Effekta RMH 700, RMH 1000, RMH 1500 Instruction Manual

UPS
Uninterruptible Power Supply
RMH 700/1000/1500
Instruction Manual
Item number: R30 / 00700MH-000
R30 / 01000MH-000 R30 / 01500MH-000
Juli 2005
UPS RMH700/1000/1500 Instruction Manual
RMH Series
Page 2 of 37
Contents
1 Presentation 4 2 Warranty conditions 5
2.1 Limitation of liability 6
3 Safety 7
3.1 General safety instructions 7
3.2 Transportation and storage 7
3.3 Setup 7
3.4 Connection 8
3.5 Operation 8
3.6 Handling batteries 9
3.7 Maintenance, servicing and faults 9
4 Introduction 11 5 System description 12 6 RMH700/1000/1500 – description of equipment 14
6.1 Display and operator control elements on the front panel 14
6.1.1 UPS operator control elements 14
6.1.2 UPS display elements 15
6.2 Equipment elements on the rear panel 15
6.3 UPS audible alarm signals 15
7 Storage and unpacking 15
7.1 Storing the UPS 15
7.2 Unpacking the equipment 15
8 Installing and connecting the UPS 15
8.1 Connecting the UPS 15
8.2 UPS communications connection 15
8.3 Connection sequence 15
9 Running and operating the equipment 15
9.1 Operating the UPS equipment 15
9.1.1 Operating modes and signals 15
9.2 Instructions for using the UPS 15
9.2.1 Switching on and starting the UPS 15
9.2.2 Powering down and switching off the UPS 15
9.2.3 Activating the test operation 15
9.2.4 Communication 15
10 Starting up the UPS equipment 15
UPS RMH700/1000/1500 Instruction Manual
RMH Series
Page 3 of 37
11 Troubleshooting 15 12 Software 15 13 Maintenance and servicing 15
13.1 Measuring the bridging time (support time) 15
13.2 Replacing the batteries 15
13.3 Service log 15
13.4 Service hotline: 15
13.5 Maintenance and service contracts 15
14 Technical Data 15
14.1 Equipment specifications 15
14.2 Accessories 15
14.3 List of wearing parts 15
15 Requirements for the declaration of conformity 15
UPS RMH700/1000/1500 Instruction Manual
RMH Series
Page 4 of 37
1 Presentation
In this instruction manual, the abbreviation UPS stands for Uninterruptible Power Supply. The following icons are used in this instruction manual:
Denotes information which, if disregarded, poses a risk to health, functionality or safety.
Warning about the handling of batteries.
Warning about dangerous electrical voltage.
Denotes additional information and tips.
Recycling symbol.
Denotes components which are governed by the electronic scrap ordinance.
Denotes components or parts which are subject to mandatory special waste disposal. Never throw these components into the regular refuse.
Copyright © 2004 All rights reserved. This instruction manual is protected by copyright law. The copyright owner is EFFEKTA Regeltechnik GmbH.
Trademarks: All trademarks used are the property of their respective owners. EFFEKTA
®
is a registered trademark of EFFEKTA Regeltechnik GmbH.
We reserve the right to make technical and visual changes, and we are not liable for typographical errors.
UPS RMH700/1000/1500 Instruction Manual
RMH Series
Page 5 of 37
2 Warranty conditions
The delivery receipt is considered to be the initial proof of purchase and should be stored carefully. It is required for all warranty claims. If the product is transferred to another user, then the latter is entitled to claim under the warranty for the remainder of the warranty period. The purchase receipt, together with this declaration, should be transferred to the possession of the new owner.
We guarantee that this equipment is in a functional state and corresponds in technical terms to the descriptions in the enclosed documentation.
The warranty period for special equipment corresponds to the minimum period prescribed by legislation.
This warranty is not valid for the following cases:
o Defects due to: damage during transportation, accidents, natural
disasters, misuse, vandalism, inappropriate use, maintenance errors or incorrect repairs by third parties.
o Modifications, unauthorized tampering, incorrect operation, another
device or accessory, incorrect installation, or any modification not approved by us.
o Disregard for the instructions in the supplied documentation. o Incompatibility of the product as a result of technical innovations or
regulations which may come into effect after the purchase.
o Incompatibility or malfunction caused by product components not
installed by us.
o Signs associated with the normal ageing process of the product
(wearing parts).
o Defects caused by external appliances.
The warranty period for parts replaced and/or repaired within the scope of this warranty expires with the original warranty for the product.
Equipment sent in without accessories will be replaced without accessories. Equipment returned will only be accepted if it is returned in the original packaging.
Incidental transportation costs are generally excluded from the scope of services provided under the warranty.
