Ei Electronics EI181, EI180, EI184, EI183, EI185 Instructions Manual

READ THIS FIRST
CHECK OPERATION OF SYSTEM
TEST BUTTON OPERATES ON ALL ALARMS.
ALL INTERCONNECTED ALARMS OPERATE WHEN EACH TEST BUTTON IS PRESSED FOR 10 SECONDS.
(EI181/184/186 ONLY) IF THE UNIT BEEPS EVERY 40 SECONDS FOR OVER 20 MINUTES THE
BATTERY IS PROBABLY DEPLETED. REMOVE UNIT FROM CEILING (SEE FIG 1) AND REPLACE BATTERY.
DO NOT ATTEMPT TO OPEN THE ALARM AS IT IS
PERMANENTLY SEALED FOR SAFETY.
IF A NUISANCE ALARM OCCURS PRESS THE
TEST/HUSH BUTTON TO SILENCE THE ALARM
FOR 10 MINUTES.
LOCATING ALARMS
SMOKE ALARMS
Sufficient smoke must enter the Smoke Alarm before it will respond. The Smoke Alarm needs to be within 7.5 metres (25 ft) ofthe fire to respond quickly.It also needs to be ina position where its alarm can be heard throughout your home, so it can wake the occupants in time for all to escape. A single Smoke Alarm will give some protection if it is properly installed, but most homes will require two or more to ensure that a reliable early warningis given. For maximum protection youshould put individual Smoke Alarms in all the rooms where fire is most likely to break out, (apart from kitchens, bathrooms etc. see Locations to Avoid).
A Smoke Alarm should be located between the sleeping area and the most likely sources of fire (living room or kitchen for example).It should not be morethan 7.5 metres (25ft) from the door to any room where a fire might start on the escape route from the house.
Important: These Smoke/Heat Alarms are designed for a single occupancy in a residential type environment.
ASmoke Alarm should be sitedwithin 3m of bedroom doorsfor improved audibility.
HEAT ALARMS
The Heat Alarm gives a fire warning when the temperature at the unit reaches 58°C. It is ideal for kitchens, garages, boiler housesand other areas where thereare normally high levelsof fumes, smoke or dust i.e. places where Smoke Alarmscannot be installed without the risk of excessive nuisance alarms.
A Heat Alarm should only be used in a room adjoining an escaperoute, in conjunction with SmokeAlarms on the escape routes.
All the Heat Alarms and Smoke Alarms should be interconnected to ensure the early warning will be heard, particularly by somebody sleeping. A properly designed early warning fire system ensures the alarm is given before the escape routes become blocked with smoke. Therefore, there must be Smoke Alarms along the escape routes as Heat Alarms would not give sufficient warning. However, a fire in a closed room (e.g. kitchen) adjoining the escape route, can eventually cause the corridor to become smoke-logged due to smoke leaking out from around the door before adequate warning can be given by detectors in the corridor. (Smoke leaking outfrom a room is often cool andslow moving so it can take a long time to rise to the ceiling, and travel to a detector which could be some distance away). A Heat Alarm in the closed roomwill give early warning of firein that room and help overcome this problem.
RECOMMENDED LOCATIONS
Figure 2 illustrates where Smoke Alarms and Heat Alarms should be located in a typical two storey house. Note the spacingsin “Recommended Protection” whichensure the early detection of fire and the warning will be heard.
Locate Heat Alarms in rooms adjoining or on escape routes ­kitchens, garages,boiler houses etc. where SmokeAlarms are unsuitable. Install within 5.3m (17 feet) of potential sources of fire.
Single Storey Dwelling.
If the Home is on one level (a bungalow or mobile home for example) you should put the firstSmoke Alarm in a corridor or hallway betweenthe sleeping and living areas. Placeit as near to the living area as possible, but make sure you can hear it loudlyenough to wake a personin the bedrooms. (forexample, see figure 3) Single storey Dwelling with Recommended ProtectionSingle Storey Dwelling with Recommended Protection
Ifthe bungalow is very largeand the corridor or hallwayis more than say 15 metres (50 ft) long, one Smoke Alarm will not be sufficient.This is because no matterwhere it is located itwill be more than 7.5 metres from potential fires.
In houses with more than one sleeping area, Smoke Alarms should be placed between each sleeping area and the living area.
Multi Storey Dwellings
If the dwelling has more than one storey it must have an interconnected alarm on each level for minimum protection.
Maximum Protection
For maximum protection you should put individual Smoke Alarms in all the rooms where fire is most likely to break out (apart from the locations to avoid, mentioned below). Ensure that they are all interconnected. The living room is the most likelyplace for a fireto start atnight, followed by thekitchen and then the diningroom. You should also consider putting Smoke Alarms in any bedrooms where fires might occur, forinstance, where there is an electrical appliance such as an electric blanket or heater, or where the occupant is a smoker. You could alsoconsider putting Smoke Alarms in any rooms where the occupant is unable to respond very well to a firestarting in the room, such as an elderly or sick person or a very young child.
