Ei Electronics Ei141, Ei144-Heat, Ei161RC - Ionisation, Ei146 - Optical, Ei164RC - Heat Installation Instructions Manual

...
IDEALLY INSTALL IN THE CENTRE OF CEILING AT LEAST 300mm FROM LIGHT FITTINGS
LOCATE IONISATION ALARMS AWAY FROM KITCHENS TO PREVENT NUISANCE ALARMS
ENSURE LIVE MAINS IS CORRECTLY CONNECTED TO L TERMINALS ON ALL INTERCONNECTED ALARMS - OTHERWISE UNITS WILL BE DAMAGED
DO NOT FIT ACTUAL ALARM UNTIL ALL BUILDING WORK IS COMPLETED TO AVOID CONTAMINATION. AFTER CHECKING OPERATION, COVER SMOKE ALARM WITH DUST COVER UNTIL REQUIRED FOR USE
DISCONNECT THE ALARM BEFORE APPLYING HIGH VOLTAGE INSULATION TESTS TO WIRING
DO NOT ATTEMPT TO OPEN THE ALARM AS IT IS PERMANENTLY SEALED FOR SAFETY
DO NOT CONNECT ALTERNATIVE ENERGY SOURCES e.g. WIND, SOLAR, UPS WITH NON-SINUSOIDAL OUTPUTS (see INSTALLATION section on page 10)
INTERCONNECT ALL ALARMS
230V~ SMOKE & HEAT ALARMS
INSTALLER INSTRUCTIONS
Ei141 - Ionisation Ei144 - Heat
Ei146 - Optical
RECHARGEABLE LITHIUM CELL BACK-UP
Ei161RC - Ionisation Ei166RC - OpticalEi164RC - Heat
ALKALINE PRIMARY BATTERY BACK-UP
© Ei Electronics 2012P/N B16008 Rev3
1.1 Installation Guide
2
2. ALARM REMOVAL
SLIDE ALARM OFF BASE
WITH THE SCREWDRIVER STILL INSERTED, PUSH THE LOWER HALF OF THE ALARM AWAY FROM THE SCREWDRIVER, IN THE
DIRECTION OF THE ARROW ON THE COVER
HOLD THE LOWER HALF OF THE ALARM AND REMOVE FROM
THE BASE PLATE BY MOVING IT VERTICALLY DOWNWARDS,
T
O
WARDS THE FLOOR.
REMOVE ALARM
LOCATE REMOVAL SLOT
LOCATE THE ARROW ON THE FRONT FACE OF THE ALARM.
THE SLOT IS LOCATED DIRECTLY ABOVE THE ARROW
.
INSERT SCREWDRIVER
INSERT A FLAT-BLADED SCREWDRIVER HORIZONTALLY
APPROX. 1cm INTO THE CENTRE OF THE REMOVAL SLOT
T
O
R
E
M
O
V
E
P
U
S
H
&
P
U
S
H
C
O
V
E
R
A
W
A
Y
S
C
R
E
W
D
R
I
V
E
R
I
N
T
O
S
L
O
T
3
2. HOW MANY ALARMS TO INSTALL
- CATEGORIES & GRADES -
The advice here follows the guidance in British Standard BS 5839-Part 6: 2004 in general (for further information see the BS standard itself).
The main reason for fitting Smoke & Heat Alarms in dwellings is to ensure that when there is a fire, sufficient early warning is given so that everybody can escape safely.
This means that the fire alarms should ideally be located near all potential sources of fires and that the alarm should be heard throughout the house – particularly in the bedrooms.
It is also important that nuisance/false alarms are minimised to ensure the units are not disabled or ignored.
The BS standard gives guidance on:
- how many alarms to install
- what type of alarm to use
- where to position alarms
The above points will depend on the type of dwelling to be protected and the level of fire risk.
Fire Risk Assessment
The ‘Grade’ and ‘Category’ of system that should be installed depends on the fire risk. The risk assessment is based on a combination of probabilities:
- fire occurring
- injury or death to occupant
- system operating correctly with a fire
- early detection and warning to occupants in the event
of a fire.
The greater the risks, the more comprehensive and reliable systems are needed.
2.1 Categories of System
There are three Categories of LD systems for Life protection in Dwellings that can be installed, depending on the fire risk and regulations.
Please see following pages for detailed information.
4
for existing dwellings
MINIMUM PROTECTION
LD3
Minimum Protection LD3:
Smoke Alarms in all hallways, stairways and circulation areas that form part of the escape routes from the dwelling.
Multi Storey Dwelling LD3
Living Room
Bedroom Bathroom
Kitchen
Bedroom
Shower
Garage
Smoke Alarms located:
on each storey every 7.5 m of hallways and escape routes within 3m of all bedroom doors
(apart from toilets & bathrooms )
Bedroom
Bedroom Bedroom
Kitchen / Dining Room
Living Room
Bathroom
Single Storey Dwelling LD3
do not fit alarm
Ionisation or Optical Smoke Alarm
Optical Smoke Alarm