UPS RMH700/1000/1500 Instruction Manual
RMH Series
Page 6 of 37
EFFEKTA GmbH does not give any express or implied warranties in relation to this equipment and its quality, performance, merchantability or suitability for a specific purpose. In some countries, the exclusion of implied warranties is not permitted by law. In this case, the validity of all express and implied warranties is restricted to the warranty period. When this period expires, all warranties cease to be valid. In some countries, a limitation of the validity period of implied warranties is not permitted by law, in which case the above restriction is not effective.
2.1 Limitation of liability
Compensation claims are excluded, unless they are based on the deliberate
acts or gross negligence of EFFEKTA GmbH or its employees. The liability according to the Product Liability Act remains unaffected. Under no circumstances will we be liable for:
o Claims for losses or damage made by third parties against you. o Loss or damage of your records or data or the cost of their recovery. o Financial consequential damage (including loss of earnings or savings)
or incidental damage, even in the event that we had been informed of the possibility of such damage.
Under no circumstances whatsoever will EFFEKTA GmbH be held responsible for any coincidental, indirect, special, consequential or other damage of any kind (including, without limitation, damage relating to loss of profit, discontinuation of business, loss of business information or any other loss) arising from use of the equipment or in any connection with the equipment, whether based on a contract, compensation, negligence, strict liability, or other claims, even if EFFEKTA GmbH has been informed in advance about the possibility of such damage. This exclusion also applies for any liability arising from claims of third parties made against the initial purchaser.
In some countries, the exclusion or limitation of coincidental or consequential damage is not legally permitted, in which case the above declaration is not effective.
UPS RMH700/1000/1500 Instruction Manual
RMH Series
Page 7 of 37
3 Safety
3.1 General safety instructions
Read and observe the user manual and safety instructions in this chapter before taking any further action (transportation, storage, connection, startup, etc.).
Since the UPS equipment uses mains voltage and incorporates an appropriate energy accumulator (high-capacity batteries) either on the inside or outside of the device, the instructions in this chapter are very important for all users and personnel. For this reason, safety information on batteries and battery packs is also provided here. When using external battery packs, you must also follow the safety instructions in the accompanying manual.
Work on the UPS equipment may only be performed by authorized technical personnel.
3.2 Transportation and storage
The UPS may only be transported to its destination in the original packaging. The same applies for removals or returns.
The equipment may not be transported or stored upside down. Position the equipment securely during transportation taking the centre of
gravity into account. Due to their weight, UPS equipment with built-in batteries may drop suddenly if their position shifts slightly.
During storage, secure positioning of the equipment must also be ensured.
3.3 Setup
The UPS is intended for use in ventilated rooms. During setup or installation, the installation location prescribed by the
manufacturer must be observed. If the UPS is exposed to extreme and rapid temperature changes, there is a
risk of condensation. Before taking any further steps, the equipment should be allowed to acclimatise for at least 2 hours.
Never set up or operate the equipment in a damp environment. Keep fluids away from the equipment.
UPS RMH700/1000/1500 Instruction Manual
RMH Series
Page 8 of 37
The UPS must not be set up near heat sources. Ensure that the vents of the equipment are not blocked and that the air
circulation is not impeded.
3.4 Connection
Only connect the UPS to an earthed shock-proof socket or, where a terminal clamp is used, connect the protective earth conductor without fail. Under no circumstances should the equipment be operated without a protective earth conductor.
The house installation socket must be easily accessible and located in the vicinity of the UPS. In the case of a fixed connection, ensure that the shortest possible cable lengths are used.
If a generator is used to operate the equipment, the correct poling must be observed when connecting the UPS.
To connect the UPS to the house installation socket, only a VDE-tested and CE-labelled mains cable may be used. In the case of a fixed connection, a suitable cable must be used.
To connect the consumer to the UPS, only use VDE-tested and CE-labelled electrical cables. In the case of a fixed connection to the consumer, a suitable cable must be used.
The fuse protection for the consumer must always be installed directly in front of it, and never centrally in front of the UPS.
Do not operate any household appliances and power tools, e.g. fan heaters, vacuum cleaners, drills, hairdryers, toasters, etc., via the UPS.
Do not connect any consumers to the UPS which could overload the equipment (e.g. laser printers).
The sum of the earth fault currents of all consumers connected to the UPS must not exceed 3.5 mA.
Keep the connecting cables as short as possible and always lay these correctly. Avoid the dangers associated with laying connecting cables where they may be tripped over, crushed or torn open, etc.
3.5 Operation
The mains power cable must never be disconnected during the operation of the UPS, otherwise the protective earthing of the UPS as well as the connected consumers will be lost.