Fire Authorities (including the Home Office, UK) recommend that both Optical and Ionisation Smoke Alarms should be fitted for the fastest response to all types of fires. An Optical Alarmshould be located downstairsto detect slow smouldering fires (e.g. from a cigarette burning in a couch or bedding,
overheated PVC wiring etc). An Ionisation Alarm should be located upstairs to detect fast flaming fires (e.g.paper burning ina container or agrease fire in thekitchen) which couldrapidly block the main escape route.
Checking you can hear the Smoke & Heat Alarms
With theAlarm sounding in its intendedlocation, check you are able tohear it in each bedroom withthe door closed, above the soundof the radio. Theradio should beset to a reasonablyloud conversation level. If you can’t hear it over your radio the chances are that it wouldn’t wake a person.
If a Smoke Alarm is too far away for it to wake a person, it is best to interconnect to another Smoke Alarm or Heat Alarm near the bedroom, so when one alarm senses fire, all interconnectedalarms respond (seebelow for further details).
LOCATIONS TO AVOID
Don’t place Smoke Alarms in any of the following areas:
Bathrooms, kitchens, shower rooms, garages or other rooms where the smoke alarm may be triggered by steam, condensation, normal smoke or fumes. Keep at least 6 metres (20 feet) away from sources of smoke.
Don’t place Heat Alarms in any of the following areas:
Bathrooms, shower rooms or other room where the unit may be triggered by steam or condensation.
Don’t place Smoke or Heat Alarms in any of the following areas:
Places where the normal temperature can exceed 40°C (104°F) or be below 4°C (39°F) e.g. attics, furnace rooms etc. directly above ovens or kettles, as the heat/steam could cause nuisance alarms.
Near a decorative object, door, light fitting, window moulding etc., that may prevent smoke or heat from entering the Alarm.
Surfacesthat are normally warmeror colder than therest of the room (for example attic hatches, uninsulated exterior walls etc). Temperature differences might stop smoke or heat from reaching the unit.
Next to or directly above heaters or air conditioning vents, windows, wall vents etc. that can change the direction of airflow.
In veryhigh or awkward areas (eg. over stairwells) where it may be difficult to reach the alarm (for testing, hushing or battery replacement).
• Locate away fromvery dusty or dirtyareas as dust build-up inthe chamber can impair performance.It can also blockthe insect screen mesh and prevent smoke from entering the
smoke detector chamber.
Locate the unit at least 1 metre (3 feet) from dimmer controlled lights and wiring - some dimmers can cause interference.
Locate unitat least 1.5m (5 feet) androute wiring at least 1m (3 feet) away from fluorescent light fittings as electrical “noise” and/or flickering may affect the unit.
Donot locate in insect infestedareas. Small insects getting into the smoke detector chamber can cause intermittent alarms. Insects and contaminationon the HeatAlarm sensor can increase its response time.
POSITIONING SMOKE/HEATALARMS
Thelocations must complywith applicable building regulations.
Hotsmoke rises and spreadsout, so acentral ceiling position is the preferred location. The air is “dead” and does not move in corners, therefore Smoke & Heat Alarms must be mounted away from corners. Place the unit at least 300mm (12 inches) from any light fitting or decorative object which might obstruct smoke / heat entering the Alarm. Keepat least 300mm (12”) away from walls. See figure 4. (Smoke Alarms should be located directly on the ceiling or up to 570mm below it. Heat Alarms should belocated directly on the ceiling or up to 90mm below it).
Wall mounting is not recommended for these Alarms.
Sloping Ceiling
In areas with sloping or peaked ceilings install your Smoke/Heat Alarm 90mm (3 feet) from the highest point measured horizontally(see figure 5), because “dead air” at the apex may prevent smokefrom reaching the unit.
INTERCONNECTING SMOKE/HEAT
ALARMS
When a fire is sensed the alarm must be given throughout the house. Up to twenty (20) Smoke Alarms (models EI 180, 181, 185, 186 only) and Heat Alarms (model EI 183, 184 only) can be interconnected so that when one senses fire all alarm. Caution: Do not interconnect to any other type of alarm. The unitinitiating the alarm can be identifiedby the red LED on the cover flashing every second. Figure 6 shows the interconnect wiring.
Note:It is only necessaryto wire one relayto the control panel. If any alarm senses fire this relay will change state due to the signal on the interconnect line.
