EHC NDIR120L, NINDSL120L, NDIR150L, NDIR180L, NDIR210L Installation & Maintenance Instructions Manual

...
Installation & Maintenance
Instructions
MARCH 2017
The Electric Heating Company Ltd
Unit 40 Block 5 Third Road
Blantyre Industrial Estate
Blantyre Glasgow
Tel: 01698 820533
Fax: 01698 825697
email: info@electric-heatingcompany.co.uk
www.electric-heatingcompany.co.uk
01
EHC NEPTUNE UNVENTED HOT WATER CYLINDERS
PAGE CONTENT
1 Introduction 2 Storage, Handling & Supply Requirements
3 Component Table 4 Siting the unit 5 General Installation 7 Discharge Arrangement 9 Technical Specifications: Slimline - Direct & Indirect 10 Technical Specifications: Direct & Indirect 11 Technical Specifications: Solar Indirect 12 Solar Coil Installation 13 S-Plan Wiring Schematics 14 Commissioning & Servicing 15 Fault Finding & User Instructions 16 - 17 Specification & Performance 18 Commissioning Record 19-24 Service Record 25-26 Guarantee - Terms & Conditions 27 Gaurantee Card
INTRODUCTION
The EHC Neptune Unvented cylinder is made from Duplex Stainless Steel for excellent corrosion resistance. The EHC Neptune has a strong rust-resistant steel case and is highly insulated with environmentally friendly foam.
The EHC Neptune is supplied complete with all the necessary safety and control devices needed to connect to the cold water mains. All are pre-adjusted. High quality controls have been selected to combine high flow rate performance with minimum pressure drop to make the EHC Neptune perform well in all areas, even those with poor water pressure.
IMPORTANT NOTE TO THE INSTALLER
Read these instructions before commencing installation. Unvented cylinders are a controlled service as defined in the latest edition of the building regulations and should only be fitted by a competent person.
The relevant regulations are: England and Wales – Building Regulation G3, Scotland – Technical Standard P3, N Ireland – Building Regulation Part F After installation the commissioning record must be completed and left, with these instructions, with the householder for future reference.
IMPORTANT NOTE TO THE INSTALLER
Read these instructions before commencing installation. Unvented cylinders are a controlled
service as defined in the latest edition of the building regulations and should only be fitted
by a competent person.
The relevant regulations are: England and Wales – Building Regulation G3, Scotland – Technical
Standard P3, N Ireland – Building Regulation Part F
After installation the commissioning record list must be completed and left, with these
instructions, with the householder for future reference.
02
EHC NEPTUNE
UNVENTED HOT WATER CYLINDERS
STORAGE PRIOR TO INSTALLATION
The EHC Neptune should be stored in its original packaging in an upright position in an area free from excessive damp. Regulations G3+L.
HANDLING PRODUCT
The EHC Neptune should be carried upright where possible. Assessments of risks for carrying the cylinder should be conducted. Use more than 1 person for carrying where appropriate. Always follow latest guidelines for lifting techniques, to avoid injury and damage to the product.
WATER SUPPLY
The EHC Neptune operates at 3 bar (controlled by the inlet control set) and is capable of delivering over 50 litres per minute. The high quality inlet control set has been designed to make the most of the flow rates available, however the performance of any unvented system is only as good as the mains water supply. The maximum possible water demand should be assessed, taking into consideration that both hot and cold services are supplied simultaneously from the mains.
The water supply should be checked to ensure it can meet these requirements. If necessary, consult the local water company regarding the likely pressure and flow rate availability.
If measuring the water pressure, note that a high static (no flow) mains pressure is no guarantee of good flow availability. In a domestic installation 1.5 bar and 25 l/min. should be regarded as the minimum. The maximum mains pressure that the inlet control set can accept is 12 bar.
Consideration should be given to upgrading existing ½” (15mm) cold mains pipework to a larger size if the recommended minimum pressure/flow rate is not being achieved.
ELECTRIC SUPPLY
The EHC Neptune requires 240 Volt electrical supply for the immersion elements. The electrical supply to each immersion heater must be fused at 13A via a double pole isolating switch to BS 3456. The cable must be at least
2.5mm2 heat resistant (85°C HOFR) sheathed flex complying to BS 6141:1981 Table 8.
UNPACKING THE UNIT
The EHC Neptune comes complete with the fittings required to complete the installation. Please see over for component content list.
