Ei Electronics Ei650iW, Ei650iC, Ei650i, Ei650W, Ei650C User Manual

...
Battery Powered Smoke Alarms Ei650 Series
Read and retain carefully for as long as the product is being used. It contains vital information on the operation and installation of your Smoke Alarm. The leaflet should be regarded as part of the product.
If you are just installing the unit, the leaflet must be given to the householder. The leaflet is to be given to any subsequent user.
Ei650
1. See table 2 for standard features and operation
2. See table 3 for intelligent features and operation
3. Certain Alarms may be supplied (on request) with the appropriate RF module fitted
Standard
Table 1
Model
Intelligent
2
1
3
Ei650C
Ei650W
Ei650iC
Ei650i
Ei650iW
No
Yes
No
Yes
No
Hardwired
Interconnect
Hardwired
Interconnect
No
No
Yes
Yes
Yes
Yes
RF
Capability
RF
Capability
No
3
Page
CONTENTS
1
2
3
4
5
6
7
8
9
10
11
12
13
14
QUICK START GUIDE
LOCATION & POSITIONING
INSTALLATION
INTERCONNECTION - HARD WIRED
TESTING, MAINTENANCE & POWER SUPPLY
MONITORING
FIRE SAFETY ADVICE
SMOKE ALARM LIMITATIONS
RADIOLINK MODULES
GETTING YOUR ALARM SERVICED
FIVE YEAR GUARANTEE
TROUBLESHOOTING
Ei650 ALARM INDICATORS
Ei650i ALARM INDICATORS
CONTACT US
4
6
12
16
18
23
26
27
28
28
29
30
31
40
4
1. Quick Start Guide
LOCATE CORRECT SITING POINT FIX BASEPLATE TO CEILING
TWISTING THE UNIT ON TO
THE BASE AUTOMATICALLY CONNECTS THE BATTERY
PLACE ALARM & TWIST ON TO BASE
ALARM SHOULD BE CEILING MOUNTED AT LEAST 300MM FROM WALLS & OBSTRUCTIONS, IDEALLY CENTRALLY IN ROOM/AREA
TWISTING THE UNIT ON TO
THE BASE AUTOMATICALLY CONNECTS THE BATTERY
Quick Start Guide
PLACE ALARM & TWIST ON TO BASE
TEST ALARM
ALARM SHOULD BE CEILING MOUNTED AT LEAST 300MM FROM WALLS & OBSTRUCTIONS, IDEALLY CENTRALLY IN ROOM/AREA
TEST ALARM AT LEAST WEEKLY
PRESS THE TEST BUTTON
5
2. Location & Positioning
Introduction
Congratulations on purchasing an Ei650 Series Alarm. You can easily install these Smoke Alarms throughout the property on escape routes, on each storey, in corridors & in closed rooms to give warning of fire.
Models Ei650C and Ei650iC can be interconnected with hard wiring (or RadioLINK plug-in modules) to give the loudest alarm sound level throughout the house.For wireless interconnection add the RadioLINK plug-in module (This module must be purchased separately).
Models Ei650W and Ei650iW can be wirelessly interconnected by adding the RadioLINK plug-in module (This module must be purchased separately).
Models Ei650 and Ei650i are stand alone Smoke Alarms and cannot be interconnected by either hardwire or RadioLink modules.
Note: Certain Smoke Alarms may be supplied (on request) with the appropriate RF module fitted.
SMOKE ALARMS - Ei650 Series
Sufficient smoke must enter your Smoke Alarm before it will respond. Your Smoke Alarm needs to be within 7.5 metres of the fire to respond quickly. Smoke Alarms also need to be in positions where they can be heard throughout the property, so they can wake you and your family in time for everyone to escape. A single Smoke Alarm will give some protection if it is properly installed, but most homes will require two or more (preferably interconnected) to ensure that a reliable early warning is given. For recommended protection you should put individual Smoke Alarms in all rooms where fire is most likely to break out (apart from the kitchen and bathroom).
6
Your first Smoke Alarm should be located between the sleeping area and the most likely sources of fire (living room for example), but it should not be more than 7.5 metres from the door to any room where a fire may start and block your escape from the house.
Multi-Storey Dwellings
If your home has more than one floor, at least one Smoke Alarm should be fitted on each level (see Figure 1). Preferably the Smoke Alarms should be interconnected so as to give sufficient warning throughout the property. RadioLINK plug-in modules are ideal in this situation as the Smoke Alarms will then interconnect using Radio Frequency (RF) signals - so no wiring is required.
Figure 1 illustrates where Smoke Alarms and Heat Alarms should be located in a typical two storey house. Note the spacings as given in figures 1&2 which ensure the early detection of fire and that the warning will be heard.
For additional protection, locate Heat Alarms in rooms adjoining escape routes ­kitchens, garages, boiler houses etc. where Smoke Alarms are unsuitable. Install within 5.3m of potential sources of fire.
Single Storey Dwelling
If the premises is one storey you should put your first Smoke Alarm in a corridor or hallway between the sleeping and living areas. Place it as near to the living area as possible, but make sure that it can be heard loudly enough in the bedroom to wake someone. See Figure 2 for placement example.
In houses with more than one sleeping area, Smoke Alarms should be placed between each sleeping area and the living area and it is recommended that Heat Alarms should be placed in the kitchen & garage.
