EHC Fusion Installation & Technical Manual

The FUSION Range of Boilers
INSTALLATION
&
TECHNICAL MANUAL
If you require any further assistance:
Telephone: 01698 820533
Fax: 01698 825697
E-mail: info@electric-heatingcompany.co.uk
Or visit our website
www.electric-heatingcompany.co.uk
2
GB-016C_f.493
INTRODUCTION
Please read and follow the installation and operating instructions carefully, to ensure the long life and reliable operation of this appliance.
The Electric Heating Company may make minor changes if necessary in the appliance that will not be shown in the operating instructions, so long as the main features of the boiler remain the same.
All boilers come with a 24 month warranty that covers all defects originating from faulty materials and workmanship in the manufacture of the boilers.
The warranty covers the replacement of any faulty parts and labour costs.
The warranty will not cover any damage to the boiler from poor or incorrect installation work.
The warranty will not cover any call out charges that are a user or external control fault.
The warranty will not cover water leaks into the boiler. All plumbing joints must be checked.
The warranty card should be completed and sent back to The Electric Heating Company as soon as possible for registration.
A magnetic filter must be fitted to the system in the horizontal position.
This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental
capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning
use of the appliance by a person responsible for their safety.
Children should be supervised to ensure that they do not play with the appliance.
Page Contents
INTRODUCTION 2 PREPARATION 3 INSTALLATION 4 ELECTRICAL CONNECTIONS AND CONTROLS 7 EXTERNAL CONTROL WIRING 8 INTERNAL BOILER WIRING 9 EXTERNAL BOILER WIRING 10 BOILER DIMENSIONS 10 USER INSTRUCTIONS 11 FAULT FINDING 13 TECHNICAL SPECIFICATIONS 14
3
GB-016C_f.493
PREPARATION
Instructions and Building Regulations
This appliance must be fitted in accordance with the following instructions.
The Local Building Regulations.
The Building Regulations.
The Building Standards, (Scotland-consolidated) Regulations.
Local water bylaws.
British Standards- code of practice.
BS 5449, 1990, forced circulating hot water systems.
BS 7671, IEE wiring regulations.
BS 4814, 1990, Specification for expansion vessels (sealed sys­tems only)
C.O.S.H.H.
Materials used in the manufacture of this appliance are non-haz­ardous and no special precautions are required when fitting or servicing this appliance.
PREPARATION
1. Load Check
A load check should be taken into consideration when installing high output boilers.
2. Boiler location
The boiler must be fitted on a wall that will provide an adequate fixing, and should be fitted in a location that the boiler and pipe­work are not subject to frost and damp conditions.
3. Central heating
Detailed recommendations are given in BS 5449, BS 6700 and CP 342, Part 2.
Pipes forming part of the useful heating surface should be in­sulated to prevent any potential heat loss or frost damage. (BS 6700:1997).
Drain valves should be fitted at the lowest point of the system pipe work in an accessible position.
Drain valves should be in accordance with BS 2879 and copper tube to BS 2871. Part 1 is recommended.
LOCATION
The boiler can be installed in almost any location within a do­mestic or commercial property, however consideration should be given to future maintenance. Never leave the boiler switched off if there is danger of having temperatures below 0°C in the room where it is located.
MOUNTING THE BOILER
Mount the boiler onto a flat wall surface that will be capable of taking the boilers full weight. Use the mounting template provid­ed with the boiler, mark and drill the fixing holes taking into con­sideration you leave the minimum clearances required around the fusion boilers.
We recommend that a minimum clearance of 450 mm should be allocated for the removal of the front cover and adequate access to the boiler plumbing and the internal electrical connections. A 50 mm allowance should be made at either side of the boiler to allow free flow air into the boiler case and allow access to screws on the boiler case (150 mm for Slimline model).
THE BOILER MUST BE INSTALLED IN THE UPRIGHT POSITION, FAILURE TO DO SO WILL INVALIDATE THE WARRANTY.
4
GB-016C_f.493
INSTALLATION
The boiler must be installed by a professional plumber or heat­ing engineer and must be connected to the power supply by a qualified electrician.
The Electric Heating Company Ltd will not be held responsi­ble for faulty installations which are performed by unqualified tradespersons.