High flow rate inlet control set - 3 bar PRV 6 bar Expansion Relief Spare Part No. CB091
Temperature and pressure relief valve Spare Part No. CB098
Acetal tundish 15 x 22 mm Spare Part No. CB096
Incoloy long life 3 kW immersion heater Spare Part No. CB099
Two port valve Spare Part No. EC10008
Dual thermostat Spare Part No. CB142
High limit thermostat Spare Part No. CB135
Expansion Vessel
• 60- 250 ltr units - 18 ltr vessel Spare Part No. CB144
• 300 ltr units - 25 ltr vessel Spare Part No. CB145
COMPONENT CONTENT TABLE
Inlet Control Set
Temp & Pressure Relief Valve
Tundish
Expansion Vessel
Immersion Heater
Two Port Valve
Dual Thermostat
Single High Limit Stat
Sensor Pocket Retaining Bungs
Installation & Maintenance
Instructions
Slimline Direct Models (Electric)
Slimline Indirect Models
Direct Models (Electric)
Indirect Models
Solar Indirect Models
Direct Models (Electric) Indire ct Mod els (Single Coil ) Solar I ndirec t Models (Two Coils)
03
EHC NEPTUNE UNVENTED HOT WATER CYLINDERS
SITING THE UNIT
The EHC Neptune can supply outlets above it or at some distance from it. Site the unit to minimise “dead leg” distances, especially to the point of most frequent use.
Outlets above the EHC Neptune will reduce the outlet pressure available by 0.1 bar for every 1m of height difference. The unit should be protected from frost. Particular care is needed if sitting in a garage or outbuilding. All exposed pipework should be insulated. EHC Neptune must be installed VERTICALLY on a flat base capable of supporting the weight of the cylinder when full. See technical specification section (page 16) for weights. The minimum recommended cupboard size is 650mm square.
NOTES:
The pressure reducing valve, non-return valve and expansion relief valve are combined together in the inlet control set.
On 60 – 180 litre sizes there is no dedicated secondary return boss and the secondary return circuit should be tee’d into the cold feed pipe just above the drain elbow.
SCHEMATIC DIAGRAM
Access for maintenance of the valves should be considered. Consideration should be given to position of discharge pipes (tundish), drain valves - shall be positioned away from electrical components.
The immersion heaters are 375mm long and care should be taken to ensure that they can be withdrawn for servicing if required. The discharge pipework from the safety valves should fall continuously and terminate safely.
IMMERSION
HEATER
COLD
MAIN ISOLATING VALV E
PRESSURE REDUCING VALV E
NON
RETURN
VALV E
EXPANSION RELIEF VALV E
TUNDISH
TEMPERATURE & PRESSURE RELIEF VALVE
BALANCED COLD CONNECTION
COLD INLET VIA DRAIN
NON RETURN VALV E
BRONZE PUMP
SECONDARY RETURN CIRCUIT ( 210, 250 & 300 L SIZES )
DUAL STAT
2 PORT
VALV E
BOILER FLOW
BOILER RETURN
HOT OUTLET
EXPANSION VESSEL WITH WALL BRACKET
04
EHC NEPTUNE
UNVENTED HOT WATER CYLINDERS
GENERAL INSTALLATION
COLD MAINS PIPEWORK
Run the cold main through the building to the place where the EHC Neptune is to be installed. Take care not to run the cold pipe near hot water or heating pipework so that the heat pick-up is minimized. Identify the cold water supply pipe and fit an isolating valve (not supplied).
A 22mm BS1010 stopcock can typically be used but a 22mm quarter turn full bore valve would be better as it does not restrict the flow as much. Do not use “screwdriver slot” or similar valves. Make the connection to the cold feed of the cylinder and incorporate a drain valve. Position the drain valve no higher than the cold inlet to ensure sufficient draining of cylinder when required. Position the inlet control just ABOVE the Temperature & Pressure Relief Valve (TPRV) mounted on the side of the cylinder. This ensures that the cylinder does not have to be drained down in order to service the inlet control set. Ensure that the arrow points in the direction of the water flow. Select a suitable position for the expansion vessel. Mount it to the wall using the bracket attached to the vessel. Use suitable fittings capable of supporting full vessel weight (and with appropriate consideration to wall material). Connect the expansion vessel to the cold feed pipework between the inlet control set and the cold inlet on the cylinder. Ensure that the top of the vessel is accessible for servicing.
