Instruction Leaflet
Smoke Alarm Systems for the Deaf & Hard of Hearing
- with Strobe & Vibrator
Ei 169/160 BASIC SYSTEM (requires a Smoke Alarm Ei161 or Ei166)
Ei 170/160 with MAINS IONISATION SMOKE ALARM Ei 161
Ei 171/160 with MAINS OPTICAL SMOKE ALARM Ei 166
SMOKE ALARM
Ei 161 or Ei 166
CONTROL PANEL Ei 173
(With rechargeable battery
STROBE
for one week standby)
Introduction
This leaflet describes the installation of the Ei 169/160, Ei
170/160 and Ei 171/160 Systems.
Important: Read all instructions before installing. This leaf-
let must be left with the end user after installation.
N.B. If the systemisnotbeing used for some tmethe Control
Panel power switch must be in the off position. This will prevent the battery from being totally depleted and possibly dam
aged.
Do not
turn on until it is fully wired.
The systems consist of:-
Ei 169 / 160
Ei 173 Control Panel (with built in strobe)
Ei 174 Vibrator Pad
Ei 172/160 Pattress for Smoke / Heat Alarm Interface (this
requires an Easi-fit Alarm to operate i.e. Ei 140, 141, 146,
161 or 166)
Ei 170 / 160
Ei 169/160 with a Mains Ionisation Smoke Alarm Ei 161
Ei 171 / 160
Ei 169/160 with a Mains Optical Smoke Alarm Ei 166
1. Location & Installation
The Control Panel should normally be fixed such that the in
ternal strobe light can be seen from the bed and the vibration
pad can be placed under the mattress or pillow. It has to be
powered from the mains (230 VAC) so a suitable power point
or junction box must be available to which it can be perma
nently connected. The Smoke Alarm must be located as de
scribed in the Smoke Alarm instructions supplied. Cable (10
m) is supplied to connect between the Control Panel and the
Ei 172/160 Pattress for the smoke alarm.
1
PATTRESS Ei 172/160
T
N
I
A
P
T
O
N
O
D
TEST
PUSH
U
N
C
L
I
P
&
S
L
I
D
E
& HUSH
VIBRATION PAD Ei 174
This can be extended up to 50 m (20 ohms max.) with suitable low voltage cable if required. The Smoke Alarm supplied
with the system may be interconnected with other Ei mains
powered smoke/heat alarms up to a maximum of 12 alarms
(see below for details) in total. Many dwellings require more
than one smoke alarm for minimum protection. See the smoke
alarm instruction leaflet for detailed advice on, interconnection, maintenance etc.
-
Warning: This mains operated system should be installed
and interconnnected by a qualified electrician in accordance
with the Regulations for Electrical Installations published by
the Institute of Electrical Engineers (UK). Failure to install this
system correctly may expose the userto shock or fire hazards.
Mains (230VAC) rated cable mustbe used for the interconnect
wire along with the mains itself.
Control Panel
The Control Panel should be permanently fixed to the wall
using the screws and plastic plugs enclosed. The screws
should be spaced 114 mm (4.5 in) vertically apart. The top
screw should be 27 mm (1.1 in) below the top surface of the
control panel when installed. The screws (large heads) should
be screwed into the wall leaving a gap of approximately 4 mm
(0.15 in) under the head. Fit the keyhole slots on the back of
the control panel over the screw heads and slide the panel
down vertically into position.
The mains adaptor can be plugged into a socket. The socket
must not be used for any other equipment and it must always
be switched on.
It is preferable to permanentlywire theunit intoa mains junc
tion box. In this case remove the plug and wire as follows.
-
-
Warning: First remove the powerto the circuit at the distribu
tion board. If you are in any doubt about how to do this, get
help from a qualified electrician.
Connecting to mains junction box.
The mains lead wires are colour coded as follows:
2
-
-
brown: live
blue: neutral
The wire which is coloured blue must be connected to the
terminal/wire which is marked with the letter N or coloured
black.
The wire which is coloured brown must be connected to the
terminal/wire which is marked withthe letter L or coloured red.
The apparatus is not to be earthed, so no connection is to be
made to terminals or wires marked with the letter E, the sym
bol or coloured green or green and yellow.