1. Pipe Connections
All Fusion Electric Boilers have a 22 mm compression connection at the boiler’s flow and return pipes. Please note that the boilers are supplied with blank washers fitted for transit purposes. These must be removed and replaced with the washers supplied. The 2 spare pcb fuses supplied must be left inside the boiler.
The flow (red) and return (blue) are clearly marked on the exter­nal case and under no circumstances should these connections be reversed.
Hot connections are not recommended at the boiler for future maintenance and boiler disconnection. Lockshield valves are recommended
2. Case Removal
Remove outer screws from boiler case and push upwards and outwards taking care to remove internal earth connections. (Slim­line model: remove screws on the right hand side and swing the boiler case open). Earth connections must be re-connected before the case is re­instated.
3. Isolation valves
Consideration should be made for the provision of lockshield iso­lation valves on the flow and return pipe-work. Such valves must be full way and not ball valves.
We recommend isolation valves on each side of the magnetic filter.
The insertion of ball valves will reduce the recommended flow through the boiler and promote premature boiler shut down caused by poor flow rate.
4. Auto air vents
An Auto air vent is integral within the boiler however an addi­tional auto air vent must be fitted at the cylinder coil if the boiler is being used for central heating and domestic hot water.
5. Boiler Sizing
Calculate the space heating requirements in accordance with BS
5449. If the boiler is to heat the domestic hot water, an allowance of 3kw (10,239 Btu’s ) should be made.
6. Insulation
Where practical and if at all possible, we recommend that all pipe-work be insulated, in particular the primary pipe-work with­in the boiler cupboard. This is to reduce heat loss and reduce high cupboard temperatures from exposed pipe-work. (BS 6700).
7. System Design
As the boilers are of a low water content an open circuit must be achieved incorporating 2 metres of continuous 22 mm pipe-work after boiler connections and before any zone valves.
We recommend the use of an automatic bypass within this circuit and set to the relevant settings to allow the minimum flow rates to pass through the boiler (8 l per min) when all radiator thermostats close. Allowance should be made for a minimum size radiator of 600mm x 600mm single convector or equal to 2500 Btu to be installed within the heating circuit and locked open. This will be located in the room that has the room stat installed.
To comply with building regulations, Part L and Part J (in Scot­land) room and cylinder stats must be fitted.
Note: We do not recommend the use of 8 mm micro-bore pipe.
8. Water connections
Provisions must be made for the replacement of water lost from the heating system (sealed systems). Reference should be made to BS 6798, for the methods of filling and make up of water.
There must be no direct connection between the boilers central heating system and the main water supply. When mains water is required to fill the system directly, all Local water bylaws must be observed. Any connection made must be disconnected after use.
9. Flushing
The system must be flushed to ensure that no debris is trapped in the flow sensor as this may result in boiler failure. Where existing radiators and pipe-work are utilised a power flush must be carried out to remove debris.
10. System pressures
All boilers are tested to 4.0 bar. The normal working pressure of the boilers should be set to 1.5 bar. All sealed systems should comply with the relevant building regulations and standards and to BS 4814, (Specification for Expansion Vessels).
Please Note In order to protect the Flow Sensor located within the boiler, it is imperative that you install a mechanical-magnetic filter on the return inlet to the boiler. This will enable you to clean the filter at regular intervals and will also ensure that the boiler does not become contaminated by system residue.
5
GB-016C_f.493
11. System types
The 6,9,12 & 14.4 kW boilers can be used in various system designs. Please refer to The Electric Heating Company for more details on our Fusion Boiler for under floor heating. We are able to supply a heat pack that contains the relevant control valves, cylinder and room thermostats required to configure an S plan heating system. The heat pack has all the necessary components that you need to connect the systems controls and plumbing con­figurations for S Plan design.
We also recommend the use of thermostatic radiator valves on all radiators except in the room that has the wall thermostat fitted. If a bypass radiator has been used in the system, it should be fitted with lock shield valves and left in the fully open position.
If a bypass radiator has not been used then a system bypass of 2 metres of 22 mm copper pipe incorporating an automatic bypass valve must be used and can be set to 8l/min from the front control panel.
Systems should be designed to current building regulations.
12. System protection
Failure to protect the system will invalidate the manufacturer’s warranty.
