Ei Electronics Ei184 User Manual

Shannon Free Zone, Shannon, Co. Clare, Ireland.
Ph.+353 61 471277 Fx.+353 61 471053 Email. eielectronics@eiltd.ie Web: www.eielectronics.com
E & OE As our policy is one of continuous product development, we reserve the right to alter product details without prior notice. Ei184 DataSht RevB
Fixed temperature fast response thermistor type
sensor, range 54°C to 62°C
Supply voltage 10.5 – 30 VDC Test/Hush button Interconnect up to 12 alarms Relay contacts Built in sounder Automatic reset facility Kitemarked to BS5446-2: 2003 5 year guarantee
Product Description
The Ei184 is a Heat Alarm that is designed to operate with suitable 8-30 volt control panels and to provide a loud local alarm.
The Ei184 has advanced features such as the ability to interconnect up to twelve alarms to allow all alarms to sound if just one of the interconnected alarms should be triggered.
Relay contacts (normally open and closed supplied) are available for triggering the panel itself and its associated ancillary products, such as extra loud sirens, magnetic door holders etc.
The Ei184 is ideal for use in kitchens and garages, where the use of optical or ionisation alarms would lead to unwanted nuisance alarms.
The Ei184 is easily installed and comes supplied with all necessary screw fixings..
Operation
The heat alarm will activate the built in sounder
upon detecting heat that reaches 58ºC
The heat alarm will automatically reset itself and
silence the sounder when the temperature drops below the preset level.
The built in sounder will provide a minimum sound
output of 85dB at 3m
The “Test/Hush” button will silence nuisance alarms
if any
The “Test”/Hush button will simulate the effect of
heat and tests sensor, electronics and horn-use to check performance at least monthly
Shannon Free Zone, Shannon, Co. Clare, Ireland.
Ph.+353 61 471277 Fx.+353 61 471053 Email. eielectronics@eiltd.ie Web: www.eielectronics.com
E & OE As our policy is one of continuous product development, we reserve the right to alter product details without prior notice. Ei184 DataSht RevB
Model Ei184 Heat Alarm
Installation & Placement
Alarms should be placed in accordance with the general guidelines shown in the diagram above. These recommendations are based on the problem of
areas of “dead air” close to corners of rooms and apexes of ceilings, which
could result in the prevention of heat reaching the heat detector Please consult the Instruction Leaflet supplied with the Ei184 for detailed
instructions as to how to correctly install and position the heat detector
Important Precaution:
Do not install the actual smoke/heat alarm itself in new or renovated buildings until all work is completed (including floor coverings) and the building has been fully cleaned. (Excessive dust and debris from building work can contaminate the smoke chamber and cause problems, and it will also invalidate the guarantee). If it must be installed, cover it completely, particularly around the edges, with a dust cover (eg. a plastic bag), until all cleaning is finished..
Technical Specification
Sensor: Thermistor
Sensitivity: Complies with BS 5446 Part 2:
2003
Source: Contains no radioactive material
Airspeed: Essentially immune to the effect
of airspeed.
Button Test: Simulates the effect of heat and
checks electronics and horn.
Supply Voltage: 10.5 to 30VDC
Alarm: Piezoelectric horn
in unit
Alarm Sound Output: 85dB (minimum) at 3m
Temperature Range: 0 to 40°C
Humidity Range: 0% to 90% Relative Humidity
Fixing: Screw fixings supplied
Plastic material: UL94HB flame retardant Dimensions: 145mm diameter x 75mm depth
Weight: 310 g Warranty: 5 year (limited) warranty Approvals: Kitemarked to BS5446-2:2003, CE
Approved
Specifications are subject to change
Loading...