These Alarms should be interconnected only within the confines ofa single family living unit. If theyare interconnected between different units there may be excessive nuisance alarms.Everybody may not beaware that they arebeing tested or thatit is a nuisance alarm caused bycooking etc. When one unit alarms all relays will switch.
Systems using more than 3 or 4 alarms must be verycarefully
planned to ensure nuisance alarms are not excessive, e.g. from cooking or weekly testing.
Smoke Alarm Locator Switch (EI 159) should be incorporated into the system and be readily accessible to all occupants so that the source of an alarm can be quickly identified. (see Accessory section).
All Alarms must be cleaned and maintained regularly.
A competent person must be on call to quickly remove any faulty alarms (i.e. units with red light flashing), which are causing all alarms to sound.
INSTALLING SMOKE/HEAT ALARMS
The Alarm is designed to be permanently mounted , using it’s own built-in terminal blocks to connect it to the panel. The mounting plate can be screwed directly to the ceiling after connecting the wires.
IMPORTANT PRECAUTION:Do not install the actual alarm itself in new or renovated buildings until all work is completed(including floor coverings) andthe building has been fully cleaned. The wiring can be installed when appropriate. (Excessive dust and debris from building work can contaminate the smoke chamber or heat sensor and cause problems, it will also invalidate the guarantee). If it must be installed, cover it completely, particularly around the edges, with a dust cover (eg. with the elasticated cover supplied or a plastic bag), until all cleaning is finished.
Warning: Wiring should only be installed by an Electrician in
accordance with current IEE wiring regulations for electrical installation. The installation must also be in accordance with thecontrol panel instructionsand the instructions inthis leaflet.
Warning: The mains circuit used to power the control panel must be a 24 hour voltage circuit and be wired on a separate circuit (one with no other lights or applilances) to ensure maximum reliability of the supply.
Warning: The Alarms must be connected to a panel that supplies a permanent voltage that cannot be switched off.
Warning: For safety reasons the voltage supply from the control panel must not be greater than 30V (peak or d.c.) and mustbe either independentof the supply mainsor isolated from it by double or reinforced insulations.
Warning:If the control panelis not provided withan ALL-POLE MAINSSWITCH (with a contactspecification of at least3mm in each pole), then the electrical installation of the building shall incorporate an ALL-POLE MAINS SWITCH, (with a contact separation of at least 3mm in each pole).
Installation
Select a location complying with the above advice.
1. Remove the mountingplate from the Smoke Heat Alarm by releasing the tamper-proof catch with a small screwdriver as shown in figure 1a and sliding the alarm from the plate.
2.Lift the foam flap coveringthe circuit on themounting plate. If necessary movethe jumpers on S1 and/or S2 (seefigure 7) by carefully lifting them and placing them over the required pins.
3. If surface wiring the unit remove the required breakaways. Low voltage signal cable is satisfactory (e.g. wire 0.22mm
2
) provided theresistance between the units andthe panel is less than 20 ohms.
All wiring must comply with local codes. Connect the wires to the terminals as shown in the wiring diagram (figure 6). The gasket flap can be tucked behind the terminals while this is being done. Place gasket flap back over circuit board and terminals.
4.Carefully align the mounting plateand screw into place. With recessed wiring,ensure the rear gasket seals around theedge
ofthe hole in theceiling. This isto prevent air draughtsaffecting the smoke / heat entering the alarm. If the orifice is toolarge it should be sealed with silicone rubber or equivalent.
Check the battery is connected in the back of the alarm ( EI 181, 184, 186 only).
Carefully line up the unit on the base and slide on.
Press the test/hush button for 10 seconds. The horn should sound (EI 181, 184, 186 only).
7. Connectthe panel power to thealarm circuit. The green light on the mounting plate should turn on.
Check the operation of the Alarm as outlined in the next section.
CHECKING AND MOUNTING YOUR
ALARMS
INSPECTION & TESTING PROCEDURE
After installation, after re-occupation following a holiday, and weekly, check all your Alarms as follows:
Check thegreen light is illuminated onthe mounting plate. This shows the panel is supplying power.
Press the test button for up to 10 seconds to ensure the sensor chamber, electronics and sounder are working. A red light on the cover will flash while horn is sounding. The relay contacts should change over with the EI185, EI186 relay contacts when the horn sounds with the EI180, EI181, EI183, EI184, it contacts within 6 seconds after the horn sounds. The alarm will stop when the button is released. Pressing the test button simulates the effect of smoke or heat during a real fire and is the best way to ensure the Alarm is operating correctly.
WARNING: DO NOT TEST WITH FLAME.
This can set fire to the Alarm and damage the house.
Wedo not recommend testingwith smoke orheat as theresults can be misleading unless special apparatus is used.
Check for any sign of contamination such as cobwebs or dust and clean the alarm as described below if necessary.
