E+E EE471 Specifications

Page 1
EE471
Temperature Sensor with Remote Probe
The EE471 temperature sensor with remote probe measures reliably the temperature (T) in applications with space restrictions and is optimized for building automation, HVAC and process control.
Analogue, Digital and Passive Outputs
The T measured data is available on the voltage or current output, as well as on the RS485 interface with Modbus RTU or BACnet MS/TP protocol. In addition, EE471 features a wide choice of sensing elements for passive T measurement.
Easy Installation
The design with remote probe is appropriate for installations where electronic shall be protected against high temperature or strong vibra­tions. Product specific information for the remote probe is printed all along the cable. The innovative immersion well is dedicated for measurement in liquids and allow for fast and safety replacement of the sensor.
Configurable and Adjustable
An optional adapter and the free EE-PCS Product Configuration Software facilitate the setup and adjustment of the EE471.
Features
External mounting holes
» Mounting with closed cover
» Protection against construction
site pollution
Product-
specic
information
IP67 cable
Bayonet screws
» Open/closed with a ¼ rotation
IP65 / NEMA 4
outlet
(star pressing of the sensor sleeve)
Test report according to DIN EN 10204 – 2.2
Technical Data
Active Output
Operating temperature remote probe: -30…+105 °C (-22...+221 °F)
electronics: -30....+70 °C (-22...+158 °F)
Sensing element Pt1000 class A, DIN EN60751 Analogue output 0-10 V -1 mA < I
4-20 mA (two-wire) R
< 500 R
L
Digital interface RS485 with max. 32 unit load devices on one bus
Protocol Modbus RTU or BACnet MS/TP
Accuracy ±0.3 °C
(±0.54 °F) at 20 °C (68 °F)
Supply voltage (Class III) 15-35 V DC or 24 V AC ±20% for RS485 and 0-10 V output 10 V DC + R Current demand (typ.) analogue 5 mA (DC) / 12 mA
RS485 3.5 mA (DC) / 12 mA
x 20 mA < V+ < 35 V DC for 4-20 mA output
L
eff
(AC)
(AC)
eff
Electromagnetic compatibility EN61326-1, EN61326-2-3 industrial environment
< 1 mA
L
= load resistance
L
164
v1.9 / Modification rights reserved
EE471EE471
Page 2
Passive Output
Operating temperature -30…+105 °C (-22...+221 °F) T sensing elements
Measurement current typ. < 1 mA
Sensor Type Nominal Resistance Sensitivity Standard
Pt100 DIN B
Pt1000 DIN B R
NTC1.8k R
NTC2.2k R
NTC10k B3950 R
NTC10k B3435 R
KTY81-210 R
Ni1000 TK6180 DIN B R Ni1000 TK5000 DIN B R
0: 100 Ω TC: 3.850 x 10
R
0: 1000 Ω TC: 3.850 x 10
25: 1.8 kΩ ± 0.2 K B25/85: 3500 K ± 1.0 % -
25: 2.252 kΩ ± 0.2 K B25/85: 3977 K ± 0.3 % -
25: 10 kΩ ± 0.5 % B25/85: 3989 K (B25/50: 3950 K ± 1.0 %) -
25: 10 kΩ ± 1 % B25/85: 3435 K -
25: 1980-2020 Ω - -
0: 1000 Ω TC: 6180 ppm/K DIN 43760 0: 1000 Ω TC: 5000 ppm/K DIN 43760
-3
/°C DIN EN 60751
-3
/°C DIN EN 60751
(according technical data of the specic T-sensing element)
T-Sensor connection two-wire, wire resistance see additional information below
General
Insulation resistance (remote probe) > 100 MΩ at 20 °C (68 °F)
Response time τ63 < 1 min, at 3 m/s (590 ft/min) air velocity < 30 s, with immersion well in liquid water bath Sensor sleeve material stainless steel Cable material PVC Electrical connection screw terminal, 2x max. 2.5 mm Enclosure material polycarbonate, UL94-V0 approved Protection class IP65 / NEMA 4 (enclosure), IP67 / NEMA 4 (remote probe) Cable gland M16x1.5, M12x1.5 , UL94-V2 Storage temperature -30…+70 °C Working and storage humidity 5...95 % RH, non condensing
(1.4571 / 316Ti)
(-22...+158 °F)
2
(0.004 in
2
)
Additional Information
Wire Resistance / Temperature Offset (relevant only for passive output EE471-M7)
Cable length Wire resistance Temperature o󰀨set for Pt100
0.5 m (1.64 ft) 0.086 0.22 °C (0.396 °F)
2 m (6.56 ft) 0.344 0.88 °C (1.584 °F)
3 m (9.84 ft) 0.516 1.32 °C (2.376 °F)
5 m (16.4 ft) 0.860 2.2 °C (3.960 °F)
10 m (32.8 ft) 1.72 4.4 °C (7.920 °F)
*) For high-resistance T-sensors (R ≥ 1000 Ω) the temperature o󰀨set is negligible.
