW2 and SW1 switches are set, press the execute button to store the setup parameter to nonvolatile memory.
5) Verify the green LED (setup data good) light ashes. If an invalid enter is made, the red LED (setup data error) light will turn on until the error is corrected.
5.1 Exiting Setup Mode
1) Tum off all ve SW2 switches.
2) Place selector switch in the OFF position.
3) Return SW1 switches to the Network Station Address recorded in Step 1 under "Entering Setup Mode" above.
4) Press the Execute Button.
5) Verify the DCM320B has returned to the normal run mode by a slow ashing CPU GOOD light.
7
Quick Start Guide
Quick Startup Guide
ECL-4005-1017 Rev. D
5.1 Direct Command Mode
Section 1: Quick Start Guide
October 2017
5.2 Valve Control Mode
(Setpoint Source)
Quick Start Guide
8
Section 1: Quick Start Guide
October 2017
5.3 Valve Travel Limits
Quick Startup Guide
ECL-4005-1017 Rev. D
5.4 ESD Function
9
Quick Start Guide
Quick Startup Guide
ECL-4005-1017 Rev. D
5.5 ESD/Monitor Relay Function
5.6 ESD Trigger Sources
Section 1: Quick Start Guide
October 2017
NOTE:
At least one source must be selected, or ESD is disabled.
Quick Start Guide
10
Section 1: Quick Start Guide
October 2017
5.7 ESD Delay Time
NOTE:
ESD Delay Time applies only to software generated ESD and not to the hardwired local ESD
input.
Quick Startup Guide
ECL-4005-1017 Rev. D
Notes on hardwired Local Inhibit/ESD:
1) Local ESD is a hardwired closed loop circuit wired to TBM tenninals 27 (+)and 28 (-) using either an external 24VDC power supply or the internal 24VDC power available at tenninals 26(+) and 29(-). See Figure 4.
2) Local ESD will inhibit control from the DCM320B module, local push buttons and selector switch. To force valve closed on local ESD, insert jumper between terminals 9 and 10. To force valve open on local ESD, insert jumper between terminals 8 and 9. Actuator will Stop (Stay-Put) if no jumpers are inserted between terminals 8-9 or 9-10.
3) To override motor thermal contacts during local ESD, insert jumper between terminals XO and 53.
WARNING:
Do not override thermals in a hazardous area.
4) Software activated ESD can activate Local ESD by wiring N.C. contacts of ESD/ Monitor relay (terminals 32 & 33) in series with Local lnhibit/ESD inputs at terminals 27 and 28.
11
Quick Start Guide
Quick Startup Guide
ECL-4005-1017 Rev. D
4.1 Position Control Bandwidth
4.2 Speed Control Bandwidth
Section 1: Quick Start Guide
October 2017
NOTE:
Speed control bandwidth is meaningful only when a VFD motor starter is used. Speed control bandwidth must be greater than position control bandwidth.
4.3 Motor Starter Type
Quick Start Guide
12
Section 1: Quick Start Guide
October 2017
4.4 Analog Output Control
4.5 Modulation Delay Time
Quick Startup Guide
ECL-4005-1017 Rev. D
13
Quick Start Guide
Quick Startup Guide
ECL-4005-1017 Rev. D
4.6 Network Response Delay Time
4.6.1 Primary Network Ports A and B
4.6.2 Secondary Network Ports C and D
Section 1: Quick Start Guide
October 2017
4.7 Torque Retry (Log-Jam) Control
Quick Start Guide
14
Section 1: Quick Start Guide
October 2017
4.8 Network Baud Rate
4.8.1 Primary Network Ports A and B
4.8.2 Secondary Network Ports C and D
Quick Startup Guide
ECL-4005-1017 Rev. D
4.9 Network Parity
4.9.1 Primary Network Ports A and B
4.9.2 Secondary Network Ports C and D
15
Quick Start Guide
Quick Startup Guide
ECL-4005-1017 Rev. D
4.10 Calibrate Analog I/O
4.11 Calibrate Analog Inputs
Section 1: Quick Start Guide
October 2017
4.12 Calibrate Analog Output
Quick Start Guide
16
Section 1: Quick Start Guide
October 2017
4.13 Load Factory Default Calibrate Values
Quick Startup Guide
ECL-4005-1017 Rev. D
4.14 User Relay #1 Application
17
Quick Start Guide
Quick Startup Guide
ECL-4005-1017 Rev. D
4.15 User Relay #2 Application
Section 1: Quick Start Guide
October 2017
NOTE:
User Relay #1 and User Relay #2 are non-latching SPST type. When power to the actuator is lost, both relays are de-energized and the contacts will open. Do not apply these relays to critical control applications where closed contacts are required during loss of power.
