EE600
Dierential Pressure Sensor
The EE600 is dedicated for reliable measurement of dierential pressure
in HVAC, building automation and lter monitoring applications. The multirange device can be employed for air as well as all non-ammable and
non-aggressive gases.
Measurement Performance
The EE600 is available with full scale (FS) 1,000 Pa (4 inch Water Column)
and 10,000 Pa (40 inch WC) and oers an outstanding accuracy of ± 0.5 %
FS. For the versions with analogue outputs, several measuring ranges are
selectable with DIP-switches. The piezo-resistive, no ow-through pressure sensing element stands for outstanding long-term stability.
Analogue and Digital Outputs
The measured data is available on the analogue voltage and current outputs or on the RS485 interface with Modbus RTU
or BACnet MS/TP protocol.
Functional and Robust
The IP65 / NEMA 4 enclosure minimizes installation costs. External mounting holes allow for installation with closed cover,
the electronics are thus protected against construction site pollution.
Congurable and Adjustable
The setup and adjustment can be easily performed with DIP-switches and push buttons on the electronics board (EE600
with analogue outputs) or with an optional adapter and the free EE-PCS conguration software (EE600 with RS485
interface). The setup includes pressure range, output signal, response time, display units and backlight. Beside dierential
pressure measurement, the EE600 can be set up for volume ow or air velocity measurement, as well as for lter monitoring or level indication. A zero and span point adjustment can be easily performed with push buttons on the electronics
board.
Features
Accuracy ± 0.5 % FS
Multi-range (analogue outputs)
» 0 … 250 / 500 / 750 / 1000 Pa
» 0 … 2500 / 5000 / 7500 / 10000 Pa
External mounting holes
» Mounting with closed cover
» Electronics protected against
construction site pollution
» Easy and fast mounting
Test report according to
DIN EN 10204-2.2
User congurable and adjustable
» Pressure range
» Output signal
» Response time
» Display units and backlight
» Zero and span point adjustment
Knockout for ½"
conduit tting (US)
Service interface for conguration
(RS485 version)
» Measurands
» Differential pressure
» Volume flow (k-factor input)
» Air velocity (k-factor input)
» Application setting
» Filter monitoring
» Level indicator
Graphic display
with backlight
Enclosure
» IP65 / NEMA 4 protection class
» Bayonet screws - open/closed with
a ¼ rotation
176
v1.7 / Modification rights reserved
EE600
EE600
Dimensions (mm/inch)
90
3.54
±0.3
mm
±0.11
“
46 mm
1.81“
FOR CONDUIT
INSTALLATION
Pressure ttings Ø 5mm
5 mm
0.2“
3.17“
80.6 mm
+ : High pressure
- : Low pressure
5 mm
0.2“
CABLE GLAND M16x1.5
Technical Data
Measured Value
Differential Pressure (Δp)
Measurement principle Piezoresistive, no flow-through
Accuracy at 20 °C
(incl. hysteresis, non-linearity and repeatability) FS = full scale (1000 Pa or 10000 Pa)
Response time t
Analogue outputs 50 ms / 500 ms / 2 s / 4s selectable with DIP switches
RS485 selectable in the range from 0.5 to 30 s using EE-PCS
Temperature dependency typ. < 0.03 % from FS/K
Long-term stability < 0.5 % from FS/year
Overload limits
0...1000 Pa
0...10000 Pa (40 inch WC) ± 80000 Pa (± 320 inch WC)
Outputs
Analogue outputs3) 0-5 V or 0-10 V -1 mA < I
selectable with and
DIP switches
Measurement range I: 0...250 / 500 / 750 / 1000 Pa (0...1 / 2 / 3 / 4 inch WC)
selectable with DIP switches
Digital interface RS485 (EE600 = 1/2 unit load)
Protocol Modbus RTU or BACnet MS/TP
General
Power supply 15-35 V DC or 24 V AC ±20 %
Current consumption, typ. at 0 Pa / 24 V DC
Analogue outputs RS485
without display 23 mA 8 mA
with display and backlight 49 mA 29 mA
Display Graphic, with backlight
Display units Pa, mbar, inch WC, kPa
Analogue outputs selectable with DIP switches
RS485 configurable using EE-PCS
Connection
Analogue outputs spring terminals, max. 1.5 mm
RS485 screw terminals, max. 2.5 mm2 (AWG14)
1) Factory setup analogue outputs: measurement range 0...100 % FS; response time t90: 50 ms; display unit: Pa; display backlight: on; analogue outputs: 0-10 V and 4-20 mA.
Other ranges upon request.
2) Factory setup RS485: response time t90: 500 ms; display unit: Pa; display backlight: on
3) Voltage and current output signals available simultaneously at the spring loaded terminals.
EE600
v1.7 / Modification rights reserved
(68 °F) ± 0.5 % FS
90
(4 inch WC) ± 10000 Pa (± 40 inch WC)
1)
0-20 mA or 4-20 mA (3-wire) R
1)
II: 0...2500 / 5000 / 7500 / 10000 Pa (0...10 / 20 / 30 / 40 inch WC)
2)
< 1 mA IL = load current
L
≤ 500 Ohm RL = load resistor
L
1)
2
(AWG16)
1)
2)
177