Ei Electronics RadioLINK Ei170RF User Instructions

Professional
Model
: EI17OR
F
RadioLi
N
Strobe & Vibration Pad Modul
For use with RadioLlNK Smoke/Heat/Fire Alarm
s
(Smoke / Heat / Fire Alar
m
supplied separately
)
Note:At least one RadioLlNK Smoke/Fire/Heat Alarm is required to make the
.Ei17OR
F
Alarm operational
. This is not supplied with the Ei170RF and must be obtained separately
.
Important:Read these instructions, together with those from the separate RadioLlN
K
Smoke/Heat/Fire alarms and accessories before installation
. All instruction leaflets must b
e
left with the end user after installation
.
The Ei170RF is for use with the following Ei RadioLINK Smoke/Fire/Heat Alarms and Accessories
.
Mains Multisensor/Smoke/Heat/Fire Alarms
:
Ei2110, Ei160RC & Eli 40 Series Alarms in conjunction with an Ei168RC RadioLINK Base
.
attery Powered Smoke / Heat Alarms
:
Ei3100RF, Ei3103RF, Ei3105RF, Ei405, Ei405TY, Ei605C (with RF module), Ei605TYC (with RF module)
.
Accessories
:
E1407
Manual Call Point,
Ei410
Remote Control (portable),
Ei411 H
Remote Control (wall mounted)
,
Ei428 Relay Module,
E1408
Switched Input Module,
Eli70RFS
Strobe Pane
l
This leaflet describes the installation of the Ei170RF and its integration into a total RadioLlNK Fire Alarm System, incorporating a choice of Smoke/Fire/Heat Alarms and Accessories
.
N .B
. It is essential that the Ei170RF is connected to the mains to preserve its one-week batter
y
standby
. Leaving the unit operating without mains connected will completely deplete the battery an
d
possibly damage it. (If the Ei170RF is not being used for a prolonged period and cannot be left plugge
d
in to the mains, then disconnect the battery)
.
Locatio
n
The Strobe Module should normally be fixed such that the internal strobe light can be seen from the bed
,
and the vibration pad can be placed under the mattress or pillow
. It has to be powered from the main
s
(230VAC) so a suitable socket or junction box must be available to which it can be permanently connected
.
The back-up battery in the Strobe Module must not be exposed to excessive heat such as sunshine
,
heaters, fires or the like
.
The associated RadioLINK Alarms and Accessories must be located and installed as described i
n
their own instruction leaflets
.
Strobe Module Ei170R
F
The battery must first be installed in the Strobe Module
. Open the rear compartment by squeezin
g
together the two latches as shown
in
Figure lb, and
lifting
the cover off
.
Squeez
e
Her
e
Channel
s
for mains lead
&
Vibration Pad
:
(and accesso'rie
s
if required
)
Figure la
Figure l
b
Squeeze as shown to ope
n
battery compartment
Figure
2
Plug the battery into the socket at the rear of the battery compartment as shown in Figure 2 (whil
e
holding the small latch on the battery plug, open)
. Place the battery in the compartment ensuring th
e
notch in the battery is used to leave clearance for the plug and sockets (see Figure 3)
.
Batter
y
Clearanc
e
Notc
h
Figure
3
Shows battery orientation - Dress the battery leads as shown, replace the battery cover an
d
push firmly down on the two latche
s
The Strobe Module can be left on a table or permanently fixed to the wall using the screws and plasti
c
plugs enclosed
.
If fixing to a wall, the screws should be spaced 95mm (3
.7 inches) horizontally apart
. The top screws wi
l
be 70mm (2
.7 inches) below the top surface of the Strobe Module when installed
. The template at th
e
end
-
of this leaflet can be used to locate the screws accurately
. The screws (large heads) should b
f
screwed into the wall leaving a gap of approximately 4mm (O
.15in) under the head
. Fit the keyhole slot
;
on the back of the Strobe Module over the screw heads and slide the panel down vertically into positio
n
The mains adaptor should then be- plugged into a socket (or permanently wired to a mains junction bo
:
- see overleaf)
. This mains socket must not be used for any other equipment and it must not be switche
c
off
. The mains plug
. must be readily removable (so the mains can be disconnected if necessary)
.
