Ei Electronics EI161, EI164, EI166, EI141, EI144 Installation Instructions Manual

...
CHECK OPERATION OF ALARM
GREEN MAINS LIGHT IS ON.
TEST BUTTON OPERATES ON ALL ALARMS.
ALL INTERCONNECTED ALARMS OPERATE WHEN EACH TEST BUTTON IS PRESSED FOR 10 SECONDS.
(Ei144/146 ONLY) IF THE UNIT BEEPS EVERY 40 SEC
-
­ABLY DEPLETED. REMOVE UNIT FROM CEILING (SEE FIG 1) AND REPLACE BATTERY. ON THE Ei164/166 UNITS ALLOW CELLS TO CHARGE FOR 2 HOURS (MAINS ON).
DO NOT ATTEMPT TO OPENTHE ALARM AS IT IS PER
­MANENTLY SEALED FOR SAFETY.
IF A NUISANCE ALARM OCCURS PRESS THE TEST/HUSH BUTTON TO SILENCE THE ALARM FOR 10 MINUTES.
SMOKE ALARMS
Sufficient smoke must enter the Smoke Alarm before it will re
­spond. The Smoke Alarm needs to be within 7.5 metres of the fire torespond quickly. It also needsto be in aposition where its alarm can be heard throughout your home, so it can wake the occupants in time for all to escape. A single
Smoke Alarm will
give some protection if it is properly installed, but most homes will requiretwo
or moreto ensure thata reliable early warningis given. Formaximum protectionyou should putindividual Smoke Alarms in all the rooms where fire is most likely to break out, (apart from kitchens etc. see Locations to Avoid).
A Smoke Alarm should be located between the sleeping area and the mostlikely sources of fire (living room orkitchen for ex
­ample), but itshould not be more than 7.5metres from the door to anyroom wherea fire mightstart on theescape route fromthe house.
Important: These Smoke/Heat Alarms are designed for a sin
­gle occupancy in a residential type environment.
A Smoke Alarmshould be sited within 3m ofbedroom doors for improved audibility.
HEAT ALARMS
The HeatAlarm givesa fire warningwhen thetemperature at the unit reaches58°C. Itis ideal forkitchens, garages, boilerhouses and other areas where thereare normally high levels of fumes, smoke or dust i.e. places where Smoke Alarms cannot be in-
stalled without the risk of excessive nuisance alarms.
A HeatAlarm shouldonly be usedin a roomadjoining anescape route, inconjunction withSmoke Alarms onthe escaperoutes.
All the Heat Alarms and Smoke Alarms should be intercon
­nected to ensurethe early warning will be heard,particularly by somebody sleeping.A properly designed earlywarning fire sys
­tem ensures the alarm is given before the escape routes be
­come blocked with smoke. Therefore, there must be Smoke Alarms along the escaperoutes as Heat Alarms would not give sufficient warning. However, a fire in a closed room (e.g. kitchen) adjoining the escape route, can eventually cause the corridor to become smoke-logged due to smoke leaking out from around thedoor before adequate warning can begiven by detectors in the corridor. (Smoke leakingout from a room is of
­ten cool andslow moving so itcan take a long timeto rise to the ceiling, and travel to a detector which could be some distance away). AHeat Alarmin the closedroom will giveearly warningof fire in that room and help overcome this problem.
RECOMMENDED LOCATIONS
Figure 2 illustrates where Smoke Alarms and Heat Alarms should be located in a typicaltwo storey house. Note the spac­ings in “Recommended Protection” which ensure the early de­tection of fire and that warning will be heard.
Locate Heat Alarms in rooms adjoining or on escape routes ­kitchens, garages, boiler housesetc. where Smoke Alarms are unsuitable. Install within 5.3m of potential sources of fire.
Single Storey Dwelling.
If the Home is onone level (a bungalow or mobile home for ex
-
ample) youshould put thefirst Smoke Alarmin a corridoror hall
­way between the sleeping and living areas. Place it as near to the living areaas possible, but make sureyou can hear it loudly enough towake aperson in thebedrooms. (for example,see fig
­ure 3)
If the bungalowis very large and the corridoror hallway is more than say15 metres long,one Smoke Alarm willnot be sufficient. This isbecause no matter where itis located it willbe more than
7.5 metres from potential fires.
In houses with more than one sleeping area, Smoke Alarms should be placed between each sleeping area and the living area.
Multi Storey Dwellings
If the dwelling has more than one storey it must have an inter­connected alarm on each level for minimum protection.
