High sensitivity – responds to all standard fires
Relay contacts rated at 30VDC/1 AMP
Power supply voltage 10.5-30VDC
Interconnect up to 12 other alarms
Circular Easy-Fit mounting base for quick
installation
Alkaline battery back up
Low battery warning
Built in sounder
Test/hush button
Kitemarked to BS EN 14604:2005
5 year guarantee
Product Description
The Ei186 is a smoke alarm that is designed to operate
with suitable 8-30 volt control panels and to provide a
loud local alarm. It senses smoke using the light scatter
principle, giving a quick response to visible smouldering
fires
The Ei186 has advanced features such as the ability to
interconnect up to twelve alarms to allow all alarms to
sound if just one of the interconnected alarms should be
triggered.
Relay contacts (normally open and closed supplied) are
available for triggering the panel itself and its associated
ancillary products, such as extra loud sirens, magnetic
door holders etc.
The Ei186 is easily installed and comes supplied with all
necessary screw fixings.
Operation
The smoke detector will activate the built in sounder
upon sensing smoke particles
The smoke detector will automatically reset itself
and silence the sounder when smoke particles are
no longer present in the sensing chamber
The built in sounder will provide a minimum sound
output of 85dB at 3m
The “Test/Hush” button will silence nuisance alarms
if any
The “Test/Hush” button will test detector circuitry,
sounder,
relay and activate all interconnected alarms

Shannon Free Zone, Shannon, Co. Clare, Ireland.
Ph.+353 61 471277 Fx.+353 61 471053
Email. eielectronics@eiltd.ie
Web: www.eielectronics.com
E & OE As our policy is one of continuous product development, we reserve the right to alter product details without prior notice. Ei186 DataSht RevB
Installation & Placement
Alarms should be placed in accordance with the general guidelines shown in
the diagram above. These recommendations are based on the problem of
areas of “dead air” close to corners of rooms and apexes of ceilings, which
could result in the prevention of heat reaching the heat detector
Please consult the Instruction Leaflet supplied with the Ei186 for detailed
instructions as to how to correctly install and position the heat detector
Important Precaution:
Do not install the actual smoke/heat
alarm itself in new or renovated
buildings until all work is completed
(including floor coverings) and the
building has been fully cleaned.
(Excessive dust and debris from
building work can contaminate the
smoke chamber and cause
problems, and it will also invalidate
the guarantee). If it must be
installed, cover it completely,
particularly around the edges, with
a dust cover (eg. a plastic bag),
until all cleaning is finished..
Technical Specification
Sensor: Optical, uses light scatter from
smoke particles
Sensitivity: Complies with BS 5446 Part 1:
2000
Source: Contains no radioactive material
Airspeed: Essentially immune to the effect
of airspeed.
Button Test: Simulates the effect of heat and
checks electronics and horn.
Supply Voltage: 10.5 to 30VDC
Alarm: Piezoelectric horn
in unit
Alarm Sound Output: 85dB (minimum) at 3m
Temperature Range: 0 to 40°C
Humidity Range: 0% to 90% Relative Humidity
Fixing: Screw fixings supplied
Plastic material: UL94HB flame retardant
Dimensions: 145mm diameter x 75mm depth
Weight: 370 g
Warranty: 5 year (limited) warranty
Approvals: Kitemarked to BS EN 14604:2005,
CE Approved
Specifications are subject to change