Bring the low voltage wiring from the control panel to where
the smoke alarm is to be located. Route all wires neatly and
securely along the walls and ceilings.
Note: Turning off the power switch on the Control Panel
does not switch off the apparatus from the supply mains. The
switch removes the AC and battery power from the Control
Panel, but the mains transformer remains connected to the
supply mains.
Vibration Pad
Plug the vibration pad into its locking socket on the control
panel. Place the vibration pad under the pillow or mattress. It
is important that the person in the bed can feel the vibration check it is sufficient to wake a person by lying on the bed and
pressing the test button on the control panel - see also “Test
ing your system”. Some mattresses may not transmit suffi
cient vibration, and in these cases it should be fitted under the
pillow. Note: During testing, or in an actual alarm situation,
the pad pulses on and off for greater effect on sleepers.
Mains Smoke Alarm Interface Pattress Ei 172/160
The pattress is used tomount the smoke alarm inits location,
to connect it to the mains and interconnect wires, and to connect it to the wires from the Ei 173 control panel.
tions from the non-isolated mains powered smoke alarms, to the low
voltage control panel wires are through an opto-isolator in the Ei
172/160 for electrical safety).
(The connec-
3. The low voltage wiring from the control panel must not be
run in the same conduit as the mains/interconnect wires.
4. Using a sharp knife remove material from the appropriate
knockouts making sure that there is no gap, either where
mated with the ducting/conduit or with the low voltage wires.
There are three knockouts and one on the rear.
5. Screw the pattress to the surface using the two screws
and plastic plugs supplied.
6. Figure 1 shows the connections. Connect the incoming
live, neutral, and interconnect (from other smoke alarms if
-
present) to the pre-wired connector block. The Pattress does
not require an Earth. The three wires for connecting to the
smoke alarm mounting plate arealready wired to the pattress.
Connect the red wire (remove the small piece of insulating
tape first) from the control panel to the terminal marked “R”
and the yellow wire to the terminal marked “Y”. The black and
blue wires from the control panel are not used. They should
both be connected to thespare terminal for extra strain relief.
7. Bring the mounting plate wires out through the hole in the
mounting plate as shown in figure 2. Connect the three wires
to the mounting plate terminals following the wiring colours
specified in figure 2. Note:The white interconnect wire must
be connected to the smoke alarm (even if there is only one
smoke alarm on the system).
SMOKE ALARM MOUNTING PLATE
WIRING FROM PATTRESS Ei172/160
-
-
LICN
LIVE (BROWN)
INTERCONNECT (WHITE)
NEUTRAL (BLUE)
PLATE
FIXING
SCREWS
PATTRESSWIRING
TO EASI-FIT SMOKE ALARM
MOUNTING PLATE
L
- BROWN
IC
- WHITE
N
- BLUE
REMOTE
CONDUIT
INTERCONNECT
TO OTHER SMOKE/HEAT
ALARMS (IF PRESENT)
LIVE
L
IC
N
NEUTRAL
L
IC
N
R
-RED
Y
- YELLOW
SPARE TERMINAL
-
TO CONTROL
PANEL Ei173
Figure 1
1. Choose the mounting position following the siting instruc
tions in the Smoke Alarm leaflet. Remove the power from the
circuit you plan to use.
2. Where the incoming mains and interconnect wires are on
the surface of the ceiling or wall the appropriately sized duct
ing/conduit must be chosen to mate with the unit.
3
Figure 2
8. Replace the wiring cover on the mounting plate. Slide the
Smoke Alarm on to the mountig plate.
Interconnecting Smoke Alarms
A maximum of 12 Ei 140,141,144,145,146,161,164,166
Smoke/Heat Alarms may be interconnected to one Ei 172/160
unit. When one alarm senses fire all interconnected units will
sound and the control panel will turn on the strobe light and vi
bration pad (See Smoke/Heat Alarm instruction leaflet for fur
ther details on
Warning
Alarm. Doing this may damagethe alarms and could result in a
shock or fire damage.
Note 1: An alarm with battery back-up (i.e. Ei
141,144,146,161,164,166) will continue to operate during
mains failure andwill be able to signal the control panel if they
sense fire.
The control panel also has battery back-up, so that it too will
operate during mains failure.
-
-
interconnection wiring).
: Do not connect to any other type of Smoke/Heat
4
-
-