Eibmarkt EIB/KNX User Manual

© 1997 – 2010 EIBMARKT GmbH
EIB/KNX IP Router
mit Power over Ethernet (PoE)
IP-Router / Interface between LAN and EIB/KNX bus
Page 1
© 1997 – 2010 EIBMARKT GmbH
Application
The KNX IP Router forwards telegrams between different lines via a rapid LAN (IP) backbone. The KNX IP Router can also be used as an interface for accessing the bus via IP, replacing an RS232 or USB interface. It has an external 12 V to 24 V power supply or can alternatively be powered via Power-over-Ethernet (IEEE 802.3af).
The EIB/ KNX IP Router has a filter table and is able to buffer up to 150 telegrams.
Page 2
© 1997 – 2010 EIBMARKT GmbH
Note: The Power over Ethernet supply is standardized acc. to Standard PoE (IEEE
802.3af) and integrated via RJ45. We can recommend a PoE Ethernet Switch from Netgear, e.g. FS108P. The device disposes of 8 ports, four of which are equipped with Power over Ethernet (IEEE802.3af, 48 VDC). The IP router for example, can be connected to one of these four ports. As an alternative, power supply can be provided by means of screw connecting terminals at the upper side using a separate power supply unit (12-24V DC) or transformer (12-24V AC). Parallel power must be avoided!
Page 3
© 1997 – 2010 EIBMARKT GmbH
Technical data
Electrical safety
• Protection (EN 60529): IP 20
• Safety extra low voltage SELV DC 24 V
EMC requirements
• Complies with EN 61000-6-2, EN 61000-6-3 and EN 50090-2-2
Environmental requirements
• Ambient temp. operating: - 5 ... + 45 °C
• Ambient temp. Non-op.: - 25 ... + 70 °C
• Rel. humidity (non-condensing): 5 % … 93 %
Certification
• EIB/KNX
CE nor m
• Complies with the EMC regulations (residential and functional buildings) and low voltage directive
Physical specifications
• Housing: Plastic
• DIN rail mounted device, width: 36 mm
• Weight: approx. 100 g
• Fire load: approx. 1000 kJ
Operating controls
• Learning key for EIB/KNX
Indicators
• Learning-LED (red)
• Signal-LED (green) for EIB/KNX
• Signal-LED (green) for LAN
Ethernet
• 10BaseT (10Mbit/s)
• Supported internet protocols ARP, ICMP, IGMP, UDP/IP and DHCP
Power supply
• External supply 12-24V
• Alternative: Power-over-Ethernet
• Power consumption: < 800 mW
Connectors
• EIB/KNX connection terminal
• LAN RJ -45 socket
• Screw connector for power supply
Page 4
© 1997 – 2010 EIBMARKT GmbH
Operating and installation manual
Coupler function (KNXnet/IP routing)
The EIB/KNX IP Router can operate as a line and/or backbone coupler. In both cases, the LAN (IP) acts as a backbone.
KNX IP Router as a line coupler