4.16 LSA Position Setpoint
Quick Start Guide
18
Section 1: Quick Start Guide
October 2017
4.17 LSB Position Setpoint
4.18 Anti-water Hammer
Quick Startup Guide
ECL-4005-1017 Rev. D
4.19 Opening Duty Cycle ON Timer
19
Quick Start Guide
Quick Startup Guide
ECL-4005-1017 Rev. D
4.20 Opening Duty Cycle OFF Timer
4.21 Closing Duty Cycle ON Timer
Section 1: Quick Start Guide
October 2017
4.22 Closing Duty Cycle OFF Timer
NOTE:
Duty cycle timers are active only when selector switch is in REMOTE position. Opening and closing speed of the valve may be adjusted (slowed) by enabling the opening or closing duty cycle timers. Duty cycle timers are available only with a solid-state or VFD starter. Anti-water hammer duty cycle is is xed at 50% duty with one second ON time and one second OFF time for SSR and VFD starters and two seconds ON time and two seconds OFF time for electro­mechanical starter. When activated, the Anti-water hammer function overrides the closing duty cycle timer. If duty cycle or Anti-water hammer functions are used in any Anti water hammer scheme, ElM must be advised of system parameters and conditions.
Quick Start Guide
20
Section 2: Modbus Memory Map Reference
October 2017
Quick Startup Guide
ECL-4005-1017 Rev. D
Section 2: Modbus Memory Map Reference
4.23 Modbus Function Codes
Host beginning register
01 Read Coil Status 00001 02 Read Input Status 10001 03 Read Holding Register 40001 04 Read Input Register 30001 05 Force Single Coil 00001
06 Preset Single Register 40001
07 Read Exception Status 08 Loopback Diagnostic Test 15 Force Multiple Coils 00001
16 Preset Multiple Registers 40001 17 Report Slave I.D.
NOTE:
All registers are zero based. Add one to inputs, coils or holding registers when conguring host database. See host beginning registers above.
4.24 Input Register Map
(Use function code 04)
00 Inputs 0-15 (Live discrete inputs) 01 Inputs 16-31 (Standard valve status) 02 Inputs 32-47 (DCM320 valve status) 03 Inputs 48-63 (Specic to DCM320B)
4.25 Input Register 03 (DCM320B only)
48 DCM is in Setup Mode 49 AIN1 Signal fault
50 AIN2 Signal fault 51 AIN3 Signal fault 52 Software triggered ESD active
53-63 Reserved inputs (always zero)
21
Modbus Memory Map Reference
Quick Startup Guide
ECL-4005-1017 Rev. D
4.26 Discrete Input Map
(Inputs 0 through 15 are hardware inputs)
(use function code 02)
00 Open limit switch (LSO) 25 Power monitor alarm 01 Close limit switch (LSC) 26 Motor thermal overload alarm 02 Contactor Aux. open contact 27 Phase monitor alarm 03 Contactor Aux. close contact 28 Local ESD alarm 04 Selector switch Local/Manual 29 Actuator fail alarm 05 Selector switch Remote/Auto 30 No input (always zero) 06 Open torque switch (TSO) 31 Unit alarm (above alarms OR'ed) 07 Close torque switch (TSC) 32 Open limit switch (LSO) 08 Power monitor alarm 33 Close limit switch (LSC) 09 Motor thermal overload 34 Stopped (valve stopped in mid travel) 10 Phase monitor 35 Opening (valve moving open) 11 Local ESD alarm 36 Closing (valve moving close) 12 Aux. alarm input (VFD fault) 37 Valve stall alarm (valve not moving) 13 User discrete input #1 38 Selector switch in Local/Manual 14 User discrete input #2 39 Unit alarm (alarms OR'ed) 15 Reserved 40 Motor thermal overload alarm 16 Open limit switch (LSO) 41 Power monitor alarm 17 Close limit switch (LSC) 42 Primary network alarm 18
