E+E Elektronik EE820 User Manual

The EE820 transmitter is designed for the measurement of CO2 in demanding applications. It incorporates the E+E dual wavelength NDIR CO2 sensor, which compensates for ageing effects, is highly insensitive to pollution and offers outstanding long term stability.
For use in special applications do not hesitate to contact E+E Elektronik or a local distributor.
GENERAL
• For use in polluted, dirty environment is essential to close tightly the transmitter cover as well as the cable glad or conduit adap-
ter in order to avoid pollution ingress into the enclosure.
• This device is not appropriate for safety, emergency stop or other critical applications where device malfunction or failure could
cause injury to human beings.
CAUTION
USER‘S GUIDE
EE820 – CO2 Transmitter for Demanding Applications
INSTALLATION/DIMENSIONS
EE820 with M12 plug does not require any wiring inside the device. The external mounting holes allow the device to be mounted without opening the front cover. The mating M12x1 cable plug for self assembly is included in the scope of supply. Please see EE820 data sheet for optional M12 plugs and cables.
EE820 with cable gland: Use a matching wrench to install the cable gland (in the scope of supply) onto the EE820 enclosure.
EE820 with conduit connection for the North American market: use a flat screwdriver to knock open the blind, carefully, in order to
avoid damaging the electronics inside the enclosure. The conduit adapter is not included in the scope of supply. The M16x1.5 opening for the cable gland shall be tightly closed using the blind plug included in the scope of supply.
FOR CONDUIT INSTALLATION
CABLE GLAND M16x1.5
M12x1 Plug
101mm
3.98“
19mm
0.75“
90
±0.3
mm
3.54
±0.11
46mm
1.81“
5mm
0.2“
80.6mm
3.17“
SCOPE OF SUPPLY
• EE820 Transmitter according to ordering guide
• Cable gland (only for EE820 with cable gland)
• Mounting set (screws and rowlplugs/screw anchors)
• Mating M12x1 connector for self assembly (only for EE820-CxxxNxx with installed M12x1 connector)
• Two self-adhesive labels for configuration changes (see user guide at www.epluse.com/relabeling)
• Quick Guide - EE820 Connection Diagram (only for EE820 with M12 connector)
• Test report according to DIN EN 10204 – 2.2
TECHNICAL DATA
(Modification rights reserved)
CONNECTION DIAGRAM
1) Mating M12x1 connector for self assembly is included in the scope of supply
2) Very important: for failure-free operation and performance according to the specs the supply GND and the measurement GND must be wired separately.
EE820 with M12 plug
1)
EE820 with cable gland
Measured values
Measuring principle dual wavelength non-dispersive infrared technology (NDIR) Measurement range 0...2000 / 5000 / 10000 ppm Accuracy at 25 °C and 1013 mbar 0...2000 ppm: < ± (50 ppm +2 % of measured value)
(77 °F...14,7 psi) 0...5000 ppm: < ± (50 ppm +3 % of measured value)
0...10000 ppm: < ± (100 ppm +5 % of measured value)
Response time
τ
63
standard: typ. 300 s fast: typ. 140 s (with a forced air circulation module) Temperature dependency typ. ± (1 + CO2 concentration [ppm] / 1000) ppm/°C (-20...45 °C) (-4...113 °F) Sample rate approx. 15 s
Output
0...2000 / 5000 / 10000 ppm 0 - 5 / 0 - 10 V -1mA < I
L
< 1 mA
4 - 20 mA RL < 500 Ohm
General
Supply voltage 24 V AC ±20% 15 - 35 V DC Current consumption standard: typ. 15 mA + output current fast: typ. 60 mA + output current Current peak max. 350 mA for 0.3 s Warm up time
1)
< 5 min
Housing material Polycarbonate, UL94V-0 approved Protection class IP54
Electrical connection Screw terminals 2.5 mm² or M12 plug
Electromagnetic compatibility EN61326-1 EN61326-2-3 Industrial Environment FCC Part 15 ICES-003 ClassB Working conditions -20...60 °C
(-4...140°F) 0...100 % RH (non-condensing)
Storage conditions -20...60 °C (-4...140°F) 0...95 % RH (non-condensing)
1) for performance according to specification
The EE820 transmitter is ready to use and does not require any configuration by the user. The factory setup of EE820 corresponds to the type number ordered. For ordering guide please see data sheet at www.epluse.com/EE820
If needed, the user can change the factory setup by using the optional Product Configuration Adapter EE-PCA and the Product Configuration Software EE-PCS. One can change the output signal, the scaling of the output and perform CO
2
adjustment/calibration.
