Ei Electronics Ei 156TLR User Manual

Shannon Free Zone, Shannon, Co. Clare, Ireland.
Ph.+353 61 471277 Fx.+353 61 471053 Email. eielectronics@eiltd.ie Web: www.eielectronics.com
E & OE As our policy is one of continuous product development, we reserve the right to alter product details without prior notice. Ei156TLR DataSht RevB
Remote control capability Tamper proof rechargeable lithium battery back up High performance optical chamber with integral
insect screen
Test/Hush button Advanced suppression and calibration technology Interconnectable to other Ei mains powered alarms Built in auto self test feature Low power cell warning Kitemarked to BS EN 14604:2005 5 year guarantee
Product Description
The Ei156TLR is an Optical Smoke Alarm that runs on 230V AC mains power, and has built in tamper proof rechargeable lithium cells that act as a battery back up in the event of mains failure. These rechargeable lithium cells are designed to have a ten year life and outlast the life of the smoke alarm itself, whilst providing up to six months of smoke alarm operation without mains power.
The Ei156TLR allows the detector to be controlled
remotely by either a “Test/Hush” Switch (Ei152), a “Locate” Switch (Ei159) or a Manual Call Point
(MCP400). If the Ei156TLR is also interconnected to other Ei mains powered alarms then the whole system will be controllable remotely.
The Ei156TLR has other advanced features such as integral insect screens to reduce the chances of false alarms, as well as the ability to interconnect up to twelve alarms.
The Ei156TLR has built in circuitry to aid suppression of voltage transients and RF interference to further reduce the chances of false alarms under such conditions.
Operation
The green indicator will illuminate to show mains
power is present
The red indicator will flash every 40 seconds to
show that the detector has performed an automatic self test
The red indicator will flash rapidly to show an alarm
condition for the smoke detector
The “Test/Hush” button will either silence false
alarms or perform a unit self test. In “Test” mode the
alarm will perform a self test and sound the horn
In “Hush” mode the alarm enters a ten minute period
of reduced sensitivity to overcome false alarm conditions, and will then automatically reset itself
When interconnected to other Ei mains powered
alarms, an alarm on one detector will trigger all other interconnected alarms within one second (only the triggered alarm will flash a red indicator)
The smoke detector will emit a beep and flash the
red light every 40 seconds to indicate that the battery back up is depleted and needs recharging
The detector can be controlled remotely by either a
“Test/Hush” Switch (Ei152), a “Locate” Switch
(Ei159) or a Manual Call Point (MCP400).
MAINS POWERED 230V~
Rechargeable Battery Back-Up
Shannon Free Zone, Shannon, Co. Clare, Ireland.
Ph.+353 61 471277 Fx.+353 61 471053 Email. eielectronics@eiltd.ie Web: www.eielectronics.com
E & OE As our policy is one of continuous product development, we reserve the right to alter product details without prior notice. Ei156TLR DataSht RevB
Model Ei156TLR Optical
Installation & Placement
Wiring for Interconnected Alarms
Be very careful about correctly wiring the alarms as mixing Live and Neutral will blow/damage interconnected alarms.
Alarms should be placed in accordance with the general guidelines shown in the diagram above. These recommendations are based on the problem of
areas of “dead air” close to corners of rooms and apexes of ceilings, which
could result in the prevention of smoke reaching the smoke detector Please consult instruction booklet for specific installation details
Important Precaution:
Do not install the actual smoke/heat alarm itself in new or renovated buildings until all work is completed (including floor coverings) and the building has been fully cleaned. The wiring can be installed when appropriate. (Excessive dust and debris from building work can contaminate the smoke chamber and cause problems, and it will also invalidate the guarantee). If it must be installed, cover it completely, particularly around the edges, with a dust cover (eg. a plastic bag), until all cleaning is finished.. Connect wires to the unit as in wiring diagram. All wiring must comply with local codes.
Technical Specification
Sensor Optical, uses light scatter from
smoke
Sensitivity: Complies with BS 5446 Part 1:
2000
Source: Contains no radioactive material Airspeed: Essentially immune to the effect
of airspeed. Button Test: Simulates the effect of smoke and
checks chamber, electronics and horn.
Ambient Light: Chamber housing design and
compensation overcomes problems with stray light.
Automatic Self-Test: Smoke Chamber is tested every 40 Sec. and unit beeps (without LED flash) if it is degraded.
Insect Screen: Prevents insects or debris entering
chamber (1.00mm mesh size)
Supply Voltage: 230V AC Battery back up: Rechargeable lithium cells Power-On Indicator: Continuous green LED
Alarm: Electronic Piezoelectric horn Alarm Sound Output: 85dB (minimum) at 3m Alarm Status: Red LED flashes every second on
unit sensing fire
Temperature Range: 0° to 40°C Humidity Range: 15% to 95% Relative Humidity Remote Control: Ei152, Ei159 or MCP400 Interconnect: Up to 12 interconnected
Ei150/151TLR/154TL/155/156TLH/ 156TLR smoke or heat alarms, along with an EI158 relay base
Fixing: Screw fixings supplied Plastic material: UL94VO flame retardant Dimensions: 140mm x 120mm x 46mm Weight: 230g Warranty: 5 year (limited) warranty Approvals: Kitemarked to BS EN 14604:2005,
CE Approved
Specifications are subject to change