Opening (valve moving open)
19
Closing (valve moving close)
20
Selector switch Local/Manual
21
Selector switch Remote/Auto
22
Open torque switch (TSO)
23
Close torque switch (TSC)
24
Valve stall alarm (valve not moving)
Section 2: Modbus Memory Map Reference
October 2017
43 Secondary network alarm 44 Open torque alarm (TSO) 45 Close torque alarm (TSC)
46 Local ESD input alarm 47 Phase monitor alarm
Modbus Memory Map Reference
22
Section 2: Modbus Memory Map Reference
October 2017
4.27 Coil Map
(Coils 0 through 7 are hardware outputs)
(use function code 01, 05 and 15)
00 Close motor starter output 42 Enable Open on ESD with ESD relay 01 Open motor starter output 43 Enable Stop on ESD with ESD relay 02 Solid-state relay NFC speed control 44 Enable ESD trigger from host 03 ESD/Monitor relay output 45 Enable ESD trigger on local ESD input 04 User relay #I/Override relay 46 Enable ESD trigger from loss of com. 05 User relay #2 47 Conguration conict error detected 06 Primary network channel 1 enable 48 Select AIN1 as setpoint source 07 Secondary network channel 2 enable 49 Select AIN2 as setpoint source 08 Host OPEN valve command 50 Select AIN3 as setpoint source 09 Host STOP command 51 Move to Default on AIN1 fault 10 Host CLOSE valve command 52 Move to Default on AIN2 fault 11 Host ESD command 53 Move to Default on AIN3 fault 12 Enable normal modulating mode 54 reserved 13 reserved 55 reserved 14 Enable VFD starter control mode 56 reserved 15 Enable pulse control mode 57 Select N.C. contacts for Relay #1 16 Open limit switch status (LSO) 58 Enable Relay #1 as Override on ESD 17 Close limit switch status (LSC) 59 Activate Relay #1 in Remote/Auto 18 Opening status (valve moving open) 60 Activate Relay #1 in Local/Manual
19 Closing status (valve moving close) 61 Activate Relay #1 at LSA setpoint
20 Selector switch Local/Manual 62 Select N.C. contacts for Relay #2 21 Selector switch Remote/Auto 63 Enable Relay #2 as Override on ESD 22 Open torque alarm (TSO) 64 Activate Relay #2 in Remote/Auto 23 Close torque alarm (TSC) 65 Activate Relay #2 in Local/Manual 24 Valve stall alarm (valve not moving) 66 Activate Relay #2 at LSB setpoint 25 Power monitor alarm 67 Set primary network to odd parity
26 Motor overload alarm (Motor thermal) 68 Set primary network to even parity
27 Phase monitor alarm 69 Set secondary net to odd parity 28 Local ESD alarm 70 Set secondary net to even parity 29 Actuator fail alarm 71 Enable primary network alarm 30 reserved for host (always zero) 72 Enable secondary network alarm 31 Unit alarm (all alarms OR'ed) 73 reserved 32 Enable torque seat mode 74 reserved 33 Enable logjam retry mode 75 Enable MRTU operating mode 34 Enable 4-20mA feedback at A0#1 76 Enable torque backseat 35 Enable monitor relay, else ESD relay 77 Save torque prole to EEPROM 36 Enable passcode protection 78 CPU has reset 37 Enable solid-state starter contol mode 79 Load factory default conguration 38 reserved 100 Host OPEN valve command 39 Enable Close on ESD w/o ESD relay 101 Host CLOSE valve command 40 Enable Open on ESD w/o ESD relay 102 Host STOP command 41 Enable Close on ESD with ESD relay 103 Host ESD command
Quick Startup Guide
ECL-4005-1017 Rev. D