Even in case of use in dirty and dusty environment, the electronics of EE820 are very well protected by the enclosure and the filter on the front cover. Do not attempt in any way to clean the inside of the device.
In case of dirt deposits on the exterior of the device, this can be cleaned by weeping it gently with a soft, light wet cloth. The enclosure must be closed during the cleaning. Do not use solvent-based cleaning agents; these might affect the enclosure and the labels. Do not attempt to clean the filter on the front cover, as it would only lead to its faster clogging.
In a polluted environment, the filter on the front cover of EE820 might get clogged in a long run. This is more likely to happen for the EE820 with forced air circulation. Longer response time indicates a clogged filter. In such a case the entire front cover shall be replaced by an original new one.
SETUP AND ADJUSTMENT
Changing the output signal:
The output signal can be changed from voltage to current or vice-versa.
Set the output signal selection switch to I for current 4 - 20 mA output or to U for voltage 0 - 10 V output. The original CO
2
output range
does not change and the calibration data remains valid.
Example:
Factory setup: voltage output (U), output scale: 0 - 10 V = 0 - 5000 ppm User setup (after setting the output signal selection switch to I): current output (I), output scale: 4 - 20 mA = 0 - 5000 ppm.
Changing the output scale:
The scaling of the output can be changed by using EE-PCA and EE-PCS.
Example:
The initial scaling of the output is 4 - 20 mA = 0 - 5000 ppm. The output scale after the change can be 4 - 20 mA = 400 - 4000 ppm.
Important:
• After changing the factory setup (output signal and/or output scale) the original type number on the EE820 identification label loses
its validity; it does not match any longer the device setup.
• The return to factory setup function of EE-PCS restores the original adjustment/calibration of the device, but does not affect the user
setup for output signal and output scale.
For EE-PCA product data sheet please see www.epluse.com/EE820 The EE-PCS Product Configuration Software is available for free download at www.epluse.com/configurator.
MAINTENANCE
PC
HA011062
EE-PCA
V03
EE820
EE820-FAC - Forced Air Circulation Module (Replacement/Retrot)
The EE820-FAC Forced Air Circulation Module is an ESD sensitive device and shall be handled at all times according to the general precautions for handling of ESD sensitive equipment .
CAUTION
EE820 Cover is not included in the scope of supply and shall be ordered separately, type number: EE820-COVER
SCOPE OF SUPPLY
Blue connector
cut-out 1
cut-out 2
restraint A
restraint B
• Release the old EE820-FAC by acting on restraint A.
For installing the new EE820-FAC:
• Observe the position of the A and B restraints in the cover and of the corresponding cut-outs 1 and 2 in the EE820-FAC board.
• Insert first the EE820-FAC into the B restraints. Than press the EE820-FAC as in the picture below, till in snaps into the A restraints.
“CLICK“
INSTALLING
1.
2.
cut-out 3
REPLACING
FOR REPLACING an existing EE820-FAC modul remove first the old EE820-FAC module:
• Disconnect the blue connector from the main EE820 board
1.
2.
1)
2)
DD
D
D
• Connect the blue connector of the EE820-FAC to the blue socket on the main EE820 board.
• Place the cover on the EE820 so that the cut-out 3 matches the location of the blue connector.
• Fix the cover with the 4 bayonett screws D.
INFORMATION
+43 7235 605 0 / info@epluse.com
Langwiesen7•A-4209Engerwitzdorf Tel:+437235605-0•Fax:+437235605-8 info@epluse.com•www.epluse.com
LGLinzFn165761t•UID-Nr.ATU44043101 PlaceofJurisdiction:A-4020Linz•DVR0962759
BA_EE820_e // v1.4 // Modification rights reserved
USA FCC notice:
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the installation manual, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment into an outlet on a circuit different from that to which thereceiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
CANADIAN ICES-003 Issue 5:
CAN ICES-3 B / NMB-3 B