After the system has been installed the cleansing and inhibiting procedure must be carried out as follows: -
Fill the system with cold mains water to the recommended pressure 1.5 bar and check for leaks, then drain the system thoroughly making sure all drain cocks are fully open and that the system is completely drained.
Add Fernox Heavy Duty restorer through the header tank or via filling loop at the recommended dose. One bottle must be used as a minimum per dwelling. If you are unsure of the correct dose rate, contact Fernox.
Re-fill the system and circulate the heavy-duty restorer prior to the boiler entering modulation mode, then commission the system as normal.
The cleansing agent must be in the system for a minimum 1 hour with the system at normal operating temperature. A longer period of time would be more beneficial to the cleansing process especially if excess flux was used.
Drain and flush the system thoroughly, then add the Fernox Protector (Copal MB1 or Superconcentrate). This will protect against the formation of scale, corrosion and microbiological growths. It is crucial however, that for the protector to work correctly, the system must be properly cleansed and flushed.
The label included within the Fernox Protector carton should be completed and attached adjacent to the boiler.
Note: motorised valves must be manually opened when flushing the system.
Note: If the system is to be drained for any reason, the Fernox Protector must be re-introduced to the system.
Any further information you may require regarding the protection and cleansing products, please contact: -
Fernox Technical Helpline on 0870 870 0362.
Fernox Method Statement for New Domestic Systems
Cleansing and inhibiting a new central heating installation using Fernox Heavy Duty Restorer and a Fernox Protector (Copal, MBI and Superconcentrate).
Procedure:
1. Fill the system with cold mains water to the recommended pressure and check for leaks, then drain the system thoroughly making sure all drain cocks are fully open and that the system is completely drained.
2. Add Fernox Heavy Duty Restorer through the header tank or via a Fernox injector at the recommended dose. One bottle must be used as a minimum per dwelling. If you are not sure of the dose rate, then contact Fernox.
3. Fill the system back up and circulate the Heavy Duty Restorer before the boiler is fired up. Then commission the system in the normal way. The cleansing agent must be in the system for a minimum of I hour with the system at normal operating temperature. A longer period of time would be more beneficial to the cleansing process especially if excess flux was used.
4. Drain and flush the system thoroughly to remove the cleaning chemical and debris present. This is a crucial part of the cleans­ing process and must be done correctly. Use a rinse test meter (TDS), such as the Fernox CTM. The reading must be within 10% of the mains ppm value.
5. Once the system has been cleansed thoroughly, then add a Fernox Protector (Copal, MB1 or Superconcentrate), to the system. The product must be added as per the manufacturer’s instructions. This will protect against the formation of scale, cor­rosion and microbiological growths. lt is crucial, however, that for a protector to work correctly, the system must be properly cleansed and flushed.
6. The sticker included within the Fernox Protector carton should be correctly filled in and attached adjacent to the boiler.
7. Please note: we recommend inhibitor levels are checked on an annual basis (usually during the service) or sooner if the system content is lost. This should be carried out using a Fernox inhibitor test kit.
8. Fernox Technical Services can be contacted on 0870 8700362 for further assistance.
NB: Motorised valves should be manually opened during the flushing process and any anti-gravity valves should be by-passed or removed temporarily.
If it is necessary to cap off the open vent during the mains flush to prevent overflow ensure the cap is removed prior to starting the appliance.
Advice as contained within BS 7593:1992 and PAS33:1999 should be followed in conjunction with this method statement.
Failure to protect systems will void manufacturers warranty.
Water Loss
If water loss occurs due to natural evaporation, leakage or any other breakdown in water seals, the boiler will not operate.
The boilers flow sensor needs a minimum of 4 litres per minute to operate. If this cannot be achieved the boiler will shut down.
We recommend setting to 8l/min.
Investigation
Should BOIL OVER/ BOIL DRY /WATER LOSS occur, investigation as to why the system has failed MUST take place. Power should only be reinstated after the fault has been rectified.
The main overheat stat on the boiler can be re-set, this is positioned at the top of the boiler market WT3. To re-set, push the brass pin with a small screwdriver. The pin will click into place when re-set.
ENSURE THAT THE MAINS POWER SUPPLY TO THE BOILER IS SWITCHED OFF PRIOR TO RE-SETTING.
Loading...
+ 11 hidden pages