Ei Electronics Ei144 Heat Product Manual

Shannon Free Zone, Shannon, Co. Clare, Ireland.
Ph.+353 61 471277 Fx.+353 61 471053 Email. eielectronics@eiltd.ie Web: www.eielectronics.com
Model Ei144 Heat
Easi-Fit base 9V Alkaline Battery back up Fixed temperature fast response thermistor type
sensor, range 54°C to 62°C
Test/Hush button Advanced suppression and calibration technology Interconnectable to other Ei mains powered alarms Low power cell warning Kitemarked to BS5446-2:2003 5 year guarantee
Product Description
The Ei144 is a Heat Alarm that runs on 230V AC mains power, and has a 9V alkaline battery back up in the event of mains failure. The 9V battery will last for up to 4 years in standby mode, and capable of powering the heat detector for up to 2 years in the event of mains failure.
The Ei144 is supplied with the Easi-Fit base that allows very quick and simple installation of the heat alarm. The Easi-Fit base automatically connects both mains power and battery as the detector head slides on to the Easi-Fit base.
The Ei144 has the ability to interconnect up to twelve alarms to allow all alarms to sound if just one of the interconnected alarms should be triggered.
The Ei144 has built in circuitry to aid suppression of voltage transients and RF interference to further reduce the chances of false alarms under such conditions.
The Ei144 heat alarm gives a fire warning when the temperature at the unit reaches 580C. Heat alarms are ideal for use in kitchens and garages, where the use of optical or ionisation alarms would lead to unwanted nuisance alarms.
On escape routes this alarm must be interconnected
Operation
The green indicator will illuminate to show mains
power is present
The red indicator will flash every 40 seconds to
show that the detector has performed an automatic self test
The red indicator will flash rapidly to show an alarm
condition for the heat detector
The “Test/Hush” button will either silence false
alarms or perform a unit self test
In “Test” mode the alarm will perform a self test and
sound the horn
In “Hush” mode the alarm enters a ten minute period
of reduced sensitivity to overcome false alarm conditions, and will then automatically reset itself
When interconnected to other Ei mains powered
alarms, an alarm on one detector will trigger all other interconnected alarms within one second (only the triggered alarm will flash a red indicator)
The heat detector will emit a beep every 40 seconds
to indicate that the battery back up is depleted and needs replacing
MAINS POWERED 230V~
9V Alkaline Battery Back-Up
Shannon Free Zone, Shannon, Co. Clare, Ireland.
Ph.+353 61 471277 Fx.+353 61 471053 Email. eielectronics@eiltd.ie Web: www.eielectronics.com
Model Ei144 Heat
Installation & Placement
Wiring for Interconnected Alarms
Be very careful about correctly wiring the alarms as mixing Live and Neutral will blow/damage interconnected alarms.
Locate heat alarms in rooms adjoining or on escape routes – kitchens, garages, boiler houses etc. where smoke alarms are unsuitable. Install within
5.3m of potential sources of fire. Please consult instruction booklet for specific installation details
Important Precaution:
Do not install the actual smoke/heat alarm itself in new or renovated buildings until all work is completed (including floor coverings) and the building has been fully cleaned. The wiring can be installed when appropriate. (Excessive dust and debris from building work can contaminate the smoke chamber and cause problems, and it will also invalidate the guarantee). If it must be installed, cover it completely, particularly around the edges, with a dust cover (eg. a plastic bag), until all cleaning is finished.. Connect wires to the unit as in wiring diagram. All wiring must comply with local codes.
Technical Specification
Sensor Thermistor Sensitivity: Complies with BS 5446 Part 2:
2003
Source: Contains no radioactive material Airspeed: Essentially immune to the effect
of airspeed. Button Test: Simulates the effect of heat and
checks electronics and horn.
Supply Voltage: 230V AC Battery back up: 9V Alkaline Battery Power-On Indicator: Continuous green LED Alarm: Electronic Piezoelectric horn
in unit
Alarm Sound Output: 85dB (minimum) at 3m Alarm Status: Red LED flashes every second on
unit sensing heat
Temperature Range: 0° to 40°C Humidity Range: 15% to 95% Relative Humidity Interconnect: Up to 12 interconnected mains
powered easi-fit smoke or heat alarms, along with an EI128 relay base
Fixing: Easi-Fit mounting base Plastic material: UL94VO flame retardant Dimensions: 145mm diameter x 52mm depth Weight: 281g Warranty: 5 year (limited) warranty Approvals: Kitemarked to BS5446-2:2003, CE
Approved
Specifications are subject to change