3
Ifconnecting
to a mains Junction Bo
x
It is preferable to permanently wire the unit into a mains junction box
. In this case remove the
plug and wire as follows
.
Warning
:
If the plug is being removed and the unit is being wired to a junction box it should b
e
installed by a qualified.electrician in accordance with the Regulations for Electrical Installation
s
published by the Institute of Engineering & Technology (UK) BS7671
. Failure to install thi
s
system correctly may expose the user to shock or fire hazards
.
First remove the power to the circuit at the distribution board
.
The mains lead wires are colour coded as follows
:
Brown:Liv
e
Blue
: Neutra
l
The wire which is coloured brown must be connected to the terminal/wire which is marked wit
h
the letter L or coloured brown
.
The apparatus is not to be earthed, so no connection is to be made to terminals or wires marke
d
with the
letterE,the symbol
O
or
coloured
green or
green/yellow
.
The wire which is coloured blue must be connected to the terminal/wire which is marked wit
h
the letter N or coloured blue
.
Vibration Pad Ei17
4
The primary vibration pad is supplied already plugged into its locking socket on the rear of the Ei170R
F
Strobe Module (see Figured a)
. Place the vibration pad under the pillow or mattress
. It is important tha
t
the person in the bed can feel the vibration – check it is sufficient to wake a person by lying on the be
d
and pressing the test button on the Strobe Module – see also Section 4, Testing and Maintaining you
r
System
. Some mattresses may not transmit sufficient vibration, and in these cases it should be fitte
d
under the pillow
. Note
: During testing, or in an actual alarm situation, the pad pulses on and off fo
r
greater effect on sleepers
.
The Strobe Module must not be exposed to dripping or splashing and items filled with liquids such a
s
vases must not be placed on or above the apparatus
.
This system uses radio to communicate between the Fire Alarms, Accessories and the Strobe Module
.
It is set-up simply by putting all of the units into "House Code Mode" and letting them automaticall
y
code with each other
. This will "House Code" the installation so that they will not accidentally signal to
,
or be affected by, nearby systems
.
The units will all communicate with each other (providing they are within range), as delivered i
.e
.
without any House Coding - however it is recommended that they are House Coded as follows
:
3.1.1
Install & power all the elements of the system
.
3.1.2
Press the House Code switch on all units – see individual instruction leaflets for switch locations
.
On the Strobe Module, the House Code switch is pressed by means of small screwdriver (or similar
,
diameter of top less than 3mm), through the access hole on the top of the unit – see figure 4
.
3.1.3
Press and hold the Strobe Module House Code button until the blue RadioLINK light comes on
.
Release it and the light will flash every five seconds
.
3
.1
.4 When all units are set into `House Code Mode' they should signal to each other and set-up thei
r
network automatically
.
3.1.5
Each unit will now flash its blue or amber light to show how many units it is RadioLINKED with
. If th
e
Strobe Module is linked to just one smoke alarm they will both flash twice
. With 6 units for example, 4 Smok
e
Alarms, a Remote Control and the Strobe Module itself, each unit will flash six times (apart from the Remot
e
Control, which does not
have this feature)
. A maximum of twelve
RF
units can be linked this
way
.
4
li
Figure
4
3.1.6
If some units flash less than the expected number of times, after being in House Code Mode fo
r
over 10 minutes) (say four times on a six unit system) they are out of range of each other
.
Follow the advice in the RadioLINK instructions supplied with the other alarms to resolve this
.
3.1.7
The units will automatically exit the House Code Mode after 30 minutes
. However we recommen
d
that you manually exit the House Code Mode by pressing and holding the House Code switch on th
e
Strobe Module until the blue light turns on, then release
. The blue light should stop flashing and a
n
`exit House Code Mode' radio signal will be sent to all other units
. Check that the amber/blue lights o
n
all other units have stopped flashing
. (if some units are still flashing it may indicate a problem with th
e
radio communication to this unit, or that the particular RadioLINK unit (models Ei3100RF, Ei3103RF
,
Ei3105RF, Ei407, Ei410, Ei411 H & Ei408) does not have this automatic cancel House Code Mod
e
feature and must be taken out of House Code Mode manually
. Check instruction leaflet supplied wit
h
the units
. Manually exiting the House Code Mode reduces the risk of accidentally House Coding you
r
RadioLINK Bases with nearby systems
.
