High sensitivity – responds to all standard fires Dual Ionization chamber - quick response fast
flaming fires
Supply voltage 10.2 to 14 volts Interconnect up to 12 alarms Relay contacts Built in sounder Test button Kitemarked to BS5446-1:2000 5 year guarantee
Product Description
The Ei100R is an Ionisation Smoke Alarm that is designed to operate with suitable 12 volt control panels and to provide a loud local alarm.
Ionisation smoke alarms operate on the principle that electrical current flowing between electrodes in an ionization chamber is reduced when smoke particles enter.
Ionisation technology gives a rapid response to fast flaming fires
Relay contacts (normally open and closed supplied) are available for triggering the panel itself and its associated ancillary products, such as extra loud sirens, magnetic door holders, etc.
The alarms can be interconnected so that when one alarm senses fire, all the units located throughout the premises sound.
The Ei100R is easily installed and comes supplied with all necessary screw fixings.
Operation
The smoke detector will activate the built in sounder
upon sensing smoke particles
The smoke detector will automatically reset itself
and silence the sounder when smoke particles are no longer present in the sensing chamber
The built in sounder will provide a minimum sound
output of 85dB at 3m
The “Test” button will perform a self test and sound
the horn (it may take up to 10 seconds)
Red LED –flashes every 40 seconds to indicate unit
checks
Interconnect up to 12 other alarms (9V ionisation,
optical or heat) when one senses smoke, all alarm. Helps ensure warning will be heard throughout the house
E & OE As our policy is one of continuous product development, we reserve the right to alter product details without prior notice. Ei100R DataSht RevA
Shannon Free Zone, Shannon, Co. Clare, Ireland.
Ph.+353 61 471277 Fx.+353 61 471053 Email. eielectronics@eiltd.ie Web: www.eielectronics.com
Model Ei100R Ionisation
Installation & Placement
Alarms should be placed in accordance with the general guidelines shown in the diagram above. These recommendations are based on the problem of
areas of “dead air” close to corners of rooms and apexes of ceilings, which
could result in the prevention of smoke reaching the smoke detector Please consult the Instruction Leaflet supplied with the Ei100R for detailed
instructions as to how to correctly install and position the smoke detector
Important Precaution:
Do not install the actual smoke/heat alarm itself in new or renovated buildings until all work is completed (including floor coverings) and the building has been fully cleaned. (Excessive dust and debris from building work can contaminate the smoke chamber and cause problems, and it will also invalidate the guarantee). If it must be installed, cover it completely, particularly around the edges, with a dust cover (eg. a plastic bag), until all cleaning is finished..
Technical Specification
Sensor Ionisation, uses electrically
charged ions that will react
to smoke particles
Sensitivity: Complies with BS 5446 Part 1:
2000
Source: Americium 241
Airspeed: Essentially immune to the effect
of airspeed.
Button Test: Simulates the effect of smoke and
checks chamber, electronics and horn.
Supply Voltage: 10.2 to 14 volts
Alarm: Piezoelectric-horn
in unit
Alarm Sound Output: 85dB (minimum) at 3m
Temperature Range: 0 to 40°C
Humidity Range: 0% to 90% Relative Humidity
Fixing: Screw fixings supplied
Plastic material: UL94HB flame retardant Dimensions: 140x120x45 mm Weight: 150 gram Warranty: 5 year (limited) warranty Approvals: Kitemarked to BS5446-1:2000, CE
Approved
Specifications are subject to change
E & OE As our policy is one of continuous product development, we reserve the right to alter product details without prior notice. Ei100R DataSht RevA