Interconnected alarms
Test the first unit by pressing the button. All the detectors should alarm within about 5seconds of the first horn sounding and the red light on the first unit only will flash once a second. The relay contacts should change over about 6 seconds after the horns sound. Check all the other units similarly. (Note: Ionisation and Heat alarms signal to other interconnected alarms, about 4 seconds after their own horn sounds. Optical alarms signal within about a second).
2
3
4
5
6
7
8
9
11
10
MOUNTINGPLATE
SEALING GASKET
CONTINUOUS GREENPANEL
POWERON
LIGHT
TAMPERPROOF
CATCH
Figure1a
PUSHSCREWDRIVER
STRAIGHTIN
TORELEASE CATCH
SLIDE
OFF
(PUSHCOVER BACK)
UNITWILL NOT FIT ONTHE MOUNTING
PLATEWITHOUT A BATTERYINSTALLED (EI181/184/186ONLY)
BASE
4WAY PLUG
ENGAGESSOCKET ONMOUNTING PLATE TOCONNECT TO PANEL
BATTERYAND
9
V
olt
Battery
BATTERY
SNAPS
(EI181/184/186
ONLY)
Figure1b
Recommended Protection
Minimum protection
Maximum protection
Smoke Alarms located on:-
- Interconnect all Alarms
Smoke Alarms located as above plus:-
Heat Alarms located in Kitchens, garages, boiler rooms etc. Within 5.3m (17ft) of potential fire sources.
every 7.5 metres (25ft) of hallways and escape routes
each storey
Within 3m (10th) of all bedroom doors.
All rooms (except bathrooms, shower rooms & kitchens)
SeeFigures2&3
Multi Storey Dwelling with Recommended Protection
Fitboth Ionisation & Opticaltype alarms.
Bestfor fast flaming fires.
Bestfor smouldering fires.
Ionisation-
Optical-
Figures2
BEDROOM
BEDROOM BEDROOM
KITCHEN
DINING
Figure 3
IDEALFOR CENTRE
OFCEILING
NEVERWITHIN 300mmOF ANY WALL/ CORNER
DEADAIR
SPACES
900mm
(3ft)
Figure 4 Figure 5
COMPATIBLE
10.5- 30 VOLT PANEL
COMPATIBLE
10.5- 30 VOLT PANEL
INTERCONNECT
INTERCONNECT
EOL- ND F INEDEVICE, SPECIFIED BY PANELEOL
Figure6a Circuit for Normally Open Relay Contacts
Fi
g
ure6b Circuit for Normally Closed Relay Contacts
+V
+V
0V
0V
NORMALLY
OPEN
CIRCUIT
NORMALLY
CLOSED CIRCUIT
COMMON
COMMON
NO
NO
*
*
EOL DEVICE
NC
NC
COMMON
COMMON
UNIT
1
UNIT1
UNIT
2
UNIT2
NO
NO
NC
NC
+
+
IC
IC
-
-
+
+
IC
IC
-
-
+
NO
IC
NC
PC
S1
-
COMMON
MAIN
BREAKAWAYS
FOR SURFACE MOUNTING
BREAKAWAYS
FOR STRAIGHT THROUGH
WIRING
S1S2POSITIONC
POSITIONNR
RELAYON CONTINUOUSLY WHEN IN ALARM (AS SUPPLIED)
NORESISTANCE IN SERIES WITH RELAY CONTACTS(AS SUPPLIED)
RELAYPULSED FOR 5 SECONDS WHEN UNIT ALARMS
RESISTORSCONNECTED TO CONTACTS AS SHOWN BELOW
POSITIONP
POSITIONR
SEALING GASKET
FLAPFOLDED
BACK
Figure 7a
NRS2R
NRS2R
PC
S1
68K
22K
R
NR
C
NO
NC
Figure 7b
Pages 2 to 11
B14090 Rev-1
12/03/01
Checking Battery Back-up
TheAlarm automatically monitors thebattery every 40seconds toensure that it is satisfactory.If it is depleted itwill give a short beep every 40 seconds (models EI 181, EI 184 and EI 186 only).
Before replacing the battery, check that the beeps arenot due to one of the following:
(i) Battery snaps not connected properly.
(ii) On the OpticalSmoke Alarms only (EI 186/185) if the unit beeps and the red light does not flash at the same time it indicates a problem with the smoke chamber – see Cleaning the Smoke Alarm section below:
If the beepshave continued for over 20 minutes (and the other causes of beeps have been ruled out – see below) the battery must be replaced.
