E+E EE451 Specifications

EE451
The EE451 wall mounted sensor measures reliably the temperature (T) indoors and outdoors, is optimized for building automation, HVAC, process control and enables weather­dependent temperature regulation.
Analogue, Digital and Passive Outputs
The T measured data is available on the voltage or current output, as well as on the RS485 interface with Modbus RTU or BACnet MS/TP protocol. In addition, EE451 features a wide choice of sen­sing elements for passive T measurement.
Easy Installation
The compact and robust enclosure allows for easy and fast installation and unbiased detection of ambient temperature.
Configurable and Adjustable
An optional adapter and the free EE-PC Product Configuration Software facilitate the setup and adjustment of the EE451.
Features
External mounting holes
» Mounting with closed cover
» Protection against construction
site pollution
Bayonet screws
» Open/closed with a ¼ rotation
for Indoor and Outdoor
Active Type Passive Type
Mounting bracket
» Distance to wall for
correct measurement of ambient temperature
Wall Mounted Temperature Sensor
IP65 / NEMA 4
Test report according to DIN EN 10204 – 2.2
Technical Data
Active Output
Sensing element Pt1000 class A, DIN EN60751 Analogue output 0-10 V -1 mA < I 4-20 mA (two-wire) R
< 500 R
L
Digital interface RS485 with max. 32 unit load devices on one bus
Protocol Modbus RTU or BACnet MS/TP
Accuracy ±0.3 °C
(±0.54 °F) at 20 °C (68 °F)
Supply voltage (Class III) 15-35 V DC or 24 V AC ±20% for RS485 and 0-10 V output 10 V DC + R Current demand (typ.) analogue 5 mA (DC) / 12 mA RS485 3.5 mA (DC) / 12 mA
x 20 mA < V+ < 35 V DC for 4-20 mA output
L
eff
(AC)
(AC)
eff
Electromagnetic compatibility EN61326-1, EN61326-2-3 industrial environment
Passive Output
T sensing elements
Sensor Type Nominal Resistance Sensitivity Standard
Pt100 DIN B
Pt1000 DIN B R
NTC1.8k R
NTC2.2k R
NTC10k B3950 R
NTC10k B3435 R
KTY81-210 R
Ni1000 TK6180 DIN B R Ni1000 TK5000 DIN B R
0: 100 Ω TC: 3.850 x 10
R
0: 1000 Ω TC: 3.850 x 10
25: 1.8 kΩ ± 0.2 K B25/85: 3500 K ± 1.0 % -
25: 2.252 kΩ ± 0.2 K B25/85: 3977 K ± 0.3 % -
25: 10 kΩ ± 0.5 % B25/85: 3989 K (B25/50: 3950 K ± 1.0 %) -
25: 10 kΩ ± 1 % B25/85: 3435 K -
25: 1980-2020 Ω - -
0: 1000 Ω TC: 6180 ppm/K DIN 43760 0: 1000 Ω TC: 5000 ppm/K DIN 43760
< 1 mA
L
= load resistance
L
-3
/°C DIN EN 60751
-3
/°C DIN EN 60751
154
v1.5 / Modification rights reserved
EE451
EE451
Measurement current typ. < 1 mA
(according technical data of the specic T-sensing element)
T-Sensor connection two-wire
General
Operating temperature -40…+70 °C (-40...+158 °F) Enclosure material polycarbonate, UL94-V0 approved Protection class IP65 / NEMA 4 Cable gland M16x1.5, UL94-V2 Electrical connection screw terminal, max. 2.5 mm
2
(0.004 in Mounting bracket material stainless steel (corr. 1.4301 / 304) Storage temperature -30…+70 °C
(-22...+158 °F)
Working and storage humidity 5...95 % RH, non condensing
Dimensions mm (inch)
Passive output
42 (1.65)
55.3 (2.18)
80.8 (3.18)
63 (2.48)
Ø4
(0.16)
Active output
2
)
~96 (3.78)
cable gland M16x1.5
55.3 (2.18)
49 (1.93)
Ø6
(0.24)
mounting bracket (included in the scope of supply)
~96 (3.78)
Mounting Mounting Bracket
26 (1.02)
4.5 (0.18)
39.5 (1.56)
9.5
(0.37)
EE451
v1.5 / Modification rights reserved
cross-head screw M3x8 A2 (in the scope of supply)
M3
49.6 (1.95)
30 (1.18)
8.5
(0.33)
70.6 (2.78)
8.5
4.5
(0.33)
(0.18)
1.5
(0.06)
155