23
Modbus Memory Map Reference
Quick Startup Guide
ECL-4005-1017 Rev. D
4.28 Holding Register Map
(RO = Read Only RW = Read/Write)
(Use function 03, 06 and 16)
00 RW Coils 0-15 42 RW Passcode char 1(LSB) & 2(MSB) 01 RO Coils 16-31 43 RW Passcode char 3(LSB) & 4(MSB) 02 RW Coils 32-47 44 RO Firmware version 03 RW Coils 48-63 45 reserved 04 RW Coils 64-79 46 reserved 05 RO Inputs 0-15 47 reserved 06 RO Inputs 16-31 48 RO Torque@ 10% valve position 07 RO Valve Position 1.0% increments 49 RO Torque@ 20% valve position 08 RO Valve Status inputs 32-47 50 RO Torque@ 30% valve position 09 RO Valve Status inputs 16-31 51 RO Torque@ 40% valve position 10 RW Analog Output (0-4095) 52 RO Torque@ 50% valve position 11 RW Valve Position Setpoint (0-4095) 53 RO Torque@ 60% valve position 12 RO Inputs 48-63 54 RO Torque@ 70% valve position 13 RO Valve Position (0.1% increments) 55 RO Torque@ 80% valve position 14 RO Position Analog Input (0-4095) 56 RO Torque@ 90% valve position 15 RO Torque Analog Input (0-4095) 57 RO Torque prole @ 10% 16 RO User Analog Input #1 (0-4095) 58 RO Torque prole @ 20% 17 RO User Analog Input #2 (0-4095 59 RO Torque prole @ 30% 18 RW Water Hammer setpoint (1-20%) 60 RO Torque prole @ 40% 19 RW Modulation delay (0.1-25.5 sec) 61 RO Torque prole @ 50% 20 RW ESD Delay timer (0-65.5 sec) 62 RO Torque prole @ 60% 21 RW Position Bandwidth (0.1-5.0%) 63 RO Torque prole @ 70% 22 RW Speed Bandwidth (0.5-10%) 64 RO Torque prole @ 80% 23 RW Default Position Setpoint (0-4095) 65 RO Torque prole @ 90% 24 RW Torque AIN Zero offset, raw cnts 66 RW Accumulator #1 (User Input #1) 25 RW Torque AIN Span, raw AID counts 67 RW Accumulator #1 (User Input #2)
26 RW User AIN1 Zero offset, raw counts 68 RW Lost COM ESD delay (mS)
27 RW User AIN1 Span, raw AID counts 69 RW Stall time delay (mS) 28 RW User AIN2 Zero offset, raw counts 70 RW RW Valve Travel Time/1% (mS) 29 RW User AIN2 Span, raw AID counts 100 RO RO Unit I.D. 30 RW A0#1 Zero offset, raw counts 31 RW A0#1 Span, raw D/A counts 32 RW LSA Setpoint (0-4095) 33 RW LSB Setpoint (0-4095) 34 RW Close ON duty cycle (0-65.5 sec) 35 RW Close OFF duty cycle (0-65.5 sec)
36 RW Open ON duty cycle (0-65.5 sec)
37 RW Open OFF duty cycle (0-65.5 sec) 38 RW Primary network baudrate 39 RW Primary network response delay 40 RW Secondary network baudrate 41 RW Secondary network response dela
Section 2: Modbus Memory Map Reference
October 2017
NOTE:
1) Unless otherwise specied, analog I/O is unsigned integer in range of 0-4095.
2) All time parameters are in mS.
3) Torque readings are raw AID counts.
4 ) To rq u e p r o  le v a lu e s ar e r ea d f ro m
EEPROM.
5) Do not write to reserved registers.
Modbus Memory Map Reference
24
Section 3: Network Installation Guide
October 2017
Section 3: Network Installation Guide
Step 1: Plan the network topology
Before connecting actuators, the entire network layout should be planned. Select desired network topology from Figures 2 and 3 on page 5. Topologies may be bus or E>Net or a combination of bus and E>Net. All networks may be redundant or ring or redundant rings. Limit the number of parallel connected bus units to 15 between E>Net units. Network planning should include node addressing, wire routing, terminations, and grounding.