(iii) Switch off the panel voltagesupply and remove the unit as shownin fig 1a. CAUTION:Do not attemptto remove the Alarm withoutfirst releasing the tamperclip. Remove depletedbattery and replacewith one of the specified 9Valkaline batteries. The alarm cannot be replaced on the mounting plate unless a battery is installed. After replacing the battery, slide on to the mounting plateand then press the test button and ensure horn sounds loudlybefore you turn on the panel supply. Note: Only use the specified Alkaline batteries shown on the base label (Duracell MN1604, Eveready 522 or Energizer 6LR61). We recommend that the “use by date” on the battery should still have at least 2 years to go. Older batteries will give beeps prematurely.
We recommend that the battery is replaced each year for optimum performance.
Please note:The ionisation and heat alarms (EI180, 181,183 and 184)give two short beeps about a secondapart at the end of the hushperiod (i.e. about 10 minutes after test/hush button has been pressed). These two beeps should not be confused with low battery beeps.
Manual Testing
We recommend that the functioning of the battery back-up is checked after installation and then at least yearly as follows:-
Turn off (or disconnect) the power at the panel (green light on mounting plate should beoff) press the test button and ensure thehorn sounds loudly for10 seconds. (This checksthe battery back-up models EI 181, EI 184 and EI 186 only).
Note: A good battery can supply the unit for over a year in standby (or 5 hours in alarm) without panel power.
Instandby, with panel power,the battery canoperate for up to4 years before the low battery beeps start – these will normally
last for over 30 days before the battery is fully depleted.
CLEANING YOUR ALARM
Clean yourAlarm regularly, particularly in dusty areas.Use the narrow nozzle attachment of your vacuum cleaner to remove dust, insects and cobwebs from the sides and cover slots wherethe smoke orheat enters. To cleanthe cover, wipewith a damp cloth. Dry cover thoroughly with a lint free cloth.
WARNING: Do not paint your Alarm.
Other than the cleaning described above, no other customer servicing of this product is required. Repairs, when needed, must be performed by the manufacturer.
All Alarms are prone to dust and insect ingress which can cause false alarms or failure to alarm.
The latest design, materials and manufacturing techniques have been used in the construction of our Alarms to minimize the effects of contamination. However it is impossible to completely eliminate the effect of dust and insect contamination, and therefore, to prolong the life of the Alarm you must ensure that it is kept clean so that excess dust does not buildup. Any insects or cobwebs inthe vicinity of the Alarm should be promptly removed.
In certain circumstances even with regular cleaning, contamination can build up in the smoke sensing chamber causing the alarm to sound or fail. If this happens the alarm must be returned to us for servicing or replacement. Contamination is beyond our control, it is totally unpredictable and is considered normal wear and tear. For this reason, contamination isnot covered by the guarantee and a charge is made for servicing suchunits.
If you experience persistent false alarms, in particular locations, due to contamination of the smoke chamber you could consider replacing Optical Smoke Alarms (EI 186/185) with Ionisation Smoke Alarms (EI 181/180). Ionisation type alarms are less susceptible to dust than Optical type alarms.
NUISANCE ALARMS
If there is a nuisance alarm simply press the test/hush button on the Alarm to silence the unit for 10 minutes.
If, when the alarm goes off, there is no sign of smoke, heat or noise to indicate that there is a fire, you should getyour family into a safe place, before you start investigating.
Check the house carefully in casethere is a small fire smould­ering somewhere.
Check whether there is some source of smoke or fumes, for example cookingfumes being drawn past the Smoke Alarmby an extractor.
Ifthere are frequent nuisance/false alarmsit may be necessary tore-locate the device away fromthe source of the fumes.If for some reason the alarm continues to sound without smoke or heat being present (due to insect infestation or contamination build-up for example) the units can be silenced by disconnecting the mains power and removing the unit (see figure 1). If cleaning the Alarm does not correct the problem it can be returned to the manufacturer for repair or replacement (see Getting Your Alarm Serviced below).
Hush Feature
All the Smoke / Heat Alarms have a combined Test/Hush Button to help you control nuisance false alarms.
1. Tocancel a false alarm, press the Test/Hush Button located on the cover. The Alarm will automatically switch to a reduced sensitivity condition (very large levels of smoke from a nearby fire willoverride the Hush on thesmoke alarms). This condition allows unwanted alarms to be silenced for a period of approximately 10 minutes.
The unit will flash the red light every 10 seconds (instead of the normal 40 seconds) to indicate the sensitivity is reduced. At the end of the hush period the Ionisation SmokeAlarm (EI 181/180) and theHeat Alarms (EI 184/183) will give two short beeps. The Optical Smoke Alarm (EI 185/186) does not give these two beeps.
On interconnected Alarms, pressing the Test/Hush Button on the one sensing smoke (i.e. the one with the red light flashing every second)will silence all alarms. Pressingthe Hush Button on any other Alarm will not cancel the alarm.
