Shannon Free Zone, Shannon, Co. Clare, Ireland.
Ph.+353 61 471277 Fx.+353 61 471053
Email. eielectronics@eiltd.ie
Web: www.eielectronics.com
E & OE As our policy is one of continuous product development, we reserve the right to alter product details without prior notice. Ei261ENRC DataSht RevA
Remote System Control capability
Easi-fit base
Proven electrochemical sensor
Tamper-proof rechargeable Lithium battery back-up
Unique easy to replace sensor module
Memory feature records if CO has been detected
Easy to use Test/Hush button
Automatic self diagnostics
Pre alarm led flashes at 50ppm CO
Loud distinctive alarm (85 dB(A) at 3 metres)
Power, alarm and fault indicator lights
Interconnectable to other Ei mains powered alarms
Fast CO test mode
Kitemarked to BSEN 50291:2001
5 Year guarantee (limited)
Product Description
The Ei261ENRC is a Carbon Monoxide(CO) alarm powered by 230V
AC mains power, and has built in tamper proof rechargeable Lithium
cells that act as a battery back up in the event of mains failure. These
rechargeable Lithium cells are designed to have a ten-year life and
outlast the life of the CO alarm. They will provide up to 4 weeks of CO
alarm operation without mains power.
The Ei261ENRC also has Remote Control capability - allowing the
alarm to be controlled remotely from a Control Switch (Ei1529RC). This
then allows remote Test, Locate and Hush functions to be performed. If
the Ei261ENRC is also interconnected to other Ei „RC‟ mains powered
alarms, then the whole system can be controlled remotely. Up to twelve
alarms can be interconnected. A Manual Call Point (MCP401RC) is
also available.
The Ei261ENRC is supplied with an Easi-Fit base that allows very
quick and simple installation of the alarm, combined with simple
removal and replacement. The Easi-Fit base automatically connects
both mains power and battery as the alarm slides on to the base.
The Ei261ENRC uses a high performance electrochemical sensor to
sense CO presence. The sensor can be replaced after 5 years to
provide a combined 10 year protection against CO gas.
The Ei261ENRC has built in circuitry to aid suppression of voltage
transients and RF interference to further reduce the chances of false
alarms.
Operation
The green indicator will illuminate to show mains power is
present
The horn will sound and the red indicator will flash at
different speeds to indicate the presence of various levels of
CO gas – slow flash indicating low levels and rapid flash to
indicate high levels
The horn will beep and the amber indicator will flash every
40 seconds to indicate a fault on the sensor
The horn will beep every 40 seconds to indicate a the
battery back up is depleted and needs recharging
The “Test/Hush” button will either silence false alarms (if
briefly pressed) or perform a unit self test (if pressed and
held). Note that the alarm cannot be silenced when sensing
a CO level of 300ppm or above
Memory Feature – after the unit has been in alarm, the red
indicator will flash every 40 seconds at a rate indicating the
CO level previously detected. Pressing the “Test/Hush”
button will also cause the red indicator to flash at a rate
specific to the previously sensed CO level.
When interconnected to other Ei mains powered alarms, an
alarm on one detector will trigger all other interconnected
alarms (only the triggered alarm will flash a red indicator)
MAINS POWERED 230V~
Remote System Control Capability
& Rechargeable Battery Back-Up
Shannon Free Zone, Shannon, Co. Clare, Ireland.
Ph.+353 61 471277 Fx.+353 61 471053
Email. eielectronics@eiltd.ie
Web: www.eielectronics.com
E & OE As our policy is one of continuous product development, we reserve the right to alter product details without prior notice. Ei261ENRC DataSht RevA
Technical Specification
Sensor Electrochemical sensor
Sensitivity: Meets BS EN 50291:2001
Button Test: Checks the electronics and horn
Fast CO Test Mode: Alarm sounds and red indicator
flashes as soon as CO is detected –
the rate of flash indicating the CO
level
Memory Feature After the unit has been in alarm, the red
indicator will flash every 40 seconds at a
rate indicating the CO level previously
detected. Pressing the “Test/Hush”
button will also cause the red indicator
to flash at a rate specific to the
previously sensed CO level.
Automatic Self-Test: Horn beeps and amber fault light
flashes every 40 seconds if a sensor
fault is found
Supply Voltage: 230V AC, 50 Hz
Battery back up: Rechargeable Lithium cells
Dimensions: 126 x 150 x 42 mm
Weight: 300g
Power-On Indicator: Continuous green LED
Alarm: Electronic Piezoelectric horn
Alarm Sound Output: 85dB(A) (minimum) at 3m
Alarm Status: Red LED flashes and horn sounds
Normal Operating
Temperature Range: -10o to +40oC
Humidity Range: 15% to 95% Relative Humidity
Interconnect: Up to 12 interconnected
- Ei261ENRC/261DENRC CO alarm
- Ei161RC/164RC/166RC smoke or
heat alarms
- Ei128RBU relay base
Use with optional control (see below)
Optional Controls: - Ei1529RC Control Switch
- MCP401RC Manual Call Point
Fixing: Easi-Fit mounting base
Plastic material: UL94VO flame retardant
Guarantee: 5 year (limited)
Approvals: Kitemarked to BSEN 50291:2001,
(License no. KM86596) and CE
certified
Specifications are subject to change
System Wiring
Wiring for Interconnected Alarms with optional Remote System Control Switch & Manual Call Point
Ensure correct wiring of the alarms and switches as mixing Live and Neutral will blow / damage interconnected units.