Ei Electronics EI 170, EI 171 User Manual

®
Professional
Instruction Leaflet
EI 170/171 Strobe and Vibration Smoke Alarm System, for the deaf and hard of hearing.
AC SMOKE ALARM EI 151 - IONISATION
(or EI 156 - optical)
CONTROL PANEL
(With rechargeable battery for one week standby)
EI 173
STROBE
Introduction
This leaflet describes the installation of the EI 170 and EI
171 Systems.
Important: Read all instructions before installing. This leaf-
let must be left with the end user after installation.
N.B. If the system is not being used for some time the Con­trol Panel power switch must be in the off position. This will prevent the battery from being totally depleted and possibly damaged.
Do not
turn on until it is fully wired.
The systems consist of:-
EI 170 System EI 171 System
EI 151 Mains Smoke EI 156 Mains Smoke
Alarm (ionisation) Alarm (optical)
EI 173 Control Panel EI 173 Control Panel
(with built-in strobe) (with built-in strobe)
EI 174 Vibration Pad EI 174 Vibration Pad
EI 172 Pattress (for EI 172 Pattress (for
Smoke Alarm interface) Smoke Alarm interface)
PATTRESS EI 172
VIBRATION PAD EI 174
the Institute of Electrical Engineers (UK). Failure to install this system correctly may exposetheuser to shockor fire hazards.
Control Panel
The Control Panel should be permanently fixed to the wall using the screws and plastic plugs enclosed. The screws should be spaced 114 mm (4.5 in) vertically apart. The top screw will be 27 mm (1.1 in) below the top surface of the con­trol panel when installed. The screws (large heads) should be screwed into the wall leaving a gap of approximately 4 mm (0.15 in) under the head. Fit the keyhole slots on the back of the control panel over the screw heads and slide the panel down vertically into position.
The mains adaptor can be plugged into a socket. The socket must not be used for any other equipment and it must always be switched on.
It is preferable to permanentlywire the unitinto a mainsjunc tion box. Wire according to the following instructions.
Warning: First remove the power to the circuit atthe distribu tion board. If you are in any doubt about how to do this, get help from a qualified electrician.
-
-
1. Location & Installation
The Control Panel should normally be fixed such that the in ternal strobe light can be seen from the bed and the vibration pad can be placed under the mattress or pillow. It has to be powered from the mains (230 VAC) so a suitable power point or junction box must be available to which it can be perma nently connected. The Smoke Alarm must be located as de scribed in the Smoke Alarm instructions supplied. Cable (10 m) is supplied to connect between the Control Panel and the
EI 172 Pattress for the smoke alarm. Thiscan be extended up
to 50 m (20 ohms max.) with suitable low voltage cable if re quired. The smoke alarm supplied with the system may be in terconnected with other to a maximum of 12 smoke alarms in total. Many dwellings re quire more than one smoke alarm for minimum protection. See the smoke alarm instruction leaflet for detailed advise on, interconnection, maintenance etc.
Warning: This mains operated system should be installed and interconnnected by a qualified electrician in accordance with the Regulations for Electrical Installations published by
EI mains powered smoke alarms up
Connecting to mains junction box.
The mains lead wires are colour coded as follows:
-
-
-
-
-
-
brown: live blue: neutral
The wire whichis coloured blue must be connected to the ter
minal/wire which ismarked with the letter N or coloured black.
The wire which is coloured brown must be connected to the
terminal/wire which ismarked with the letter L or coloured red.
The apparatus is not to be earthed, so no connection is to be made to terminals or wires marked with the letter E, the sym bol or coloured green or green and yellow.
Bring the low voltage wiring to where the smoke alarm is to be located. Routeall wires neatly and securely along the walls and ceilings.
Note: Turning off the power switch on the Control Panel does not switch off the apparatus from the supply mains. The switch removes the AC and battery power from the Control
1
-
-
Panel, but the mains transformer remains connected to the supply mains.
Vibration Pad
Plug the vibration pad into its locking socket on the control panel. Place the vibration pad under the pillow or mattress. It is important that the person in the bed can feel the vibration ­check it is sufficient to wake a person by lying on the bed and pressing the test button on the control panel - see also “Test ing your system”. Some mattresses may not transmit suffi cient vibration, and in these cases it should be fitted under the pillow. Note: During testing, or in an actual alarm situation, the pad pulses on and off for greater effect on sleepers.