Maximum Protection
For maximum protection you should put individual Smoke Alarms in all the rooms where fire is most likely to break out (apart from the locations to avoid, mentioned below). Ensure that theyare allinterconnected. The livingroom isthe most likely place for afire to start at night, followed bythe kitchen and then the dining room. You should also consider putting Smoke Alarms in any bedrooms where fires might occur, for instance, where thereis anelectrical appliance suchas an electricblanket or heater, or where the occupant is a smoker. You could also consider putting Smoke Alarms in any rooms where the occu
­pant is unableto respond very well to afire starting in the room, such as an elderly or sick person or a very young child.
BEDROOM
BEDROOM BEDROOM
KITCHEN
DINING
Figure 3
5
PAGE 2,3,4&5
B13729
REV-1
READ THIS FIRST
CONT.
Single Storey Dwelling with Recommended Protection
8
?
4
4
MOUNTING PLATE
SEALING GASKET
TAMPERPROOF
CATCH
PUSH SCREWDRIVER
STRAIGHT IN
TO RELEASE CATCH
SLIDE
OFF
WARNING:DISCONNECT MAINS
BEFORE REMOVING ALARM
(PUSH COVER BACK)
UNIT WILLNOT FIT
ON THE MOUNTING
PLATEWITHOUT A BATTERYINSTALLED (EI141/144/146 ONLY)
Figure 1a
LOCATING ALARMS
4
4
Multi Storey Dwelling with Recommended Protection
Recommended Protection
See Figures2&3
Minimum protection
+
Smoke Alarms located on:-
·
each storey
·
every 7.5 metres of hallways and escape routes
·
within 3m of all bedroom doors.
- Interconnect all Alarms -
Maximum protection
1
Smoke Alarms located as above plus:
·
All rooms (except bathroom, shower rooms & kitchens)
Heat Alarms located in Kitchens, garages, boiler rooms etc. within 5.3m of potential fire sources.
BASE
4WAYPLUG
ENGAGES SOCKET
ON MOUNTING PLATE
TO CONNECT MAINS BATTERYAND
9
V
olt
Battery
BATTERY
SNAPS
(EI141/144/146
ONLY)
Figure 1b
Figure 2
2
4
Checking you can hear the Smoke & Heat Alarms
With the Alarm soundingin its intended location, check you are able to hear itin each bedroom with the door closed,above the sound ofthe radio. The radioshould be set toa reasonably loud conversation level. If you can’t hear it over your radio the chances are that it wouldn’t wake a person.
If aSmoke Alarm is toofar away forit to wakea person, it isbest to lnterconnect to another SmokeAlarm or HeatAlarm near the bedroom. The alarms can be interconnected -when one alarm senses smoke, all interconnected alarms respond (see below for further details).
LOCATIONS TO AVOID
Don’t place Smoke Alarms in any of the following areas:
·
Bathrooms, kitchens, shower rooms, garages or other rooms where the smoke alarm may be triggered by steam, condensation, normal smoke or fumes. Keep at least 6 metres (20 feet) away from sources of smoke.
Don’t place Heat Alarms in any of the following areas:
·
Bathrooms, shower rooms or other room where the unit may be triggered by steam or condensation.
Don’t place Smoke or Heat Alarms in any of the following areas:
· Places where the normal temperature can exceed 40°C or
be below 4°C e.g. attics, furnace rooms etc. directly above ovens or kettles, as the heat/steam couldcause nuisance alarms.
·
Near adecorative object, door, light fitting,window mould­ing etc., that may prevent smoke or heat from entering the
Alarm.
· Surfaces that are normally warmer or colder than the rest
of the room (forexample attic hatches, uninsulated exterior walls etc). Temperature differences might stop smoke or heat from reaching the unit.
·
Next to or directly above heaters or air conditioning vents, windows,wall vents etc. thatcan change thedirec
-
tion of airflow.
·
In veryhigh or awkward areas(eg. over stairwells) whereit may be difficult to reach the alarm (for testing, hushing or battery replacement).
·
Locate awayfrom verydusty or dirtyareas asdust build-up in thechamber canimpair performance. Itcan also blockthe insect screen mesh and prevent smoke from entering the smoke detector chamber.
·
Locate theunit at least 1 metrefrom dimmer controlled lights and wiring - some dimmers can cause interference.
·
Locate unitat least1.5m androute wiringat least 1m awayfrom fluorescent light fittings aselectrical “noise” and/or flickering may affect theunit. Do not wire into thesame circuit as fluores
-
cent lights or dimmers.
·
Do not locate in insect infested areas. Small insects get
­ting intothe smoke detectorchamber can causeintermittent alarms. Insects and contamination onthe Heat Alarm sen
­sor can increase its response time.
·
The locationsmust complywith applicable buildingregulations.