Note
:
When the blue or amber light has stopped flashing on a unit it is out of House Code Mode — d
o
not press the House Code switch again as this will put it back into House Code Mode
.
3
.2 ADDING UNIT
S
To add units to the system simply repeat the above procedure, i
.e
. put all into House Code Mode, ne
w
as well as old units, and ensure that the number of flashes shown equals the number of units in th
e
system
. For the other RadioLINK components see their instruction leaflets
.
3
.3 RESETTING HOUSE CODE
S
Sometimes it is necessary to cancel the House Code learned i
.e
. to reset the units to the factor
y
settings
. To reset the Strobe Module to clear the House Codes, simply hold the House Code butto
n
until the blue light illuminates solidly, then starts to flash and then stops flashing, then release th
e
button, this will take about six seconds
. For other RadioLINK components see their separat
e
instruction leaflets
.
Clock Inpu
t
(if required
)
Main
s
Indicato
r
Gree
n
(main
s
disconnected
=
amber flash
/
4 seconds)
Alar
m
Red
4
.1 AFTER INSTALLATIO
N
4.1.1
Check that all RadioLINK Alarms and Accessories are powered correctly
.
4.1.2
Check that the green light on the Ei17ORF Strobe Module is continuously lit
.
4.1.3
Press the test button on all RadioLINKED Smoke/Heat/Fire Alarms, Remote Controls an
d
Manual Call Points in turn, and check that all other Smoke/Heat/Fire Alarms in the system alarm afte
r
about 4 seconds and that the strobe and vibration pad activate
. Also check that the RadioLIN
K
accessories were operated
.
N.B.
Wait 12 seconds before testing the next unit or if you wish to repeat testing
.
4.1.4 Press the Strobe Module test button
. Check the vibration pad pulses, the strobe flashes and th
e
red alarm light on the Strobe Module flashes (this will also cause the Smoke/Heat/Fire Alarms t
o
sound and also their red lights to flash rapidly)
.
4
.2 DAILY&WEEKLY TESTIN
G
Check daily that the vibration pad is in its correct position under the pillow or mattress by pressing th
e
test button on the Strobe Module
. Also check daily that the green light on the Strobe Module is o
n
constantly
. We recommend that you test your system weekly by pressing all the smoke/heat/fire alar
m
test buttons and checking that the vibration pad and strobe light operate
.
Check the Strobe Module indicator lights as follows (see figure 4
)
4.2.1 Green mains power should be constantly on
. If it is
off
check that it is plugged into the mains
,
that the socket is not switched
off,
fuses, circuit breakers etc . If the mains is off, the green light will b
e
off and the unit will be running on the rechargeable battery
. The green light will be replaced by a
n
amber flash every 4 seconds to indicate battery is satisfactory
. When this amber flash stops, th
e
battery is depleted and the mains should be reinstated (If the mains cannot be reinstated at this time
,
the depleted battery should be removed, until the mains can be re-connected)
.
4.2.2 Press the Test button on the Strobe Module and check that the strobe flashes, the red alarm ligh
t
flashes and that the blue RadioLINK light illuminates on for about 3 seconds indicating the radio tes
t
signal is being sent to the Smoke/Fire/Heat alarms and any accessories
.
4
.2 .3
Check that the amber fault light is not flashing every 4 seconds
. If it is check that the primar
y
vibration pad is connected firmly to the socket with its plug latched (see figure 1). If the primar
y
vibration connection is satisfactory, it is probably indicating that the battery is depleted
. Connect th
e
unit to the mains and check after 24 hours that the amber fault light has ceased flashing
.