Mains Smoke Alarm Interface Pattress EI 172
The pattress is used to mount the smoke alarm in its location, to connect it to the mains and interconnect wires, and to con nect it to thewires fromthe tions from the non-isolated mains powered smoke alarms, to the low voltage control panel wires are through an opto­isolator in the
EI 172 for electrical safety).
Figure 1
MOUNTING SCREW
HOLES (4)
CONDUIT
LIVE
INTERCONNECT TO OTHER SMOKE ALARMS (IF PRESENT
NEUTRAL
PLUG IN TO SMOKE ALARM
EI 173control panel.(The connec
EARTH (IF PRESENT)
L IC
LICNE
SLEEVE
N
R (RED) Y (YELLOW) SPARE TERMINAL
TO CONTROL PANEL Ei 173
Figure 2
CONDUIT
-
-
SMOKE ALARM CONNECTOR
PLATE FIXING SCREWS
LATCH RECESS
TO CONTROL PANEL Ei 173
-
-
8. Push theplug on to the pins in the rear of the Smoke Alarm
and slide on to the mounting plate.
Interconnecting Smoke Alarms
A maximum of 12 EI 150/ 151/ 153/ 154/ 155/ 156 Smoke/Heat Alarms may be interconnected to one unit. When one alarm senses fire all interconnected units will sound and the control panel will turn on the strobe light and vi bration pad (See Smoke Alarm instruction leaflet for further details on
Warning
interconnection wiring).
: Do not connect to any other type of Smoke Alarm. Doing this maydamage thealarms and could result in a shock or fire damage.
Note 1: An alarm with battery back-up (i.e.
EI 151/154/156)
will continue to operate during mains failure and will be able to signal the control panel if they sense fire.
The control panel also has battery back-up, so that it too will
operate during mains failure.
2. Testing your System
EI 172
-
1. Choose the mounting position following the siting instruc­tions in the Smoke Alarm leaflet. Remove the power from the circuit you plan to use. The HMSO Building Regulations state that self-contained Smoke Alarms should be permanently wired to a separately fused circuit at the distribution board.
2. Where the incoming mains and interconnect wires are on the surface of the ceiling or wall the appropriately sized duct ing/conduit must be chosen to mate with the unit.
3. The low voltage wiring from the control panel must not be run in the same conduit as the mains/interconnect wires.
4. Using a sharp knife remove material from the appropriate knockouts making sure that there is no gap, either where mated with the ducting/conduit or with the low voltage wires. There are five knockouts, four on the sides and one on the rear.
5. Screw the pattress to the surface using the two screws
and plastic plugs supplied.
6. Figure 1 shows the connections. Connect the incoming live, neutral, and interconnect (from other smoke alarms if present) to the pre-wired connector block. If an earth wire is present connect it tothe fourthterminal as shown.The Smoke Alarm connector plug is alreadywired to the pattress. Connect the red wire (remove the small piece of insulating tape first) from the control panel to the terminal marked “R” and the yel low wire to the terminal marked “Y”. The black and blue wires from the control panel are not used. They should both be con nected to the spare terminal for extra strain relief.
7. Bring the connector plug out through the rectangular hole in the mounting plate, line up the latch with its recess and then screw the mounting plate on to the box as shown in figure 2 with the screws provided.
After Installation
1. Turn on the AC mains power to the smoke alarm circuit.
Check the continuous green lightis visible on the smoke alarm cover. The red light behind the test button will flash every 40 seconds.
2. Plug in the control panel mains adaptor (or turn on the AC
-
mains if it is connected to a junction box). Slide the power switch on the side of the unit to the “on” position. Check the continuous green light on the control panel cover is visible.
3. Press the test button on the smoke alarm. The smoke alarm should sound and the red light behind the button will flash every second. After about 4 seconds the control panel will start flashing the strobe light and the vibration pad will turn on. Two people may be needed for this test. Interconnected smoke alarms (where present) should also be testedin similar fashion.
4. Press the control panel test button. Check the vibration pad is on and that the strobe is flashing.
Daily & Weekly Testing
We recommend that you test your system weekly by press ing all the smoke alarm test buttons and checking that the vi bration pad and strobe light are operating. Also check at the same time that the green power lights are visible on both the
­smoke alarm(s) and the control panel.
-
Check daily that the vibration pad is in its correct position by
pressing the test button on the control panel.
Periodic Testing of Rechargeable Battery
The rechargeable battery takes about 20 hours to charge from the control panel when it is first powered up. The panel then maintains it in the fully charged state by continuous trickle charge. In the event of a mains failure the battery will
2
-
-
Loading...
+ 1 hidden pages