2 INSTALLATION EG30xx Owner’s Manual
2.2 Materials required for installation
• Per phase: 1× 15A circuit breaker or single multi-pole breaker
• Black, red, and white stranded AWG14 wire; length depending on installa-
tion location. Blue wire is needed in addition for 3-phase installations.
• Electrical tape
• Conduit and couplings as needed
• If required, appropriately rated external NEMA enclosure
2.3 Tools required for installation
• #0 slotted screw driver (needed if length of CT-wires needs to be adjusted)
• Circuit-breaker finder (ring-out tool)
• Voltage meter
Additionally, for device commissioning and installation verification:
• Clamp-on AC current meter
• Laptop with Ethernet cable
2.4 Nomenclature and Symbols
In the US, residences typically receive power through split-phase power distribution which is provided through two hot legs, a neutral, and a protective ground.
Most commercial and industrial buildings receive power through 3-phase power
distribution provided through 3 hot phases, a neutral and protective ground.
Throughout the rest of this document, we use the term “phase” to refer both to the
phases of 3-phase power distribution as well as the two legs used in split-phase
power distribution.
The following table describes the symbols used on the device:
3 November 3, 2016