(b) carefully cut around the knockouts on the two alarm side
walls so it blends with the contours of the alarm sidewall.
Important: only cut the thinned down knockout section and
leave thetop intactas shown. Thereis only oneposition suitable
for the surface wiring to enter the alarm.
6. Carefully alignthe mounting plate andscrew into place. Con
-
nect the wires to the terminal block. With recessed wiring, en
sure the rear gasket seals around the edge of the hole in the
ceiling or wall. This is to prevent air draughts affecting the
smoke / heat entering the alarm. If the orifice is too large it
should be sealed with silicone rubber or equivalent.
Replace the wiring cover. Check the battery is connected (140
series only).
Carefully line up the unit on the base and slide on.
Press thetest/hush buttonfor 10 seconds.The hornwill sound.
CAUTION: Do not attemptto remove the Alarm without first re
leasing the tamper clip as shown in Figure 1.
7. Connect the mains power to the alarm circuit. Check the
green light is on. Attach the label provided to the distribution
board to identify the alarm circuit.
Attach the‘Mains Smoke/ Heat Alarm’label onor near thedistribution board and write in date installed and the number of
alarms on the circuit.
Check the operation of the Alarm as outlined below.
INTERCONNECTING
EI ELECTRONICS SMOKE / HEAT
ALARMS
Note: Amaximum oftwelve Ei143/144/145/146/ 164/166Smoke or
Heat Alarms maybe interconnected along with an Ei
128 pattress
with relay (see Accessories below).
(If youwish to connectmore than twelvealarms contact yourdistrib
utor). Systemsusing more than 3or 4 alarms mustbe very carefully
planned to ensure nuisance alarms are not excessive. e.g. from
cooking or weekly testing.
·
Smoke Alarm Locator Switch (EI 159) should be incorpo
-
rated into the system and be readily accessible to all occu
-
pants sothat thesource of analarm canbe quickly identified.
·
All alarms must be cleaned and maintained regularly.
·
A qualified person must be on call to quickly remove any
faulty alarms (i.e. units with red light flashing), which are
causing all the alarms to sound.
WARNING: Donot connectthese Alarms toany other typeof Ei
Alarm, or to any other model produced by another manufac
-
turer, apart from thoselisted above. Doing this may damage the
Alarms and could result in a shock or fire hazard.
The interconnectwire (minimum0.75mm
2
cable) mustbe treated as
if it was live. It should be insulated and sheathed.
A maximumof 250metres of wirecan beused (maximum resistance
between detectors 50 ohms).
These Smoke/HeatAlarms shouldbe interconnected onlywithin the
confines ofa single family livingunit. If theyare connected between
different units theremay be excessive nuisance alarms.Everybody
may not be aware thatthey are being tested or that it is a nuisance
alarm caused by cooking etc.
INSPECTION & TESTING PROCEDURE
After installation check all the Alarms
We recommend thatthe functioning of the mains batteryback-up is
checked directly after installation as follows:
(i) Turn offthe mains power at the distributionboard and check that
the green mains indicator on the alarm is extinguished.
(ii) Press the testbutton and ensure that the horn sounds loudly for
10 seconds. Ensure that any interconnected alarms also sound.
(iii) Repeatthe process on all interconnectedalarms on the system.
Turn the mains power on only if the units pass the above test.
(iv) Check thatthe green mains indicator lightis on. (If it isoff check
circuit breakers, fuses and wiring etc.) Check the red light on the
cover flashes every 40 seconds.
(v) Press the test button for up to 10 secondsto ensure the sensor
chamber, electronics andsounder are working. The red lighton the
cover willflash while horn is sounding.The alarm will stop whenthe
button is released. Pressing the test button simulates the effect of
smoke or heat during a real fire and is the best way to ensure the
Alarm is operating correctly.
WARNING: DO NOT TEST WITH FLAME.
This can set fire to the Alarm and damage the house.
We do not recommendtesting with smoke or heat as theresults
can be misleading unless special apparatus is used.
Interconnected alarms
Test the firstunit by pressing thebutton. All the detectors should
alarm within about 5 seconds of the first horn sounding and the
red light on thefirst unit only will flash once a second. Checkall
the otherunits similarly. (Note:Heat alarms signal toother inter
connected alarms about4 seconds after their own horn sounds.