Step 2: Select network cable
Ensure correct cable is being used. Networks require twisted pair and shielded cable with a characteristic impedance between 50 and 120 Ohms. Capacitance between conductors must be less than 30pF/ft (98 pF/m); 10-15pF/ft is ideal. Shielding may be aluminum foil with drain wire. Only cables with stranded conductors are recommended. Insulating and outer jacket materials must be selected for the application environment. Following are acceptable Belden or equivalent cables for most network applications.
Quick Startup Guide
ECL-4005-1017 Rev. D
24AWG 9841, 12.8pF/ft
22AWG 8761, 24pF/ft
20AWG 8762, 27pF/ft
18AWG 8760, 24pF/ft
16AWG 8719, 23pF/ft
14AWG 8720, 24pF/ft
8162, 9729, and 9842 are 24AWG, 2-pair cables with <13pF/ft
Step 3: Route cable away from electrical interference
Network cables should enter the electrical enclosure at the bottom or lowest point near the transformer end. Route cable around the transformer end, normally in a counter clockwise direction to the top side of the TBM. Never install network cable in the same conduit with power conductors. Never route network cable through the high voltage contactor area. The cable should never lie across the TBM or hinder the protective cover of the TBM. Always use the shortest distance and keep excess cable to a minimum; 6" typical.
Step 4: Observe polarity and network grounding
Each network connection is polarized + and - on wiring diagrams. Always use consistency in wiring and the use of wire colors to track polarity. The cable shield or drain wire must be connected to the designated (SH) terminal at each port of each actuator. The shield must be connected to earth ground at only one point. Some networks may require a jumper between shield connections (Terminals 22 and 23) of each actuator to carry the shield through the network. The shield connection of each actuator is isolated from earth. Do not allow the shield to touch circuits on the TBM or the metal enclosure. Use plastic electrical tape or heat shrink tubing to isolate the shield or drain wire.
Step 5: Wire preparation and connections
Screw terminals of the TBM have wire clamps that accept wires without terminals but may be applied if desired. Strip insulation back 3/8" when connecting directly to the TBM screw terminals. Do not allow wire clippings to fall on the TBM or into the actuator enclosure. Protect conductors and the shield or drain wire to prevent contact with the TBM. Use plastic electrical tape or heat shrink tubing to prevent bare conductors from contacting other circuits or earth ground.
25
Network Installation Guide
Quick Startup Guide
ECL-4005-1017 Rev. D
Step 6: Wire preparation and connections
Use EIM's Conguration and Control Utility (CCU) or Controlinc Pocket Technician to test the network prior to connecting to a host or network master. The CCU is a Windows application that will run on a laptop using an RS232 to RS485 adapter or EIM's Network Interface Unit (NIU) for connecting to the network. After all actuators are veried to operate in Local mode, test each actuator to verify all network connections and each actuator operates via the network in Remote mode.
Section 3: Network Installation Guide
October 2017
Network Installation Guide
26
Section 4: System Startup Guide
October 2017
Section 4: System Startup Guide
Step 1: Set position and torque limit switches
Set open and close position and torque switches while operating valve full open and close with local push buttons. Refer to Manual E796 for limit switch setting instructions.
Step 2: Set DIP switches
Set address DIP switches to unique address as shown in the rst section of this guide. Refer to Figure 5 on page 5 for location of DIP switches. Refer to network station address switch settings on pages 6 and 7. Also remember to check baud rate of each actuator to ensure it matches the host system.
Step 3: Check network wiring
Check polarity of each network connection per wiring connections shown in Figure 3 of this guide. Ensure shield is connected at each actuator and is earth grounded at only one point. Refer to page 26 for additional instructions on network installation.
Step 4: Check network terminations
Quick Startup Guide
ECL-4005-1017 Rev. D
Bus networks require termination resistance and bias at each end of the network. Remove termination and bias on all modules except the last, most distant unit at the end of the network. Always leave termination and bias on every unit when using E>Net. See Figure 4 for location of DIP switches and jumpers for termination and bias selection. Verify quiescent line bias is 250mV minimum during no communication activity.
Step 5: Test network
Use EIM's Conguration and Control Utility (CCU) software to test each actuator. Ensure each station address is tested and verify received data. View communication signals with oscilloscope to ensure good signal strength and clean waveforms. Repeat test for each actuator on redundant network if installed.