Hot smokerises and spreads out, soa central ceiling positionis the preferred location. The air is “dead” and does not move in corners, therefore Smoke & Heat Alarms must be mounted away from corners. Place the unitat least 0.5m ) from any light fitting ordecorative objectwhich might obstructsmoke / heaten
-
tering the Alarm. Keep at least 0.5m away from walls. See fig
­ure 4.(Smoke Alarms shouldbe locateddirectly on theceiling or up to 0.57mbelow it. Heat Alarms should be locateddirectly on the ceiling or up to 90mm below it).
Wall mounting is not recommended for these Alarms.
Sloping Ceiling
In areaswith sloping orpeaked ceilings installyour Smoke/Heat Alarm 0.9m from the highest point measured horizontally (see figure 5), because “dead air” at the apex may prevent smoke from reaching the unit.
The Alarm is designed to be permanently mounted , using it’s own built-interminal block toconnect itto the mains.The mount
­ing plate can be screwed directly to the ceiling. Alternatively it can bescrewed to a standard junctionbox. It requires acurrent of 40mA. TheAlarm must not be exposedto dripping or splash
­ing. Thereare importantmarkings on theunderside ofthe alarm.
IMPORTANT PRECAUTION: Do not install the actual
alarm itself in new or renovated buildings until all
work is completed (including floorcoverings) and the buildinghas been fullycleaned. The wiringcan be installed whenappro
­priate. (Excessive dust and debris from building work can contaminate the smokechamber or heat sensor andcause problems, it willalso invalidate the guarantee).If it must be installed, cover it completely, particularly around the edges, witha dustcover (eg. withthe elasticated coversup
­plied or a plastic bag), until all cleaning is finished.
The Alarmmust not
be connectedwhen the housewiring insula
-
tion is being checked with high voltages.
WARNING:
Mains operated Alarms should beinstalled and in
­terconnected by a qualified electrician in accordancewith local institutions. Failureto installthis Alarm correctlymay expose the user to shock or fire hazards.
An ALL-POLE MAINS SWITCH witha contact separation of at least 3mmin each poleshall be incorporated inthe electricial in
­stallation of the building.
WARNING:
The Alarmmust be continuously powered24 hours a dayso it isimportant that itis not on acircuit that canbe turned off by a switch.
INSTALLATION
1. Select a location complying with the above advice.
2. Disconnect theAC mains supply from the circuitthat is going to be used.
3. Remove the mounting plate from the Smoke/Heat Alarm by re
­leasing thetamper-proof catch with asmall screwdriver asshown in figure 1 and sliding the Alarm from the plate.
4. The housewiring must be connected tothe terminal block on the mounting plate as follows:
L: Live - connect to the house wires coloured brown, red or marked L.
N: Neutral - connect to the house wires coloured blue, black or marked N.
IC: Interconnect - connectto the third core. (If you arenot inter
­connecting units, do not connect anything to the IC terminal). (See below for information on interconnecting).
Warning: Mixing Live & Neutral wires will damage intercon
­nected alarms.
We recommend the use of 6243Y mains cable when intercon
­necting units. Use the third core for interconnection.
Do not use an earth wire for the interconnect line.
Lift off the wiring cover as shown in Fig 6.
N.B. Thealarm does notneed to beearthed. However thetermi­nal marked is providedfor the convenienceof theinstaller so that any copper earth wire or cable coloured green or green & yellow, can be safely terminated.
To interconnectthe Alarms connect allthe IC terminalstogether as shown in Figure 8.
5. If the mains wires are recessed, bring the wires through the rear hole in the mounting plate as shown in figure 7.
If the mains wires are being brought along the surface:
(a) positionthe mounting plateso the cabletrunking is as shown in figure 7.
PAGE 6,7,8&9
B13729
REV-1
7
6
8
9
POSITIONING SMOKE & HEAT ALARMS
INSERT SCREWDRIVER
TO LIFT AND REMOVE
WIRE COVER
N
IC
L
CEILING GASKET
(MUST BE IN PLACE)
Figure 6
TERMINAL
SCREWS
EARTH
(IF PRESENT)
(TRUNKING)
RECESSED WIRING
KNOCKOUT FOR
SURFACE CABLE ENTRY
(LEAVETOP INTACT)
N - NEUTRAL
L -LIVE
IC - INTERCONNECT
Figure 7
Figure 5
Figure 4
IDEAL IN CENTRE
OF CEILING
NEVER WITHIN 300mm OF ANY WALL / CORNER
DEAD AIR
SPACES
INSTALLING SMOKE & HEAT ALARMS
90cm
900mm
(3 ft)
Loading...
+ 2 hidden pages