2. The unit will reset to normal sensitivity at the end of the silenced period. If additional silenced time is required, simply push the Test/Hush Button again.
IMPORTANT SAFE GUARDS
When using household protective devices, basic safety precautionsshould always be followed,including those listed below:
Please read all instructions.
Rehearse emergency escape plans so everyone at home knows what to do in case the alarm sounds. Further information can be obtained from the Home Office Publication entitled“Smoke Detectors in the Home” (FB2) or from your local fire prevention officer.
NOTE: Constant exposure to high or freezing temperatures or high humidity may reduce the life of the battery.
Tomaintain sensitivity to smoke,do not paint orcover smoke /heat alarms inany manner; do not permit any accumulation of cobwebs, dust or grease.
• If a unit has been damaged in any way or does not function properly,do notattempt a repair. Return Alarm (see- Getting your Alarm Serviced).
This appliance is only intended for premises having a residential type environment.
Smoke / HeatAlarms are not a substitute for insurance. The supplier or manufacturer is not your insurer.
The chamber inside the Ionisation Smoke Alarms (EI 181/180)contains a small amountof radioactive material. Do not tamper with the chamber. You may safely install and clean the Smoke Alarm following this leaflet’s instructions.
In the United Kingdom Ionisation Smoke Alarms can be disposed of in normal household refuse, but due to the tiny amountof radioactive material contained inthe unit, no more than one alarm per dustbin.
In theRepublic of Ireland Ionisation smokealarms should be returnedfor disposal to the nearestaddress at the endof this leaflet.
Do not dispose of your Alarm in a fire.
Use the Smoke / Heat Alarm Test Buttons to familiarize your family with the Alarm sound and to practice fire drills regularly with all family members. Draw up a floor plan that will show each member at least 2 escape routes from each room in the house. Children tendto hide when they don’t know what to do. Teach children how to escape, open windows, and use roll up fire laddersand stools without adult help.Make sure they know what to do if the alarm goes off - see next page.
PLANNING YOUR ESCAPE FOR WHEN THE
ALARM GOES OFF
1. Check room doors for heat or
smoke. Do not open a hot door. Use an alternate escape route. Close doors behind you as you leave.
2.If smoke is heavy, crawl out,staying
close to floor. Take short breaths, if possible, through a wet cloth or hold your breath. More people die from smoke inhalation than from flames.
3. Get out as fast as you can. Do not
stop for packing. Have a prearranged meeting place outside for all family members. Check everybody is there.
4. Call the Fire Brigade from a neighb our’s house. Remember to give your name and address.
5. NEVER re-enter a burning house.
LIMITATIONS OF SMOKE HEAT ALARMS
Smoke/Heat Alarms have significantly helped to reduce the number of fire fatalities in countries where they are widely installed.
However independentauthorities have stated that theymay be ineffective in some circumstances. There are a number of reasons for this:
The Alarms will not work if the mains power is off and the back-up battery is depleted. On the EI181/184/186 alarms the batteries should be replaced annually and whenthe unit gives low battery beeps.
Smoke/Heat Alarms will not detect fire if sufficient smoke/ heat does not reach the alarm. Smoke/Heat may be prevented from reaching theAlarm if the fire is too far away, for example, if the fire is on another floor, behind a closed door, in a chimney, in a wall cavity, or if the prevailing air draughts carrythe smoke/heat away. Installing Smoke/Heat Alarms on both sides of closed doors and installing more than oneSmoke/Heat Alarm as recommended in this leaflet very significantly improves the probability of early detection.
The Alarm may not be heard.
ASmoke / Heat Alarmmay not wake aperson who hastaken drugs or alcohol.
Smoke/ Heat Alarms maynot detect every typeof fire to give sufficientearly warning. They areparticularly ineffective with: fires caused by smoking in bed, escaping gas, violent explosions, poor storage of flammable rags and/or liquids, (for example petrol, paint, spirits etc), overloaded electrical circuits, arson and children playing with matches.
Fire Authorities(including the Home Office, UK) recommend that both Optical and Ionisation Smoke Alarms should be fitted for the fastest response to all types of fires.
Smoke / Heat Alarms don’t last indefinitely. For example if there is a build up of contamination, performance will be impaired.
The manufacturer recommends replacement of the Smoke/ Heat Alarms after 10 years as a precaution.
ACCESSORY
Smoke Alarm Locator EI 159:
The Smoke Alarm locator is recommended for systems with three or more Smoke / Heat Alarms as it helps quickly identify the unit in alarm and reduces the impact of nuisance alarms.
Pressing the Smoke Alarm Locator button will silence all interconnected alarms for 10 minutes, except those sensing fire. It is easily installed between the interconnect and 0 volt terminals.
