The eFlow3NV power supply/chargers convert a 220VAC (working range 198VAC - 256VAC), 50/60Hz input to a
12VDC or 24VDC nominal output (see Power Supply Configuration Reference Chart and Specifications).
eFlow3NV Series Power Supply Configuration Reference Chart:
Nominal DC Outputs
[DC][AUX]
Altronix
Model Number
eFlow3NV
eFlow3NXV–––
12VDC Output
Range (V)
10.13-
13.2
20.28-
26.39
24VDC Output
Range (V)
12VDC Output
Range (V)
10.15-
13.2
20.2-
26.39
Maximum Supply
Current for Main and
24VDC Output
Range (V)
Aux. Outputs (A)
2A2.1A 5A/250V3A/32V960N/A1
Input Rating:
220VAC 50/60Hz
Input Fuse Rating
Battery Fuse Rating
Ripple Voltage (mV)
Under low battery condition
Power Distribution
Modiule
Number of Outputs
Fused Output Ratings
Auto-Resettable
PTC Output Ratings
––
P
Accommodates up to
7AH Batteries
Accommodates up to
12AH Batteries
–
P
eFlow3N4V
eFlow3NX4V2A––
eFlow3N4DV
eFlow3NX4DV–2A–
10.13-
13.2
9.78-
13.2
20.28-
26.39
20.0-
26.39
10.15-
13.2
10.15-
13.2
20.2-
26.39
20.2-
26.39
2A2.1A 5A/250V3A/32V960PD44
2A2.1A 5A/250V3A/32V960PD4CB4
2A–
–2A
P
–
P
P
–
P
These units are suitable to power sensors, electro-mechanical devices (e.g. electric door strikes) defined in the National Electrical Code/
NFPA70/NFPA72 and the Canadian Electrical Code, Part 1.
• Low power shutdown. Shuts down DC output terminals
if battery voltage drops below 71-73% for 12V units
and 70-75% for 24V units (depending on the power
supply). Prevents deep battery discharge.
Fuse Ratings:
• Refer to eFlow3NV Series Power Supply Configuration
Reference Chart, pg. 2.
Visual Indicators:
• Green AC Power LED indicates 220VAC present.
• AC input and DC output LED indicators.
Additional Features:
• Short circuit and overload protection.
• Unit is complete with power supply, enclosure,
battery leads and cam lock.
Enclosure Dimensions (approximate H x W x D):
eFlow3NV, eFlow3N4V, eFlow3N4DV:
13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.55mm)
eFlow3NXV, eFlow3NX4V, eFlow3NX4DV:
15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm)
Installation Instructions:
Wiring methods should be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, The Canadian
Electrical Code, Part 1 and with all local codes and authorities having jurisdiction. The product must be located indoors
within the protected premises.
1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the
enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s
upper keyholes over the two upper screws, level and secure. Mark the position of the lower two holes. Remove the
enclosure. Drill the lower holes and install the two fasteners. Place the enclosure’s upper keyholes over the two
upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pgs. 11-12).
Secure enclosure to earth ground.
2. Set desired DC output voltage by setting SW1 to the appropriate position on the power supply board (Fig. 1i, pg. 5).
3. Connect unswitched AC power (220VAC 50/60Hz) to the terminals marked [L, N] (Fig. 1a, pg. 5). Use 14 AWG or
larger for all power connections. Secure green wire lead to the ground lug. Keep power-limited wiring separate from
non power-limited wiring (220VAC 50/60Hz Input, Battery Wires). Minimum 0.25” spacing must be provided.
For Fire Alarm applications the outputs are “Special Applications” only, see list (refer to Appendix A, pg. 12).
Keep power-limited wiring separate from non power-limited wiring (220VAC 50/60Hz Input, Battery Wires).
Minimum 0.25” spacing must be provided.
CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment.
There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel.
4. Measure output voltage before connecting devices. This helps avoiding potential damage.
5. Connect devices to be powered:
a. For eFlow3NV/eFlow3NXV: connect devices to the terminals marked [- DC +] (Fig. 1h, pg. 3).
b. For other Power Distribution Models: connect devices to be powered to the terminal pairs 1 to 4 marked
[1P & 1N] through [4P & 4N] (Fig. 3a & 3b, pg. 6) carefully observing correct polarity.
For auxiliary device connection: this output will not be affected by Low Power Disconnect or Fire Alarm Interface.
Connect device to the terminals marked [+ AUX -- ] (Fig. 1f, pg. 5).
6. For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result in the loss
of the output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel type.
Connect battery to terminals marked [-- BAT + ] (Fig. 1g, pg. 5). Use two (2) 12VDC batteries connected in series for
24VDC operation (battery leads included). Use batteries - Casil CL1270 (12V/7AH), CL12120 (12V/12AH),
CL12400 (12V/40AH), CL12650 (12V/65AH) batteries BAZR2 batteries of an appropriate rating.
7. Connect appropriate signaling notification devices to AC FAIL & BAT FAIL (Fig. 1b, pg. 5) supervisory
relay outputs.
8. To delay AC reporting for 2 hrs. set dip switch [AC Delay] to the OFF position (Fig. 1c, pg. 5).
To delay AC reporting for 1 min. set dip switch [AC Delay] to the ON position (Fig. 1c, pg. 5).
