Ei Electronics EI 103C User Manual

1. Basic Information about your Heat Alarm
A Heat Alarm is an early warning device. A system based on in terconnected Heat Alarms and Smoke Alarms, can give you and your family valuable extra time to escape.
Note:-
Install correctly, in the centre of the ceiling if possible.
·
·
Replace alkaline battery yearly or when it beeps once a min
·
ute. When the power is first connected the Alarm may sound for
·
2-3 seconds - this is normal. A Heat Alarm does not prevent fires.
·
Plan your escape route.
·
Proper fire protection requires Smoke Alarms in addition to
·
Heat Alarms with all units interconnected. If you have any doubt or query about Heat Alarms consult
·
the supplier or your local Fire Brigade.
Near a decorative object, door, light fitting, window
Figure 1
-
Recommended Locations for Interconnected Heat Alarms and Smoke Alarms
·
molding etc., that may prevent the heat reaching the unit Surfaces that are normally warmer or colder than the rest
·
of the room (for example attic hatches, uninsulated exterior walls etc).
Next to or directly above heaters or air conditioning
·
vents, windows, wall vents etc. that can change the direc
Heat Alarms
-
tion of airflow. In very high or awkward areas (eg. over stair shafts) where
·
it may be difficult to reach the alarm for testing and battery
-
replacement.
Smoke Alarms
·
trolled lights and wiring - some dimmers can cause inter
-
-
Locate the unit at least 1 metre (3 feet) from dimmer con
ference. Locate unit at least 1.5m(5 feet) and route wiring at least 1m
·
(3 feet) away for fluorescent light fittings as electrical “noise” and/or flickering may affect the unit.
In excessively dirty or dusty locations where contamination
·
build-up could slow down response.
2. Locating your Heat Alarm
The Heat Alarmgives a fire warningwhen the temperature at the unit reaches 58° C. It is ideal for kitchens, garages, boiler houses and other areas where there are normally high levels of fumes, smoke or dust i.e. places where Smoke Alarms cannot be installed without the risk of excessive nuisance alarms. A Heat Alarm should only be used in a room adjoining an escape route, in conjunctionwith Smoke Alarms onthe escape routes.
All the Heat Alarms and Smoke Alarms should be intercon­nected to ensure the early warning will be heard, particularly by somebody sleeping. A Heat Alarm installed in a closed room will give early warning of fire in that room. A properly designed early warning fire system ensures the alarm is given before the es cape routes become blocked with smoke - therefore there must be Smoke Alarms along the escape routes as Heat Alarms would not give sufficient warning. However, a fire in a closed room (e.g. kitchen) adjoining the escape route, can eventually cause the corridor to become smoke-logged due to smoke leak ing out from around the door before adequate warning can be given by detectors in the corridor. (Smoke leaking out from a room is often cool and slow moving so it can take a long time to rise to the ceiling, and travel to a detector which could be some distance away).
Figure 1 illustrates where Heat Alarms and Smoke Alarms should be located in a typical two storey house. The following gives the recommended spacings tobe used to ensure the early detection of fire and that the warning will be heard:
2
Heat Alarms
Rooms adjoining or on escape routes - kitchens, garages,
-
boiler houses etc. where Smoke Alarms are unsuitable. In stall within 5.3m (17 feet) of potential sources of fire.
Smoke Alarms
1. Within 7m (23 feet) of doors to rooms where a fire is likely to start. Corridors over 15m (46ft) should have more than
-
one Smoke Alarm.
2. On each storey.
3. Within 3m (10 feet) of bedroom doors - so warning will be heard.
4. All other rooms where a fire could start (except those with cooking/car fumes or condensation).
3. Positioning your Heat Alarm
Location must comply with applicable building regulations.
(a) Ceiling Mounting
Hot smoke rises and spreads out, so the Heat Alarm must be put on the ceiling- preferably in thecentre. The sensitive element (in the cylindrical protrusion) must not be less than 25mm (1 inch) or more than 150mm (6 inches) below the ceiling or roof.
3
The air is “dead” and does not move in corners, therefore Heat Alarms must be mounted away from corners. Place the unit at
-
least 30cm (12 inches) from any light fitting or decorative object which might obstruct the heat travelling to the Alarm. Keep at
IDEAL IN CENTRE OF CEILING
least 15 cm (6 inches) away from walls and corners. (See figure 2). Wall mounting is not recommended for Heat Alarms. If the ceiling has a pitched roof install an Alarm
DEAD AIRSPACES NEVER WITHIN 15cm
OF ANYCORNER
within each apex.