Optical alarms signal within about a second.
Checking Battery Back-up
When the unit is beeping:
The Alarm automatically monitors the battery every 40 seconds to
ensure that it is satisfactory. Ifit is depleted it will give a short beep
every 40 seconds.
Models Ei144 & Ei 146 only
Before replacingthe battery,check that thebeeps arenot due toone
of the following:
(i) battery snaps not connected properly.
(ii) Onthe Optical SmokeAlarm only (
EI 146/145)if the unitbeeps
and the redlight does not flash atthe same time it indicatesa prob
lem with the smokechamber - see Cleaning the Smoke Alarm section below.
If the beeps have continued for over 20 minutes (and the other
causes of beepshave been ruled out -see below) the battery must
be replaced.
(iii) Switch off themains and remove the unit as shownin figure 1a.
Remove depleted battery and replace with one of the specified 9V
alkaline batteries. The alarm cannot be replaced on the mounting
plate unless a battery is installed. After replacing the battery, slide
on the mounting plate then press the test button and ensure horn
sounds loudly before you turn on the mains. Ifit is satisfactory turn
on the mains and check that the green light comes on. Note: Only
use the specified Alkaline batteries shown on the base label
(Duracell MN1604 or Eveready522). We recommend that the “use
by date” onthe battery should still haveat least 2 years togo. Older
batteries will give beeps prematurely.We recommend that the bat
tery is replaced each year for optimum performance.
Models Ei161, Ei164 & Ei 166 only
(i) Check that thegreen mains power light is on. Ifit is off the Alarm
has beenpowered fromthe cells andthe beeps indicatethey are de
pleted. Re-connect the mains,check fuse, circuit breakers and wir
ing. If in doubt contact a qualified electrician. The beeps should
cease within 2 hours as the cells charge up.
(ii) The cells may be depleted. The beeps should cease within 2
hours asthey charge up. Fullycharged, the cells willprovide up to 6
months back-up without mains power.
(iii) On the Optical Smoke Alarms only (
EI 166) if the unit beeps
and the redlight does not flash atthe same time it indicatesa prob
lem with the smoke chamber - see Cleaning the Smoke Alarm.
If all ofthe above possible causes ofbeeps have been ruled outbut
the beepinghas stillpersisted for over2 hours withthe green lighton
- the rechargeable cells are probably defective. The Smoke / Heat
Alarm must be returned to the manufacturer for repair or replace
-
ment (see section Getting Your Alarm Serviced).
(Please note:The ionisation alarms(EI140/141/161) give twoshort
beeps abouta second apart atthe end of thehush period (i.e. about
10 minutes after test/hush button has been pressed. These two
beeps should not be confused with low battery beeps.
(a) Relay Module
EI 128:
The Ei128 module has a relayrated 250V AC /5 amps. This isuse
-
ful for remote signalling and turning on lights.
(b) Smoke Alarm Locator Ei 159:
The SmokeAlarm locator isrecommended for systemswith three or
more Smoke / Heat Alarms as it helps quickly identify the unit in
alarm and reduces the impact of nuisance alarms.
Pressing the Smoke Alarm Locator button will silence all interconnected alarms for 10 minutes, exceptthose sensing fire. It is easily
installed between the interconnect and neutral terminals.
(2) The Heatalarms (Ei 143/144/164) give twobeeps 10 minutes
after the test/hush button is pressed.
(3) Ifthe Optical units(EI 146/145/166) beepswithout the redlight
flashing atthe same time, thechamber is defective.Clean the
chamber.
4. INTERCONNECTED ALARMS DO NOT ALL SOUND:
(1) Holdtest button for10 seconds afterfirst alarm has sounded
to ensure signal is transmitted to all units.
(2) Switch off mains and check that live, neutral and intercon
-
nect cableshave beencorrectly connected andthat the con
-
nections are tight.
10
11
12
13
CHECKING THE OPERATION OF THE
ALARMS
PAGE 10,11,12&13
B13729
REV-1
ACCESSORIES
Figure 8
L - LIVE
N - NEUTRAL
IC -I
NTERCONNECT
TROUBLESHOOTING
CONT.