CONNECTING TO THE CYLINDER
All of the pipework connections on the cylinder are 22mm compression and supplied complete with gland nuts and olives, in the Accessory Kit box. Only connect 22mm Table X copper tube to these connections.
Cut the tube with a pipe cutter and ensure no sharp edges or burrs protrude. Slide both gland nut and olive onto the tube and push tube fully home into the connection, ensuring the tube end fully bottoms on the connection recess. Smear the outer wall of the olive with plumbing paste and tighten gland nut in the prescribed manner. Upon filling/commissioning, ensure all connections are completely watertight. Note: No control or isolation valve should be fitted between the expansion relief valve and the storage cylinder. The relief valve connections should not be used for any other purpose.
(expansion vessel not to scale)
Turn to test
Cold
Mains In
Balanced Cold Connection
Outlet to Cylinder
Expansion Relief to Tundish
Expansion Relief Connection
05
EHC NEPTUNE UNVENTED HOT WATER CYLINDERS
BALANCED COLD CONNECTION
If there are to be showers, bidets or monobloc taps in the installation then a balanced cold supply is necessary. There is a 22mm balanced connection on the inlet set.
HOT WATER PIPEWORK
Run the first part of the hot water distribution pipework in 22mm. This can be reduced to 15mm and 10mm as appropriate for the type of tap etc. Your aim should be to reduce the volume of the hot draw-off pipework to a practical minimum so that the time taken for the hot water is as quick as possible. Where monobloc mixing taps and showers are used, these should be installed to comply with the Water Supply (Water Fittings) Regulations 1999. If these devices are supplied with un-balanced supplies there should be single check valves installed at both inlets, to stop over pressurising of either supply.
PRIMARY COIL CONNECTIONS FOR INDIRECT UNITS For Solar input models refer to pages 11-12 before making any connections.
Connect the primary connections (Indirect only) using the compression connections provided. The primary circuit must be positively pumped. Gravity circulation is not suitable. Either primary connection may be used as the primary flow, reheat times are not effected. The primary circuit can be open vented or sealed, with up to a maximum pressure of 3.5 bar. If you seal the primary circuit an additional expansion vessel and safety valve is required. The boiler may be Gas, Electric or Oil but must be under effective thermostatic control. Uncontrolled heat sources such as some AGA’s, back boilers, solid fuel stoves, etc. are NOT SUITABLE. Please contact our Technical department for guidance. Connect the two port zone valve ( indirect only ) into the primary flow pipework. The direction of flow arrow should be towards the primary flow connection.
SECONDARY CIRCULATION
The EHC Neptune can be used with secondary circulation. An appropriate WRAS approved bronze circulator should be used in conjunction with a non-return valve to prevent backflow. On large secondary circulation systems it may be necessary to incorporate an extra expansion vessel into the circuit to accommodate the increased system water volume. Secondary circulation should be avoided on Direct electrically heated units being used on off-peak electricity tariffs. A secondary return boss is fitted as standard on 210, 250 & 300 ltr units. On smaller sizes, tee into the cold feed pipe above the drain.
IMMERSION HEATERS
Only immersion heaters with a thermal cut-out may be used. To help ensure this, the immersion heaters have a special 1 3/4” thread. They are rated at 3kW at 240V and are of a low noise Incoloy construction. They have both a thermostat and a high limit cutout. Please order the correct replacement via ourselves; fitting non­approved immersions may affect your guarantee. When fitting, ensure the ‘O’ ring is positioned correctly on the head of the immersion heater and lubricate before fitting. Fit it by hand until almost home then tighten gently as the ‘O’ rings will seal easily. The electrical supply to each immersion heater must be fused at 13A via a double pole isolating switch to BS 3456. The cable must be 2.5mm2 heat resistant (85°C HOFR) sheathed flex complying to BS 6141:1981 Table
8. Do not operate the immersion heater/s until the unit is full of water. Do not operate the immersion heater/s if any sterilisation liquid is in the cylinder as this will cause premature failure.
ELECTRICAL CONNECTIONS
Complete the wiring – use the appropriate wiring diagrams on page 12- 13.