(b) Locations to Avoid
Figure 2
Don’t place your Heat Alarm in any of the following areas:
·
Places where extremes of temperature may occur - below 4°C or above 43°C. e.g. attics, furnace rooms etc. Directly above ovens or kettles as the heat/steam could cause nui sance alarms.
·
Bathrooms, shower rooms or other rooms where the unit may be triggered by steam or condensation.
4
Figure 3
(1) COVER
(4) WRITE IN
DATE BATTERY
INSTALLED
(6) SCREW
HOLE
(10) 9 VOLT
BATTERY
(9) BATTERY
HOLDER
(2) "OPEN HERE"
(8) BATTERY
CONNECTORS
TAB
(7) PLASTIC
CLIP
(3) COVER
STRAIN RELIEF
(11) INTERCONNECT
TERMINALS
4. Installing your Heat Alarm
(a) Attaching to Ceiling .
-
(NB: for wiring the interconnect see page 7)
The Heat Alarm is battery operated. Use figure 3, as a help in mounting.
5
(5) HINGES
(6) SCREW
HOLE
P/N B11803
PAGE 2,3,4&5
REV 0
1. Pull Coveropen at Tab (2).Do not remove Coverfrom base.
2. Place the Base on ceiling or wall exactly where you want to mount the unit. With a pencil, mark the location of the Screw Holes (6)
3. Taking care to avoid any electrical wiring in the ceiling, drill a hole through thecenters of themarked locations. Push the plas tic Screw Anchors provided into the drilled holes. Screw in firmly.
(b) Connecting the battery.
With a pencil, write the date of Battery installation on the inside of the Cover to remind you when to replace the battery (4).
Lift Battery from Battery holder, and snap Battery Connectors to Battery. They fit together only one way (Figure 4).
9 Volt
Battery
Figure 4
Battery
Connectors
Figure 5
NOTE: You may hear a loud chirp when attaching the Battery Connectors to the Battery. Test the installed Heat Alarm - see section 6(a) below.
Some models will be fitted with a battery missing indicator warn­ing flag which pops up when the battery is removed. This pre vents the cover from closing when there is no battery in the unit. When the battery is being installed or changed, this flag must be held down while gently pushing the Battery into the Battery Holder. (see figure 5).
5. Interconnecting your Heat Alarms and Smoke Alarms.
A maximum of 12 interconnect EI 103, EI 100C and EI 105C Heat/Smoke Alarms may be wired together so that when one unit senses fire all other units sound a warning. This helps en sure the alarms will be heard.
Warning: Do not interconnect to any other Heat / Smoke Alarms
A maximum of 820 feet (250 metres) of wire can be used, (maxi mum resistance between detectors 50 ohm).The units areinter connected by wiring all the terminals marked 1 together, and all the terminals marked 2 together,as shown in Figure 6. An open ing should be made in the label covering the wiring hole in the base, and the wires routed into the unit as shown. Note that the
6
wiring inside the unit must be kept clear of the test button con tacts, and must not impede the air flow. Drafts from wiring open ings, conduit, or mounting boxes/holes, may blow smoke away from the sensing chamber, making it insensitive. It is essential that all such openings be closed by silicone sealant or similar.
-
WIRING HOLE
Figure 6
COVER (NOT REMOVEABLE)
INTERCONNECT WIRES
TERMINAL 1
TERMINAL 2
TEST BUTTON
CONTACTS
After wiring together the Interconnect Alarms, test the first unit by pressing the button. All the detectors should alarm within 10 seconds and the red light only on the unit being tested, will flash about once a second. Check all the other units similarly.
These Alarms should be interconnected only within theconfines of a singlefamily living unit. Ifthey are connected between differ­ent units there may be excessive nuisance alarms. Everybody may not be aware that they are being tested or that it is a nui­sance alarm caused by cooking etc.
-
6. Looking after your Heat Alarm
(a) Testing your Heat Alarm
It is recommended that you test your Heat Alarm once a week to be sure the unit is working. Press and hold the Test Button until the alarm sounds (it may take up to 10 seconds) see figure 7. It will also help you and your family to become familiar with the sound of the Alarm.
(b) Testing with Heat
­When you press the Test Button it simulates the effect of Heat during a real fire. So, there is no need to test the Alarm with Heat.