UPS RMH700/1000/1500 Instruction Manual
RMH Series
Page 9 of 37
The UPS equipment contains an energy accumulator (batteries). This means that the output of the UPS can be live even if it is not connected on the line side.
To completely switch off the UPS, first press and hold the "ON/OFF" button for more than 3 seconds, wait until the UPS switches off and only then disconnect the equipment from the mains (remove input fuse or disconnect mains supply cable from the equipment).
Make sure that no fluids or foreign bodies enter the UPS.
3.6 Handling batteries
Warning – danger of electric shocks and burns. Batteries can cause electric shocks and are capable of producing high short­circuit currents which can also inflict burns.
Unauthorized persons must be kept away from batteries. Do not place batteries against heat sources and do not throw them into a fire.
They might explode! Do not open or destroy batteries. The electrolyte released is extremely
dangerous to people and the environment (danger of chemical burning to skin and eyes, toxic).
Defective batteries must be disposed of in an environmentally-friendly manner. Never throw batteries into the household refuse. The local waste disposal regulations must be observed.
3.7 Maintenance, servicing and faults
Warning – danger of electric shocks. The UPS remains connected to the battery circuit even after it has been disconnected from the mains power supply, and has a dangerous voltage potential. Therefore always disconnect the battery circuit before carrying out servicing or maintenance work and make sure that the equipment has been disconnected from the supply.
Work on batteries may only be performed and monitored by personnel with appropriate technical knowledge about the required precautions.
Unauthorized persons must be kept away from batteries. When working on the UPS, the following precautions must be taken:
UPS RMH700/1000/1500 Instruction Manual
RMH Series
Page 10 of 37
o Remove wristwatches, rings and other metallic objects o Only use electrically-insulated tools
The UPS must not be dismantled.
UPS RMH700/1000/1500 Instruction Manual
RMH Series
Page 11 of 37
4 Introduction
This manual is intended to provide basic information on single-phase online UPS equipment including their functional principle, application of the various functions and troubleshooting. In addition, this manual contains information on transportation and storage as well as handling and installation of the UPS equipment. The planning guidelines in this handbook relate only to the specific requirements for UPS equipment. During installation, the national and local regulations for electrical installations must be followed without fail. This equipment description contents may change as a result of technological developments. We have endeavoured to make these contents as accurate and clear as possible. However, we would be grateful for information on any errors which are noted. We accept no liability for errors in this description and their consequences.
The UPS equipment (Uninterruptible Power Supply) is to protect sensitive electrical devices such as computers, workstations, electronic points of sale, mission-critical instruments, telecommunications equipment, process controls, etc. from faults which may arise as a result of poor power supply quality or even power failures. Sensitive devices such as these require comprehensive protection against electrical faults. These may be external faults (e.g. bad weather, operating faults) or faults caused by neighbouring devices (e.g. motors, air conditioning units, processing machines, welding equipment, etc.). The power supply faults can be summarised as follows:
o Fast and slow voltage spikes and fluctuations; o Mains power failure; o Fast and slow frequency spikes and fluctuations; o Mains heterodyning or transient voltages
The UPS equipment prepares the mains voltage and ensures that the voltage values at the output to the consumer load remain constant. Faults in the mains voltage are thus prevented from reaching mission-critical devices and cannot cause any damage to software and hardware, data loss or operating faults.
UPS RMH700/1000/1500 Instruction Manual
RMH Series
Page 12 of 37
5 System description
The UPS operates continuously according to the double converter principle. It ensures the preparation of the line current and delivers an uninterrupted and fault-free single-phase voltage to mission-critical consumer loads In addition to supplying consumer loads, the equipment also keeps its internal batteries in a fully charged state. In the event of a power failure or power fault, the UPS continues to deliver a clean uninterrupted voltage supply to the UPS output. During support operation, energy is drawn from the batteries.
Fig. 1: Block diagram RMH series 700/1000/1500
The block circuit diagram shows the individual modules of the equipment and provides a general impression of how they interact.
When the mains power failure exceeds the bridging time of the UPS, it shuts down to prevent deep discharging of the batteries. When the mains power supply is restored, the UPS restarts automatically, supplies the consumer loads and controls the charging of the battery pack.
Notable performance features of the RMH series online UPS include:
o Absolutely no interruption or signal modification in event of primary
mains power supply failure.
o Perfect sine voltage at the UPS output. Greatly enhanced quality of
output voltage when compared to the mains voltage of the house network.
o Processor-controlled bypass operation; o Input-side “power factor” correction (>0.95);
Loading...
+ 25 hidden pages