06
EHC NEPTUNE
UNVENTED HOT WATER CYLINDERS
DISCHARGE ARRANGEMENT
Position the inlet control group so that the discharge from both safety valves can be joined together via a 15mm end feed Tee (see diagram above). Connect the Tundish and route the discharge pipe. The discharge pipework must be routed in accordance with Part G3 of schedule 1 of the Building Regulations. The information that follows is not exhaustive and if you are in doubt you should seek advice. The two safety valves will only discharge water under fault conditions. When operating normally water will not be discharged. The tundish should be vertical, located in the same space as the unvented hot water storage system and
be fitted as close as possible to, and lower than, the safety device, with no more than 600mm of pipe between the valve outlet and the tundish. The tundish should be positioned away from electrical devices. Any Discharge should be visible at the tundish. The tundish should be located such that any discharge is visible. In addition, where discharges from safety devices may not be apparent, e.g. people with impaired vision or mobility, consideration should be given to the installation of a suitable safety device to warn when discharge takes place, e.g. electronically operated.
Diagram of a typical discharge pipe arrangement (extract from Building Regulation G3)
Note: The discharge will consist of scalding water and steam. Asphalt, roofing felt and non-metallic rainwater goods may be damaged by such discharges.
Note: D2 pipe from tundish is now allowed to be installed in soil stacks within premises. This activity is not recommended as discharge from T&P may continue for long periods of time. It is the installer’s responsibility to ensure the discharge pipework can support the discharge for prolonged periods. If used follow guidance on mechanical seal without water trap given in G3 Building Regulations. As discharge can be in excess of 90oC discharge into plastic pipework is also not recommended.
07
EHC NEPTUNE UNVENTED HOT WATER CYLINDERS
The discharge pipe (D2) from the tundish should:
A) Have a vertical section of pipe at least 300mm long, below the tundish before any elbows or bends in the pipework.
B) Be installed with a continuous fall of at least 1 in 200 thereafter.
The discharge pipe (D2) from the tundish should be of metal or other material that have been demonstrated to be capable of withstanding temperatures of the water discharged.
The discharge pipe (D2) should be at least one pipe size larger than the nominal outlet size of the safety device unless its total equivalent hydraulic resistance exceeds that of a straight pipe 9m long i.e. discharge pipes between 9m and 18m equivalent resistance length should be at least two sizes larger than the nominal outlet size of the safety device, between 18 and 27m at least 3 sizes larger, and so on. Bends must be taken into account in calculating the flow resistance. Refer to diagram 1, Table 1 and the worked example. An alternative approach for sizing discharge pipes would be to follow BS670 ce of services supplying water for domestic use within buildings and their curtilages.
The discharge pipe (D2) should terminate in a safe place where there is no risk to persons in the vicinity of the discharge. Examples of acceptable discharge arrangements are:
a. To a trapped gully with the end of the pipe below the fixed grating and above the water seal.
b. Downward discharges at a low level; i.e. up to 100mm above external surfaces such as car parks, hard standings, grassed areas etc. are acceptable providing that where children play or otherwise come into contact with discharges, a wire cage or similar guard is positioned to prevent contact whilst maintaining visibility. c. Discharges at a high level; e.g. in to metal hopper and metal down pipe with the end of the discharge pipe clearly visible or onto a roof capable of withstanding high temperature discharges of water and 3m from any plastic guttering systems that would collect such discharges. d. Device to warn when discharge takes place.
WORKED EXAMPLE
The example below is for G1/2 temperature relief valve with a discharge pipe (D2) having 4 No. elbows and length of 7m from the tundish to the point of discharge. From Table 1: Maximum resistance allowed for a straight length of 22mm copper discharge pipe (D2) from a G1/2 temperature relief valve is: 9.0m. Subtract the resistance for 4 No. 22mm elbows at 0.8m each = 3.2m. Therefore the maximum permitted length equates to: 5.8m. 5.8m is less than the actual length of 7m therefore calculate the next largest size. Maximum resistance allowed for a straight length of 28mm pipe (D2) from a G1/2 temperature relief valve equates to: 14m. As the actual length is 7m, a 28mm (D2) copper pipe will be satisfactory.
TAB L E 1
Sizing of copper discharge pipe ‘D2’ for a temperature relief valve with a G1/2 outlet size (as supplied).
Size of discharge pipework
Maximum length of straight pipe (no bends or elbows)
Deduct the figure below from the maximum length for each bend or elbow in the discharge pipe
22mm Up to 9m 0.8m
28mm Up to 18m 1m
35mm Up to 27m 1.4m
08
EHC NEPTUNE
UNVENTED HOT WATER CYLINDERS
Loading...
+ 19 hidden pages