WARNING: Do not test with flame.
-
This can be a fire hazard in itself.
­If you want to check your Alarm with heat we recommend using
a hair dryer with a power rating of at least 1000 watts. Direct the
­hot air as shown in figure 8 on to the heat sensor and the alarm
should sound within 30 seconds.
7
-
-
Figure 7
Figure 8
If the alarm fails to sound, follow this checklist.
1. Check BatteryConnectors to be sure they are firmly snapped to the Battery.
2. Replace the Battery. (Check the date marked on the Cover when you last replaced the Battery).
3. Refer to “Cleaning Your Heat Alarm” 6 (d).
(c) Replacing the Battery.
A fresh battery should last about one year. When battery power is low andreplacement is necessary,the Alarm will “beep” about once per minute for at least 30 days. The battery must then be replaced. Replace battery if the alarm does not sound when the Test Button is pressed. For maximum reliability, replace battery at least once a year.
If the Power Indicator light ceases flashing every 40 seconds re­place the battery. Be sure to replace the battery as soon as pos­sible to ensure proper operation and to avoid a leaking battery. Leakage could cause damage to the Alarm, furniture, and car peting.
For replacement batteries, refer to the label inside the Heat Alarm Cover.
WARNING: Use of any other battery may be detrimental to the operation of the Heat Alarm.
(d) Cleaning your Heat Alarm
Heat Alarms arenot as susceptible todust and contamination as Smoke Alarms but it is prudent to clean them periodically. Use the narrow nozzle attachment of your vacuum cleaner to re move dust, insects and cobwebs from the sides and cover slots where the heat enters. To clean the cover, wipe with a damp cloth. Dry cover thoroughly with cloth.
WARNING: Do not paint your Heat Alarm.
Other than the cleaning described above, no other customer servicing of this product is required. Repairs, when needed, must be performed by the manufacturer.
8
7. Nuisance Alarms
If, when the alarm goes off, there is no sign of smoke, heat or noise to indicate that there is a fire, you should get your family into a safe place, before you start investigating.
Check the house carefully in case there is a small fire smould-ering somewhere.
Check whether there is some source of heat, fumes or smoke, for example steam froma kettle triggering a Heat Alarm or cook ing fumes being drawn pasta Smoke Alarm by an extractor. The Heat Alarm or Smoke Alarm initiating the alarm can beidentified as it willhave a rapidlyflashing red light. If there are frequent nui sance/false alarms it may be necessary to re-locate the offend ing device away from the cause of the alarm.
8. (a) Important Safeguards
When using household protective devices, basic safety precau tions should always be followed, including those listed below:
Please read all instructions.
·
Rehearse emergency escape plans so everyone at home
·
knows what to do in case the alarm sounds.
· For replacement batteries,refer to label insideHeat Alarm.
· NOTE: Constant exposure to high or freezing temperatures
or high humidity may reduce the life of the batteries.
· Do not disconnect battery to stop alarm sounding. (Fanning
vigorously with a newspaper or similar will remove heat from the Heat Alarm and stop it sounding.)
· Do not attempt to recharge or burn batteries, as they may
explode. Wrap in paper and discard normally.
· When removing battery, handle carefully to avoid possible
-
-
eye damage or skin irritation if battery has leaked or cor roded.
·
To maintain sensitivity to heat, do not paint or cover Heat Alarm in any manner; do not permit any accumulation of cobwebs, dust or grease.
·
If unit has been damaged in any way or does not function properly,do not attempt a repair. Return Heat Alarm (see ­Getting your Heat Alarm Serviced page 11.)
·
This appliance is only intended for premises having a resi dential type environment.
·
This is not a portable product. It must be mounted following the instructions in this leaflet.
·
Heat Alarms are not a substitute for insurance. The supplier or manufacturer is not your insurer.
(b) Limitations of Heat Alarms
Heat Alarms combined with Smoke Alarms can significantly help to reduce the risk of fire fatalities.
However independent authorities have stated that these sys tems may be ineffective in some fire situations. There are a number of reasons for this:
9
-
-
-
-
-
-
-
P/N B11803
PAGE 6,7,8&9
REV 0
Heat Alarms will not work if the batteries are depleted or if
·
they are not connected, or if the wrong type of battery is used. Test regularly and replace batteries at least yearly or when depleted.