Step 6: Verify network master configuration
If using EIM Controlinc Network Master, refer to the User Manual supplied with the system for setup details. If direct connecting to your DCS, SCADA, or PLC system, refer to the manufacturer's supplied documentation. Verify network baud rate and parity match the settings of the actuators. Verify the master is congured for the total number of actuators and database matches network address assignments per actuator location on network. Take system out of test or diagnostic mode when nished.
27
System Startup Guide
Quick Startup Guide
ECL-4005-1017 Rev. D
Step 7: Test host interface
If using EIM Controlinc Network Master, use Modbus host test software supplied with the system to test slave port(s) of the network master. If direct connect to other host equipment, use software supplied with that equipment to test actuators. Verify database for each node and I/O point by tag name and mapping of each point to operator's screen. Operate each valve open and close or to setpoint. Test each auxilliary I/O point.
Tools:
1) Speed handle or 3/8" battery drill with 1/2" thin wall socket
2) Common screwdriver
3) Multimeter (VOM)
4) Portable oscilloscope (optional)
5) Laptop computer with Windows
6) EIM Conguration and Control Utility (CCU) w/ RS485 adapter
7) Other system test software supplied with host system
8) Programming cables
9) 4-20mA calibrator for analog I/O
Section 4: System Startup Guide
October 2017
System Startup Guide
28
Section 5: Optional Phase Monitor
October 2017
Section 5: Optional Phase Monitor
If your actuator contains the optional phase monitor, then this section applies.
The phase monitor module shown in Figure 7 is mounted on the back side of the DCM 320B module facing the motor starter.
Figure 7
Quick Startup Guide
ECL-4005-1017 Rev. D
29
NOTE:
We advise using phase sentry mode rather than phase correction.
Phase sentry mode will cause the actuator to shut down if phases are out of sequence for proper electric motor rotation or a loss of phase is detected. Phase correction mode will cause the actuator to correct the phase sequence and continue to operate when phases are out of sequence. Either mode will cause the actuator to shut down if a loss of phase {single­phasing) is detected.
To select modes, do the following:
1) Remove TBM 320A termination panel.
2) Locate 3-pin jumper P9 on bottom of board marked PC and PS.
PC means Phase Correction.
PS means Phase Sentry.
3) Move the shorting strap to the desired mode selection {PC or PS).
Optional Phase Monitor
World Area Configuration Centers (WACC) offer sales support, service, inventory and commissioning to our global customers. Choose the WACC or sales office nearest you:
NORTH & SOUTH AMERICA
19200 Northwest Freeway Houston TX 77065 USA T +1 281 477 4100
Av. Hollingsworth 325 Iporanga Sorocaba SP 18087-105 Brazil
MIDDLE EAST & AFRICA
P. O. Box 17033 Jebel Ali Free Zone Dubai T +971 4 811 8100
P. O. Box 10305 Jubail 31961 Saudi Arabia T +966 3 340 8650
T +55 15 3413 8888
24 Angus Crescent
ASIA PACIFIC
Longmeadow Business Estate East
P.O. Box 6908 Greenstone No. 9 Gul Road #01-02 Singapore 629361 T +65 6777 8211
No. 1 Lai Yuan Road
1616 Modderfontein Extension 5
South Africa
T +27 11 451 3700
EUROPE
Wuqing Development Area Tianjin 301700 P. R. China T +86 22 8212 3300
Holland Fasor 6
Székesfehérvár 8000
Hungary
T +36 22 53 09 50
Strada Biffi 165
29017 Fiorenzuola d’Arda (PC)
Italy
T +39 0523 944 411
For complete list of sales and manufacturing sites, please visit
www.emerson.com/actuationtechnologieslocations or contact us at info.actuationtechnologies@emerson.com
www.emerson.com/eim
©2018 Emerson. All rights reserved.
The Emerson logo is a trademark and service mark of Emerson Electric Co.
TM
is a mark of one of the Emerson family of companies.
EIM All other marks are property of their respective owners.
The contents of this publication are presented for information purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available on request. We reserve the right to modify or improve the designs or specifications of our products at any time without notice.
Loading...