GETTING YOUR ALARM SERVICED
If your Alarm fails to work after you have carefully read all the instructions, checked theunit has been installed correctly, and is receiving panel power contact Customer Assistance at the addressgiven at the endof this leaflet. Ifit needs to bereturned for repair or replacement put it in a padded box and send it to “Customer Assistanceand Information” at the nearest address given on the Alarm or in this leaflet. Do not snap on the mounting plate as this connects the battery and the unit may beep or alarm in the post. State the nature of the fault
, where
the Alarm was purchased and the date of purchase.
FIVE YEAR PRODUCT GUARANTEE
EIElectronics Ltd. guarantees this Alarm(excluding the batteryin the EI181/184/186 models)for five years from date of purchase against any defect s that are due to faulty materials or workmanship. This guarantee only applies to normal conditions of use and service, and does not include damage resulting from accident, neglect, misuse, unauthorised dismantling, or contamination howsoever caused. This guarantee excludes incidental and consequential damage. This guarantee does not cover costs associated with the removal and/or installation of alarms. If this Alarm shouldbecome defective within the guarantee period, it must be returned to EI Electronics, with proof of purchase, carefully packaged, with the problem clearly stated.(see “Getting Your Alarm Serviced”) We shall at our discretion repair or replace the faulty unit.
Donot interfere with theAlarm or attempt totamper with it. This will invalidate the guarantee, but more importantly may expose the user to shock or fire hazards. This guarantee is in addition to your statutory rights as a consumer.
Aico Ltd., Mile End Business Park,
Maesbury Rd, Oswestry, Shropshire SY10 8NN, U.K.
Telephone : 01691 657466
EI Electronics. Shannon, Co Clare, Ireland.
www.eielectronics
www.asis.com
SPECIFICATIONS
Supply Voltage: 10.5 to 30.0 Volts (DC Only)
StandbyCurrent: 7.5mA (max) @ 12 V;10.0mA (max) @24 V.
AlarmCurrent: 58.0mA (max)@ 12 V; 60.0mA (max) @24 V.
Relay Contacts: 30 volts/1 amp resistive (normally open and
normally closed supplied). The unit is supplied with the relay operating in continuous mode (i.e. relay is on while unit is sensing smoke). To select pulse mode (relay turns on for 5 seconds only at start of smoke sensing), set jumper S1 to "P" position.
The unit is also supplied with the relay in conventional, i.e. no contact resistance, mode. If required, 22K ohm can be connected in series with the C terminal and relay contact and 68K ohmbetween C and NC screwterminals by setting jumper S2 to "R" position.
Wiring: Wiring may be surface or recessed .
Cable: 4 core max resistance 20 ohms, provided specified
supply voltage is maintained at unit.
Test Button: Simulates the effect of fire and checks electronics and horn.
Power-on Indicators:
- Continuous green light on mounting plate for panel power
- Red LED flashes every 40 seconds.
Alarm output: Piezo horn 85dB (A) @ 3m
Standby Temp: 0
o
C-40oC
Humidity:10 - 90 %Relative HumidityInterconnect: Up to 20 units in total (EI180, EI 181, EI 183, EI 184, EI185, EI 186 units only)can be interconnected so that when one sensesfire all alarm. Relays switch on all units.
Alarm Indicator: Red LED flashes rapidly only on units sensing fire.
Battery Back-Up: 9 Volt Alkaline Primary Battery will power the unit in standby for over 1 year without external power. Will power the unit for over 2 hours in alarm. Batteryis monitored for open circuit, short circuit and high impedance. The unit will beep once a minute when it is starting to be depleted.
Ionisation EI 181
Sensor: Dual Ionisation Chamber
Sensitivity: Complies with BS5446-1: 2000
Source: 0.9 microcurie of Am 241
Combined Test/HushButton: Tests and then hushes unit for
10 minutes. Automatically resets. RedLED flashes every 10 seconds whilein hush. At the end of the hush period unitgives a double beep.
Airspeed: No false alarms up to 10 m/s (22mph)
Insect Screen: Prevents insects or debris entering the
chamber
Dimensions: 145mm (d) X 55mm (h)
Weight: 380 grams
Ionisation EI 180
As EI 181 but without battery back-up
Optical EI 186
Sensor: Detects light scattered by smoke Sensitivity: Complies with BS5446: Part 1: 2000
AmbientLight: Chamber design and electroniccompensation
overcomes problems with stray light
Combined Test/HushButton: Tests and then hushes unit for 10 minutes. Automatically resets. Red LED flashes every 10 seconds while in hush.