4
.3 PERIODIC TESTING OF RECHARGEABLE BATTER
Y
4
.3
.lThe rechargeable battery can take up to 20 hours to charge when the unit, is first powered up
. It i
s
then maintained in a fully charged state by continuous trickle charge . In the event of a mains failure th
e
battery will power the system in standby for a week and then be capable of at least 4 minutes of alarm
.
If the mains fails, the green light is extinguished and the amber light flashes every 4 seconds on th
e
Strobe Module to indicate it is on battery power . The amber light will also flash every 4 seconds if th
e
battery is almost depleted
. Both the amber lights
will
go
off
to indicate the battery is depleted and the uni
t
is totally unpowered .The battery will last 5 years in normal use provided it is not exposed to extremes o
f
temperature for prolonged periods, or fully discharged & charged a large number of times
.
We recommend that the functioning of the rechargeable battery is checked at least yearly as follows:-
4.3.2 Ensure the Strobe Module has been mains powered for at least the previous 20 hours for th
e
battery to charge
.
4
.3 .3
Turn off the mains power to the unit by unplugging it or switching off the circuit at the distributio
n
board
. Check that the green light goes
off
and the amber light starts to flash
.
4.3.4 Press the Strobe Module test button for 20 seconds and check the strobe flashes brightly, th
e
pad vibrates strongly and that all the RadioLINK alarms trigger
. Check that the red alarm light-flashe
s
while the test button is pressed
. (Cover the strobe light with a card to stop this dazzling you whil
e
looking at the red light) . If the red light goes off, or if the strobe is weak, or if the vibration pad is weak
,
6
the battery will need to be replaced
. Contact the nearest address in this leaflet for advice about gettin
g
a replacement
. The battery also needs to be replaced if it is over 5 years old (see "replace battery by
"
date on side panel)
. To remove the battery reverse the instructions in the first part of section 2
. Contac
t
nearest address at the end of this leaflet on obtaining a replacement battery
.
Replace the entire Strobe Module after 10 years operation . (see "replace unit by" date on side panel)
.
If the units fail any of the above tests after installation, the system has probably been incorrectl
y
installed and/or all units are not House Coded correctly. Check carefully that all units are powered
. I
f
the power lights on any of the mains units are not on constantly, or flashing once every 45 seconds o
n
battery powered units, check the connections to the mains and/or the connections to the batteries
.
(See individual unit instruction leaflets if necessary)
. For mains units check that the power is not of
f
(i.e. due to a tripped circuit breaker or fuse)
.
The wiring to the primary vibration pad is monitored and if the vibration pad is removed or if its wiring i
s
open circuit, the strobe and the amber fault light will flash (this may take up to approximately 45 seconds)
.
There are no user serviceable parts in this unit (apart from the battery)
. If the unit (apart from th
e
battery) is thought to be defective, it must be returned to the nearest address at the end of this leafle
t
for repair or replacement (see "Five Year Guarantee" section)
.
Some troubleshooting items (including RF links) are specific to individual units and may not be covere
d
in this leaflet
. In these cases the more comprehensive unit leaflet should be consulted
.
OTHER FEATURE
S
Strobe&Vibration Pad Module -
Auxiliary
Outputs - AUX 1&AUX 2:The two auxiliary outputs ar
e
activated when the Strobe Module is in alarm . The Aux 1 socket can supply up to 180mA at 12 Volts
.
The AUX 2 socket can supply up to 20mA at 12 Volts
.
N.B. The AUX 2 socket can be used for low power devices such as pager trigger inputs
.
Note:As supplied the two auxiliary sockets AUX
. 1 and AUX
. 2 are protected by latched plastic plugs whic
h
must be removed before the auxiliary devices can be plugged in (see figure 5)
. These plugs can be remove
d
by pressing the latch lever (on the side nearest the "AUX" marking) before gently pulling the plug off
.
