EE451
The EE451 wall mounted sensor measures reliably the
temperature (T) indoors and outdoors, is optimized for building
automation, HVAC, process control and enables weatherdependent temperature regulation.
Analogue, Digital and Passive Outputs
The T measured data is available on the voltage or current output,
as well as on the RS485 interface with Modbus RTU or BACnet
MS/TP protocol. In addition, EE451 features a wide choice of sensing elements for passive T measurement.
Easy Installation
The compact and robust enclosure allows for easy and fast installation and unbiased detection of ambient temperature.
Configurable and Adjustable
An optional adapter and the free EE-PC Product Configuration Software facilitate the setup and adjustment of the EE451.
Features
External mounting holes
» Mounting with closed cover
» Protection against construction
site pollution
Bayonet screws
» Open/closed with a ¼ rotation
for Indoor and Outdoor
Active Type Passive Type
Mounting bracket
» Distance to wall for
correct measurement
of ambient temperature
Wall Mounted Temperature Sensor
IP65 / NEMA 4
Test report according to
DIN EN 10204 – 2.2
Technical Data
Active Output
Sensing element Pt1000 class A, DIN EN60751
Analogue output 0-10 V -1 mA < I
4-20 mA (two-wire) R
< 500 Ω R
L
Digital interface RS485 with max. 32 unit load devices on one bus
Protocol Modbus RTU or BACnet MS/TP
Accuracy ±0.3 °C
(±0.54 °F) at 20 °C (68 °F)
Supply voltage (Class III) 15-35 V DC or 24 V AC ±20% for RS485 and 0-10 V output
10 V DC + R
Current demand (typ.) analogue 5 mA (DC) / 12 mA
RS485 3.5 mA (DC) / 12 mA
x 20 mA < V+ < 35 V DC for 4-20 mA output
L
eff
(AC)
(AC)
eff
Electromagnetic compatibility EN61326-1, EN61326-2-3
industrial environment
Passive Output
T sensing elements
Sensor Type Nominal Resistance Sensitivity Standard
Pt100 DIN B
Pt1000 DIN B R
NTC1.8k R
NTC2.2k R
NTC10k B3950 R
NTC10k B3435 R
KTY81-210 R
Ni1000 TK6180 DIN B R
Ni1000 TK5000 DIN B R
0: 100 Ω TC: 3.850 x 10
R
0: 1000 Ω TC: 3.850 x 10
25: 1.8 kΩ ± 0.2 K B25/85: 3500 K ± 1.0 % -
25: 2.252 kΩ ± 0.2 K B25/85: 3977 K ± 0.3 % -
25: 10 kΩ ± 0.5 % B25/85: 3989 K (B25/50: 3950 K ± 1.0 %) -
25: 10 kΩ ± 1 % B25/85: 3435 K -
25: 1980-2020 Ω - -
0: 1000 Ω TC: 6180 ppm/K DIN 43760
0: 1000 Ω TC: 5000 ppm/K DIN 43760
< 1 mA
L
= load resistance
L
-3
/°C DIN EN 60751
-3
/°C DIN EN 60751
154
v1.5 / Modification rights reserved
EE451
EE451
Measurement current typ. < 1 mA
(according technical data of the specic T-sensing element)
T-Sensor connection two-wire
General
Operating temperature -40…+70 °C (-40...+158 °F)
Enclosure material polycarbonate, UL94-V0 approved
Protection class IP65 / NEMA 4
Cable gland M16x1.5, UL94-V2
Electrical connection screw terminal, max. 2.5 mm
2
(0.004 in
Mounting bracket material stainless steel (corr. 1.4301 / 304)
Storage temperature -30…+70 °C
(-22...+158 °F)
Working and storage humidity 5...95 % RH, non condensing
Dimensions mm (inch)
Passive output
42 (1.65)
55.3 (2.18)
80.8 (3.18)
63 (2.48)
Ø4
(0.16)
Active output
2
)
~96 (3.78)
cable gland
M16x1.5
55.3 (2.18)
49 (1.93)
Ø6
(0.24)
mounting bracket (included in the scope of supply)
~96 (3.78)
Mounting Mounting Bracket
26 (1.02)
4.5 (0.18)
39.5 (1.56)
9.5
(0.37)
EE451
v1.5 / Modification rights reserved
cross-head screw M3x8 A2
(in the scope of supply)
M3
49.6 (1.95)
30 (1.18)
8.5
(0.33)
70.6 (2.78)
8.5
4.5
(0.33)
(0.18)
1.5
(0.06)
155