E+E EE80 Specifications

EE80
HVAC Room CO2 Switch
EE80 room CO2 switch is based on the non-dispersive infrared (NDIR) measurement principle. A patented auto-calibration procedure compensates for the aging of the infrared source and ensures outstanding long term stability.
Two different enclosure designs ensure professional appearance according to regional standards.
EE80
Typical Applications Features
building management for residential and office areas ventilation control
optional display
easiest installation
long-term stable
Technical Data
Measured values CO
Measurement principle Non-Dispersive Infrared Technology (NDIR) Sensor E+E Dual Source Infrared System Working range 0...2000 / 5000 ppm Accuracy at 25 °C (77 °F) 0...2000 ppm: < ± (50 ppm +2 % of measuring value) and 1013 mbar 0...5000 ppm: < ± (50 ppm +3 % of measuring value) Response time t Temperature dependence typ. 2 ppm CO Long term stability typ. 20 ppm / year Sample rate approx. 15 s
Switch Output
Max. switching voltage 50 V AC / 60 V DC Max. switching load 0.7 A at 50 V AC 1A at 24 V DC Min. switching load 1 mA at 5 V DC Contact material Ag+Au clad
General
Display LC display
Electromagnetic compatibility EN61326-1 FCC Part 15 EN61326-2-3 ICES-003 ClassB Working temperature range 0...90 % RH (non condensing) / -20...60 °C Storage temperature range 0...90 % RH (non condensing) / -20...60 °C (-4...140 °F)
1) warm up time for performance according specification
2
< 195s
63
/°C
2
Supply voltage 24 V AC ±20 % 15 - 35 V DC Current consumption typ. 10 mA max. 0.5 A for 0.3 s Warm up time Housing material Polycarbonate US Version: UL94V-0 approved / EU Version: UL94HB approved Protection class IP30
Electrical connection screw terminals max. 1.5 mm
1)
< 5 min
2
(AWG16)
(-4...140 °F)
modern design
194
v2.5 / Modification rights reserved
EE80
EE80
Connection Diagram
power supply
15...35 V DC 24 V AC ±20 %
Housing Dimensions (mm)
Europe: W x H x D = 85 x 100 x 26 mm (3.3 x 3.9 x 1”) USA: W x H x D = 85 x 136 x 26 mm (3.3 x 5.4 x 1”)
relay status
ON
OFF
Ordering Guide
WORKING RANGE MODEL DISPLAY HOUSING DESIGN & COLOUR
0...2000 ppm
0...5000 ppm
EE80-
Order Example
Hysteresis [% of WR]
switching off
25% of WR
Housing colour:
Standard (EU & US): Front cover: Signal white RAL 9003 Back cover: Light grey RAL 7035
Level [% of WR]
Optional (only EU): Front and Grey (Anthracite grey RAL 7016)
on
switching
1000500
2000
ppm
back cover Silver (White aluminum RAL 9006)
NO = normally open NC = normally closed WR = working range
(2) CO
Switch (CS) without Display (--) EU-Standard (RAL9003 / RAL7035) (--)
2
(5) with Display (D04) EU-Grey (RAL7016) (G)
EU-Silver (RAL9006) (S) US (RAL9003 / RAL7035) (US)
EE80-2CSD04G EE80-5CSUS
Working range: 0...2000 ppm Model: CO Display: with Display
Switch
2
Housing design & colour: EU-Grey (RAL7016)
EE80
v2.5 / Modification rights reserved
Working range: 0...5000 ppm Model: CO Display: without Display Housing design & colour: US (RAL9003 / RAL7035)
Switch
2
195