Airspeed: No effect Insect Screen: Prevents insects and debris entering the
chamber
Automatic Self Test: Chamber is tested every 40 seconds and unit beeps if it is degraded (without red light flashing at same time)
Dimensions: 145mm (d) x 60mm (h)
Weight: 380 grams
Optical EI 185
As EI 186 but without battery back-up
Heat EI 184
Sensor: Fast response Thermistor
Sensitivity:58 +/- 4
o
C(Response grade 1 as definedin EN54:
Part5)
Combined Test/Hush Button: Tests and then hushes unit for 10 minutes. Automatically resets. Red LED flashes every 10 seconds while inhush. At the end of the hush period unit gives a double beep.
Airspeed: No effect
Contamination: Much less affected by insects and
contamination than Smoke Alarms
Dimensions: 145mm (d) x 65mm (h)
Weight: 380 grams
Heat EI 183
As EI 184 but without battery back-up
TROUBLESHOOTING
1. FREQUENT NUISANCE ALARMS OCCUR:
(1) Close kitchen / bathroom door when in use.
(2)Ensure that thealarm is sited atleast 6m awayfrom sources of fumes.
(3) Contamination from insects, paint or paint fumes may have occurred. Clean the alarm as described in this booklet.
(4) If the problem persists, resiting of the unit should be considered. Alternatively, replace the unit with an Optical unit (EI186/185), assumingthat the problem is with anIonisation type alarm (EI181/180).
2. ALARM SOUNDS FOR NO APPARENT REASON:
(1) Identify the alarm source. On interconnected units, the red light on the cover will flash rapidly only on the unit which is the source of the alarm.
(2) Check for fumes, steam etc. from the kitchen or bathroom. Paint and other fumes can cause nuisance alarms.
(3) Press the test/hush button to silence the Smoke/Heat Alarm for 10 minutes.
(4) If alarm does not stop, remove the unit (see figure 1). (Only remove alarm with red light flashing, the others are probably satisfactory).
3. LOW BATTERY BEEPS:
(On EI 181/184/186 only)
If the battery is correctly connected and the unit has beeped for over 20 minutes the battery is probably depleted. Obtain a new battery, remove thealarm and replace the depleted battery. (see figure 1).
OTHER BEEPS:
(1) If the panel is providing power and replacing battery or cleaning unit has not stopped beeps, a fault may exist. Replace the unit (see figure 1).
(2) The Ionisation/Heat units (EI 181/180/184/183) give two beeps 10 minutes after the test/hush button is pressed.
(3) If the Optical units (EI 186/185) beep without the red light flashing at the same time, the chamber is defective. Clean the chamber.
4. INTERCONNECTED ALARMS DO NOT ALL SOUND AND THE RELAY DOES NOT SWITCH:
(1) Hold test button for 10 seconds after first alarm has sounded to ensure signal is transmitted to all units. Relay should switch.
(2)Check that thegreen power light onthe mounting plateis on.
(3) Check panel and wiring.
12
13
14
15
16
17
18
19
1
20
Pages1&14to21
B14090 Rev-1
12/03/01
IONISATION
EI181
EI180
EI184
EI183
EI186
EI185
ALKALINE9 VOLT BATTERYBACK-UP
NOBATTERY ACKUP
HEAT OPTICAL
LOW VOLTAGEPANEL
SMOKE & HEATALARM
Professional
®
Contains vitalinformation on unit operation and installation. Read and retaincarefully. If you are just installing this unit, this leaflet be given to the householder.
MUST
LEAVEWITH USER
READ THIS FIRST
INSTRUCTIONS
IDEALLY INSTALL IN THE CENTRE OF CEILING AT LEAST 300mm (1ft) FROM LIGHT FITTINGS. KEEP IONISATION ALARMS AWAY FROM KITCHENS TO PREVENT NUISANCE
REMOVE UNIT FROM MOUNTING PLATE BY RELEASING CATCHASSHOWN IN FIG1a.
EI181/184/186 ONLY: CHECK BATTERY IS CONNECTED TO SNAP(SEE FIG1b). BATTERYWILLNOT POWER THEUNIT UNTILITIS SNAPPED ONTO THEMOUNTING PLATE.
ENSURE THE PANEL IS CORRECTLY CONNECTED TO ALL TERMINALS OTHERWISE UNITS WILL NOT OPERATE CORRECTLY.CHECK GREEN PANELPOWER LIGHT IS LIT ON MOUNTINGPLATE.
DO NOT FIT ACTUAL ALARM UNTIL ALL BUILDING WORK IS COMPLETED TO AVOIDCONTAMINATION. AFTER CHECKING OPERATION, COVER SMOKE ALARM WITH DUST COVER UNTILREQUIREDFOR USE.
ALARMS.INTERCONNECT ALL ALARMS.
Continued Page 2
4
4
4
4
5
© EIElectronics 2001 P/NB14090 Rev1
Loading...