Ei Electronics Ei186 User Manual

Shannon Free Zone, Shannon, Co. Clare, Ireland.
Ph.+353 61 471277 Fx.+353 61 471053 Email. eielectronics@eiltd.ie Web: www.eielectronics.com
E & OE As our policy is one of continuous product development, we reserve the right to alter product details without prior notice. Ei186 DataSht RevB
High sensitivity – responds to all standard fires Relay contacts rated at 30VDC/1 AMP Power supply voltage 10.5-30VDC Interconnect up to 12 other alarms Circular Easy-Fit mounting base for quick
installation
Alkaline battery back up Low battery warning Built in sounder Test/hush button Kitemarked to BS EN 14604:2005 5 year guarantee
Product Description
The Ei186 is a smoke alarm that is designed to operate with suitable 8-30 volt control panels and to provide a loud local alarm. It senses smoke using the light scatter principle, giving a quick response to visible smouldering fires
The Ei186 has advanced features such as the ability to interconnect up to twelve alarms to allow all alarms to sound if just one of the interconnected alarms should be triggered.
Relay contacts (normally open and closed supplied) are available for triggering the panel itself and its associated ancillary products, such as extra loud sirens, magnetic door holders etc.
The Ei186 is easily installed and comes supplied with all necessary screw fixings.
Operation
The smoke detector will activate the built in sounder
upon sensing smoke particles
The smoke detector will automatically reset itself
and silence the sounder when smoke particles are no longer present in the sensing chamber
The built in sounder will provide a minimum sound
output of 85dB at 3m
The “Test/Hush” button will silence nuisance alarms
if any
The “Test/Hush” button will test detector circuitry,
sounder, relay and activate all interconnected alarms
Shannon Free Zone, Shannon, Co. Clare, Ireland.
Ph.+353 61 471277 Fx.+353 61 471053 Email. eielectronics@eiltd.ie Web: www.eielectronics.com
E & OE As our policy is one of continuous product development, we reserve the right to alter product details without prior notice. Ei186 DataSht RevB
Model Ei186 Optical
Installation & Placement
Alarms should be placed in accordance with the general guidelines shown in the diagram above. These recommendations are based on the problem of
areas of “dead air” close to corners of rooms and apexes of ceilings, which
could result in the prevention of heat reaching the heat detector Please consult the Instruction Leaflet supplied with the Ei186 for detailed
instructions as to how to correctly install and position the heat detector
Important Precaution:
Do not install the actual smoke/heat alarm itself in new or renovated buildings until all work is completed (including floor coverings) and the building has been fully cleaned. (Excessive dust and debris from building work can contaminate the smoke chamber and cause problems, and it will also invalidate the guarantee). If it must be installed, cover it completely, particularly around the edges, with a dust cover (eg. a plastic bag), until all cleaning is finished..
Technical Specification
Sensor: Optical, uses light scatter from
smoke particles
Sensitivity: Complies with BS 5446 Part 1:
2000
Source: Contains no radioactive material
Airspeed: Essentially immune to the effect
of airspeed.
Button Test: Simulates the effect of heat and
checks electronics and horn.
Supply Voltage: 10.5 to 30VDC
Alarm: Piezoelectric horn
in unit
Alarm Sound Output: 85dB (minimum) at 3m
Temperature Range: 0 to 40°C
Humidity Range: 0% to 90% Relative Humidity
Fixing: Screw fixings supplied
Plastic material: UL94HB flame retardant Dimensions: 145mm diameter x 75mm depth
Weight: 370 g Warranty: 5 year (limited) warranty Approvals: Kitemarked to BS EN 14604:2005,
CE Approved
Specifications are subject to change
Loading...