Note: Must be set to the ON position for Burglar Alarm Applications.
9. To enable Fire Alarm Disconnect set dip switch [Shutdown] to ON position (Fig. 1c, pg. 5).
To disable Fire Alarm Disconnect set dip switch [Shutdown] to OFF position (Fig. 1c, pg. 5).
10. Trigger terminals are end of a line resistor supervised (10k ohms). Opening or shorting trigger terminals will cause [DC] output to shutdown (Fig. 1d, pg. 5).
11. Place a jumper for non-latching FACP. A momentary short on these terminals resets FACP latching
[Trigger EOL Shutdown] (Fig. 1e, pg. 5).
12. For Access Control Applications: mount tamper switch (Sentrol model 3012 or equivalent) at the top of the enclosure.
Slide tamper switch bracket onto the edge or the enclosure approx. 2” from the right side (Fig. 4, pg. 7 or Fig. 6, pg. 9).
Connect tamper switch wiring to the Access Control Panel input or the appropriate reporting device.
Use 18 AWG or larger for all low voltage power connections.
Note: Take care to keep power-limited circuits separate from non power-limited wiring (220VAC, Battery).
Unit should be tested at least once a year for the proper operation as follows:
Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper voltage level
eFlow3NV: 12VDC or 24VDC nominal rated @ 2A max.
Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage
(12VDC @ 13.2 or 24VDC @ 26.4) both at the battery terminal and at the board terminals marked [-- BAT + ] to ensure
that there is no break in the battery connection wires.
Note: Maximum charging current under discharges is 1.54A.
Note: Expected battery life is 5 years, however it is recommended changing batteries in 4 years or less if needed.
eFlow3NV Series - 3 -
Wiring:
Maintenance:
LED Diagnostics:
Power Supply/Charger
Red (DC)Green (AC/AC1)Power Supply Status
ONONNormal operating condition.
ONOFFLoss of AC. Stand-by battery supplying power.
OFFONNo DC output.
OFFOFFLoss of AC. Discharged or no stand-by battery. No DC output.
Power Distribution Module
Green (AC)Power Distribution Module Status
ONNormal operating condition.
OFFNo Power Output.
Terminal Identification:
Power Supply/Charger
Terminal
Legend
L, NConnect 220VAC 50/60Hz to these terminals: L to hot, N to neutral (non power-limited) (Fig. 1a, pg.5).
– DC +12VDC or 24VDC nominal @ 2A continuous output (power-limited output) (Fig. 1h, pg. 5).
Trigger EOL
Supervised
NO, GND
RESET
+ AUX – Auxiliary Power-Limited output rated @ 1A (unswitched) (power-limited output) (Fig. 1f, pg. 5).
AC Fail
NC, C, NO
Bat Fail
NC, C, NO
– BAT +Stand-by battery connections. Maximum charge current 1.54A (non power-limited) (Fig. 1g, pg. 5).
Function/Description
Fire Alarm Interface trigger input from a short or FACP. Trigger inputs can be normally open,
normally closed from an FACP output circuit (power-limited input) (Fig. 1d, pg. 5).
FACP interface latching or non-latching (power-limited) (Fig. 1e, pg. 5).
Indicates loss of AC power, e.g. connect to audible device or alarm panel. Relay normally energized
when AC power is present. Contact rating 1A @ 30VDC (power-limited) (Fig. 1b, pg. 5).
Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized when DC power
is present. Contact rating 1A @ 30VDC. A removed battery is reported within 5 minutes.
Battery reconnection is reported within 1 minute (power-limited) (Fig. 1b, pg. 5).
Power Distribution Module
Terminal Legend
PD4/PD4CB
1P to 4PPositive DC power outputs.
1N to 4NNegative DC power outputs.
Function/Description
- 4 - eFlow3NV Series
Fig. 1 - eFlow3NV Board configuration
OFF --- 24V
ON
1i
ON --- 12V
1h
--- DC +
3A
1g
--- BAT +
5A 250V
5A 250V
AC1
LG N
NC C NO NC C NO
1a1b
AC FAIL
BAT FAIL
AC
AC DELAY SHUTDOWN
O
N
DC
1 min.
2 hr.
enable
disable
3A 32V
TRIGGER EOL
SUPERVISED
NO GND
RESET
1e1f1d1c
+ AUX –
Trouble/Time Limited Warning of Stand-by Batteries:
The Time Limited Warning circuit must be connected for local or remote annunciation with an Amber or Red LED to indicate DC Trouble (low battery, loss of battery or when 95% of the stand-by battery has been depleted). Connect the circuit
to the Batt Fail relay contacts to an appropriate input of a Burglar Alarm or Access Control Panel. The following figure
shows the circuitry needed for local annunciation.
Fig. 2 - Battery trouble indication -
Wire one leg of a power source to the indicating lamp. Wire the second leg of the power source to the indicating lamp in
series with the battery fail relay contact terminals marked [BAT FAIL - C, NO] (Fig. 2, pg. 5).
BAT FAILAC FAIL
eFlow3NV Series - 5 -
POWER
SOURCE
NC C NO NC C NO
RED INDICATING
LAMP
Loading...
+ 11 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.