Dimensions mm (inch)
80.8 (3.18)
63 (2.48)
Ø6
(0.24)
55 (2.17)
Ø4
(0.16)
5
(0.2)
star pressing
M12x1.5
M16x1.5
42 (1.65)
55.3 (2.18)
55.3 (2.18)
*)
39.5 (1.56)
Immersion well
width across ats: 22 (0.87)
14 (0.55)
Ø8
(0.31)
8
(0.31)
*)
L
EE471
v1.9 / Modification rights reserved
*)
According to ordering guide
165
Page 3
Ordering Guide
Position 1 - Temperature Sensor
Model
Output
T-sensor passive
(see www.epluse.com/R-T_Characteristics)
Hardware Configuration
Cable length
Unit
Scale T low
Scale T high
Protocol
Setup Outputs
Baud rate
1) Factory setting: Even parity, Stopbits 1. Modbus Map and communication setting: see User Guide and Modbus Application Note at www.epluse.com/ee471
2) Factory setting: No parity, Stopbits 1. Product Implementation Conformance Statement (PICS) available at www.epluse.com/ee471
3) Only for BACnet MS/TP
active M3 passive M7 0-10 V A3 4-20 mA A6 RS485 J3 Pt100 DIN B TP2 Pt1000 DIN B TP4 NTC 1.8k TP7
Ni1000, TK6180 DIN B TP9
NTC 10k, B3950 TP11
KTY81-210 TP13
NTC 10k, B3435 TP14
Ni1000, TK5000 DIN B TP19
NTC 2.2k TP21
0.5 m
(1.6 ft) K0.5
2 m
(6.6 ft) K2
3 m
(9.8 ft) K3
5 m
(16.4 ft) K5
10 m (32.8 ft)
°C no code °F MA2 0 no code value
(within working range) SAL value
50 no code value
(within working range) SAH value
Modbus RTU BACnet MS/TP
1)
2)
9.600 BD5
19.200 BD6
38.400 BD7
3)
57.600
3)
76.800
EE471-
K10
P1 P3
BD8 BD9
Position 2 - Mounting Accessories
Plastic mounting flange HA401101
Immersion well: R½’’ ISO:
length (L) 50 mm (1.97“) 100 mm (3.94“) 135 mm (5.31“) 285 mm (11.22“) brass stainless steel HA400201 HA400204 HA400202 HA400203
Immersion well: ½’’ NPT:
length (L) 50 mm (1.97“) 100 mm (3.94“) 135 mm (5.31“) 285 mm (11.22“)
brass HA400111 HA400114 HA400112 HA400113 stainless steel HA400211 HA400214 HA400212 HA400213
HA400101 HA400104 HA400102 HA400103
166
v1.9 / Modification rights reserved
EE471
Page 4
Order Example
EE471-M3J3K3P3BD7
Model: active Output: RS485 Cable length: 3 m
(9.8 ft)
EE471-M7TP11K5
Model: passive T-sensor passive: NTC 10k, B3950
Cable length: 5 m Protocol: BACnet MS/TP Baud rate: 38.400
Accessories
Product configuration adapter
- for analogue output see data sheet EE-PCA
- for digital output - USB configuration adapter HA011066 Product configuration software EE-PCS
(free download: www.epluse.com/configurator)
Power supply adapter V03 (see data sheet Accessories) Conduit adapter, M16x1.5 to 1/2“ HA011110 Cable gland
(M12x1.5, -40 °C...+100 °C / -40 °F... +212 °F, UL94-V0) HA403101
Hose clamp (for pipe mounting of remote probe) HA402101
For further information please see datasheet EE441.
Mounting with Immersion Well
(16.4 ft)
1.
.
2
1. The spring inside the well must be removed and replaced by a standard M12x1.5 cable gland (not included in the scope of supply).
2. Insert the remote cable sensor and x it by fastening the cable gland.
Please observe the operating temperature range of the cable gland!