Alarms will not detect fire if sufficient heat/smoke does not
·
reach the alarms. Heat/smoke may be prevented from reaching the Alarm if the fire is too far away, for example, if the fire is on another floor, behind a closed door, in a chim ney, in a wall cavity, or if the prevailing air drafts carry the heat/smoke away. Installing heat alarms and smoke alarms on both sides of closed doors and throughout the house or premises as recommended in this leaflet will very signifi cantly improve the probability of early detection.
The Alarms may not be heard.
·
An alarm may not wake a person who has taken drugs or al
·
cohol.
The alarms maynot detect every type of fire togive sufficient
·
early warning. They are particularly ineffective with: fires caused by smoking in bed, escaping gas, violent explo sions. poor storage of flammable rags and/or liquids, (for ex ample petrol, paint, spirits etc), overloaded electrical circuits, arson, children playing with matches.
· The Alarms don’t last indefinitely. The manufacturer recom-
mends regular weekly testing and replacement after, at most, 10 years, as a precaution.
9. (a) Planning your Escape for when the Alarm goes off
Use the Heat Alarm and Smoke Alarm test buttons to familiarize your family and other occupants with the Alarm sound and to practice fire drills regularly with all occupants. Draw up a floor plan that will show each member at least 2 escape routes from each room in the house. Children tend to hide when they don’t know what to do. Teach children how to escape, open windows, and use roll up fire ladders and stools without adult help. Make sure they know what to do if the alarm goes off - see below.
1. Check room doors for heat or smoke. Do not open a hot door. Use an alternate escape route. Close doors behind you as you leave.
2. If smoke is heavy, crawl out, stay ing close tofloor. Take short breaths, if possible, through a wet cloth or hold your breath. More people die from smoke inhalation than from flames.
3. Get out as fast as you can. Do not stop for packing. Have a prear ranged meeting place outside for all family members. Check everybody is there.
-
-
-
-
(b) Fire Safety Hints
­Store petrol andother flammable materials inproper containers.
Discard oily or flammable rags.
Always use a metal fireplace screen and have chimneys cleaned regularly.
Replace worn or damaged sockets, switches, home wiring and cracked or frayed electrical cords and plugs.
Do not overload electrical circuits.
Keep matches away from children.
Never smoke in bed. In rooms where you do smoke, always check under cushions for smouldering cigarettes and ashes.
Service central heating systems regularly.
Be sure allelectrical appliances andtools have arecognised ap proval label.
Futher information can be obtained from the Home office Publi cation entitled “SmokeDetectors in your Home” (FB2) or yourlo cal fire prevention officer.
4. Call the Fire Brigade from a neigh bour’s house. Remember to give your name and address.
5. NEVER re-entera burning house.
10. Getting your Heat Alarm Serviced
If your Heat Alarm fails to work after you have read the sections on “Connecting the battery” and “Looking after your Heat Alarm” return it for repair or replacement in a padded box (battery dis
­connected) to “Customer Assistance and Information” at the nearest address given on the Heat Alarm or in this leaflet. State the nature ofthe fault, wherethe Heat Alarm was purchased and the date of purchase.
11. Five Year Product Guarantee
Ei Electronics guarantees this product (excluding battery) for
­five years from date of purchase against any defects that are
due to faulty material or workmanship. This guarantee only ap plies to normal conditions of use and service, and does not in clude damage resulting from accident, neglect, misuse, unauthorised dismantling, or contamination howsoever caused.
­This guarantee excludes incidental and consequential dam
age. If this Heat Alarm should become defective within the war ranty period, it must be returned to the E.I. Co, carefully packaged, with the problem clearly stated. (see “Getting Your Heat Alarm Serviced”) We shall at our discretion repair or re place the faulty unit. Do not interfere with the Heat Alarm or at tempt to tamper with it. This will invalidate the guarantee.
This guarantee is in addition to your statutory rights as a con sumer.
Ei Electronics, 9 Grundy Street, Liverpool L5-9SG, U.K. Ei Electronics, Shannon, Co.Clare, Ireland.
-
-
-
-
-
-
-
-
-
-
-
© Ei Electronics 2001
P/N B11803
9 VOLT BATTERY
HEAT ALARM
INSTRUCTION LEAFLET
Contains vital information on unit operation and installation. Read and retain carefully. If you are just installing the unit this leaflet MUST be given to the householder.
10
11
P/N B11803
PAGE 10,11,12 &1
REV 0
12
MODEL:
EI 103C WITH INTERCONNECT
Loading...