7
8
Recommended Protection
Fire authorities recommend you put individual Smoke Alarms in or near all rooms where fire is most likely to break out (apart from the locations to avoid e.g kitchens & bathrooms - see Section 3). The living room is the most likely place for a fire to start at night, followed by the kitchen (where a Heat Alarm is recommended) and then the dining room. Consideration should be given to installing Smoke Alarms in any bedrooms where fires might occur, for instance, where there is an electrical appliance such as an electric blanket or heater, or where the occupant is a smoker. In addition, consideration should be also given to installing Smoke Alarms in any rooms where the occupant is unable to respond very well to a fire starting in that room, such as an elderly or sick person or a very young child.
Checking Smoke Alarms Can Be Heard
With the Smoke Alarms sounding in their intended locations check that the alarm can be heard in each bedroom with the door closed, above the sound of any TV/audio systems. The TV/audio systems should be set to a reasonably loud conversation level. If you cannot hear the alarm over the sound of the TV/audio system, the chances are it would not wake you. Interconnecting the Smoke Alarms using either a hard-wired interconnection (where the feature is present) or RadioLINK plug-in modules will help to ensure that the alarm will be heard throughout the property.
Positioning
Ceiling Mounting
Hot smoke rises and spreads out, so a central ceiling position is the recommended location. The air is “dead” and does not move in corners, therefore Smoke Alarms must be mounted away from corners. Keep at least 300mm from walls and corners
Bedroom
Bedroom
Bedroom
L
iving Roo
m
Kitchen
Ba
thr
oom
D
ining Roo
m
Figure 2
For minimum protection
- Smoke Alarm on each storey
- every 7.5 metres of hallways and escape routes
- within 3 metres of all bedroom doors
- all Alarms interconnected (where feature is present)
For recommended protection
(in addition to the above):
- Smoke Alarms in every room (except kitchens and bathrooms)
- Heat Alarms located in kitchens, garages etc. within 5.3m of potential fire sources
9
Figure 1
(see Figure 3). Additionally, mount the alarm at least 300mm from any light fitting or decorative object which might prevent smoke entering the Smoke Alarm.
We do not recommend wall mounting of Smoke Alarms.
On a Sloping Ceiling
With a sloping or peaked ceiling install a Smoke Alarm within 600mm of the peak (measured vertically). If this height is less than 600mm it is regarded as being flat
(see Figure 4).
10
DEAD AIR SURFACE
S
NEVER WITHIN
300
mm
O
F ANY CORNER
IDEAL IN CENTRE
OF C
EILIN
G
SMO
KE ALARM
S
<600mm
Figure 3
Figure 4
Locations to avoid
DON’T place Smoke Alarms in any of the following areas:
• Bathrooms, kitchens, shower rooms, garages or other rooms where the smoke
alarm may be triggered by steam, condensation, normal smoke or fumes. Keep at least 6 metres away from sources of normal smoke/fumes.
• Locate away from very dusty or dirty areas as dust build-up in the chamber can impair
performance. It can also block the insect screen mesh and prevent smoke from entering the smoke detector chamber.
• Do not locate in insect infested areas. Small insects getting into the smoke
detector chamber can cause intermittent alarms.
• Places where the normal temperature can exceed 40°C or be below 0°C (e.g.
attics, furnace rooms, directly above ovens or kettles etc.) as the heat/steam could cause nuisance alarms.
• Near a decorative object, door, light fitting, window moulding etc., that may
prevent smoke or heat from entering the Alarm.
• Surfaces that are normally warmer or colder than the rest of the room (e.g. attic
hatches). Temperature differences might stop smoke or heat from reaching the alarm.
• Next to or directly above heaters or air conditioning vents, windows, wall vents etc.
that can change the direction of airflow.
• In very high or awkward areas (e.g. over stairwells) where it may be difficult to
reach the Alarm (for testing & hushing).
• Locate the Alarm at least 1m from dimmer controlled lights and wiring as some
dimmers can cause interference.
11
• Locate alarm at least 1.5m and route any interconnectedwiring at least 1m away from
fluorescent light fittings as electrical “noise” and/or flickering may affect the Alarm.
3. Installation
Installation Procedure
1. Select a location complying with the advice in Section 2.
2. Remove the mounting plate from the Smoke Alarm by twisting it in an anti-clockwise direction (see Figure 5).
3. Place the mounting plate on the ceiling exactly where you want to mount the Alarm. With a pencil, mark the location of the two screw holes.
4. If interconnecting Smoke Alarms using hard-wired connections, run suitable twin core cabling to the marked locations of each Alarm. Make the connections to the Alarm (see Section 4).
5. Taking care to avoid any electrical wiring in the ceiling, drill holes using a 5.0mm drill bit through the centre of the marked locations. Push the plastic screw anchors provided into the drilled holes. Screw the mounting plate to the ceiling.
If using RadioLINK Smoke Alarms then they should be mounted with antennas in the same orientation (i.e. essentially parallel). This means
12
ROTATE UNIT ANIT-CLOCKWISE
UNIT WILL NOT TWIST OFF - IT MAY BE
TAMPERPROOFED - SEE FIGURE 8c
Figure 5
Loading...
+ 28 hidden pages