"Clock Input" Socket
:
A suitable alarm clock signal (with a 5 to 24 Volts AC or DC output
electrically isolated from the mains supply) can be connected to this input socket with a 3
.5mm mon
o
jack plug
. (see figure 4) When the alarm clock triggers, the vibration pad turns on continuously (i.e. i
t
is not pulsed) to wake the person, but the internal strobe or auxiliary outputs are not activated
. Thi
s
lets the user know it is a wake-up call and not a fire.. Therefore the user needs only one vibration pa
d
under their pillow or mattress – rather than two, one for the Fire Alarm and one for the alarm clock
.
ACCESSORIE
S
Ei178 - Auxiliary Strobe:(draws 180mA)
. Supplied with 10m of cable and a suitable plug fo
r
connection to the auxiliary socket. It should be plugged into AUX 1
. It.. can be located, for example
,
where it is readily seen during the day (e
.g
. downstairs hallway)
.
Ei174 - Auxiliary Vibration Pad:(draws 120mA)
. Supplied with 5m of cable and a suitable plug fo
r
connecting to the auxiliary socket
. It should be plugged into AUX 1
.
Ei410 - RadioLINK Remote Control
(portable)
: The Remote Control Ei410 allows you to Test, Hush o
r
Locate suitable RadioLlNK Smoke/Fire/Heat Alarms
.
Ei411 H - RadioLINK Remote Control
(wail mounted)
: This wall mounted switch allows you to Test
,
Hush or Locate suitable RadioLINK Smoke/Fire/Heat Alarms
. (Note
: the Strobe Module Ei17OR
C
ignores a RadioLINK LOCATE message and will continue to flash the strobe and drive the vibratio
n
pad as long as it gets an RF alarm signal)
.
Ei407 - RadioLINK Manual Call Point
:
This allows remote triggering of RadioLINK alarms / accessorie
s
and is ideal where emergency situations are identified and which require immediate evacuation
.
7
Ei428 - RadioLINK Relay Module
:
This module contains a set of relay contacts that switch upo
n
receipt of an alarm signal from suitable RadioLINK Smoke/Fire/Heat Alarms
.
EHi70RFS
: An additional RadioLINK Strobe Module, without a vibration pad (i.e. Strobe only) is availabl
e
for use in a day rooms etc
. to give a visual fire warning
.It is supplied with a blanking plug, without a cabl
e
attached, which connects into the primary vibration pad socket (marked "PAD") to prevent the amber faul
t
light and strobe activating, indicatingafault (which would occur if the socket was left empty)
.
Ei408 - RadioLINK Switched Input Module:This allows panels or other devices with Volt-free rela
y
outputs to trigger the RadioLlNK system, including the Ei170RF
.
Primary Vibration Pa
d
Template for Mounting Screw
s
Ei Electronics guarantees this device for five years from the date of purchase against any defects tha
t
are due to faulty materials or workmanship
. This guarantee only applies to normal conditions of use an
d
service, and does not include damage resulting from accident, neglect, misuse, unauthorise
d
dismantling, or contamination howsoever caused
. This guarantee excludes incidental and consequentia
l
damage
. If this device should become defective within the guarantee period, it must be returned to th
e
nearest address given below, carefully packaged, with the problem clearly stated along with proof of th
e
date of purchase
. We shall at our discretion repair or replace the faulty unit
.
Aico Ltd.Mile End Business Park
,
Maesbury Rd, Oswestry, Shropshire SY10 8NN, U
.K
.
Tel
: 0870 758 400
0
w
ww
.aico
.co.uk
Ei Electronics.Shannon, Co Clare, Ireland
.
Tel
:+353 (0)61 47127
7
w ww
.eielectronics
.co
m
Remove
protectio
n plug before connectin
g
accessories
Drill Holes Her
e
Figure
5
The crossed out wheelie bin symbol that is on you
r
product indicates that this product should not be dispose
d
of via the normal household waste stream
. Prope
r
disposal will prevent possible harm to the environment o
r
to human health. When disposing of this product pleas
e
separate it from other waste streams to ensure that it ca
n
be recycled in an environmentally sound manner
. Fo
r
more details on collection and proper disposal, pleas
e
contact your local government office or the retailer wher
e
you purchased this product
.
P/N B16308
RevO
©
Ei Electronics
2008
Loading...