E+E EE441 Specifications

EE441
Strap-on Temperature Sensor
The EE441 strap-on sensor measures reliably the temperature (T) on round ducts and pipes and is optimized for heating systems (warm and cold water pipes) or solar collectors.
Analogue, Digital and Passive Outputs
The T measured data, is available on the voltage or current output, as well as on the RS485 interface with Modbus RTU or BACnet MS/TP protocol. In addition, EE441 features a wide choice of sensing elements for passive T measurement.
Easy Installation
The compact enclosure and the stainless steel hose clamp allow for easy and fast installation on pipes with diameter from 25 to 175 mm (0.98”…6.89“).
Configurable and Adjustable
An optional adapter and the free EE-PC Product Configuration Software facilitate the setup and adjustment of the EE441.
Features
External mounting holes
» Mounting with closed cover
» Mounting on plane surfaces
» Protection against construction
site pollution
Aluminium contact surface
» Very good thermal transfer
» Fast response time
Bayonet screws
IP65 / NEMA 4
» Open/closed with a ¼ rotation
Hose clamp
» Installation on pipes
Test report according to DIN EN 10204 – 2.2
Technical Data
Active Output
Operating temperature -40…+70 °C (-40...+158 °F) Sensing element Pt1000 class A, DIN EN60751 Analogue output 0-10 V -1 mA < I 4-20 mA (two-wire) R
< 500 R
L
Digital interface RS485 with max. 32 unit load devices on one bus
Protocol Modbus RTU or BACnet MS/TP
Accuracy ±0.3 °C
(±0.54 °F) at 20 °C (68 °F)
Supply voltage (Class III) 15-35 V DC or 24 V AC ±20% for RS485 and 0-10 V output 10 V DC + R Current demand (typ.) analogue 5 mA (DC) / 12 mA
RS485 3.5 mA (DC) / 12 mA
x 20 mA < V+ < 35 V DC for 4-20 mA output
L
(AC)
eff
eff
(AC) Electromagnetic compatibility EN61326-1, EN61326-2-3 industrial environment
Passive Output
Operating temperature (contact area) -40…+110 °C (-40...+230 °F) T sensing elements
Measurement current typ. < 1 mA
Sensor Type Nominal Resistance Sensitivity Standard
Pt100 DIN B
Pt1000 DIN B R
NTC1.8k R
NTC2.2k R
NTC10k B3950 R
NTC10k B3435 R
KTY81-210 R
Ni1000 TK6180 DIN B R Ni1000 TK5000 DIN B R
(according technical data of the specic T-sensing element)
0: 100 Ω TC: 3.850 x 10
R
0: 1000 Ω TC: 3.850 x 10
25: 1.8 kΩ ± 0.2 K B25/85: 3500 K ± 1.0 % -
25: 2.252 kΩ ± 0.2 K B25/85: 3977 K ± 0.3 % -
25: 10 kΩ ± 0.5 % B25/85: 3989 K (B25/50: 3950 K ± 1.0 %) -
25: 10 kΩ ± 1 % B25/85: 3435 K -
25: 1980-2020 Ω - -
0: 1000 Ω TC: 6180 ppm/K DIN 43760 0: 1000 Ω TC: 5000 ppm/K DIN 43760
150
< 1 mA
L
= load resistance
L
-3
/°C DIN EN 60751
-3
/°C DIN EN 60751
v1.5 / Modification rights reserved
EE441
EE441
T-sensor connection two-wire
General
Insulation resistance > 100 MΩ at 20 °C (68 °F)
Response time τ63 < 1 min Enclosure material polycarbonate, UL94-V0 approved, T-range: -40...+110 °C Protection class IP65 / NEMA 4 Cable gland M16x1.5, UL94-V2 Electrical connection screw terminal, max. 2.5 mm
2
(0.004 in
2
)
Hose clamp material stainless steel (corr. 1.4301 / 304) Storage temperature -30…+70 °C
(-22...+158 °F)
Working and storage humidity 5...95 % RH, non condensing
Dimensions mm (inch)
80.8 (3.18)
63 (2.48)
55.3 (2.18)
Ø25-175
(0.98-6.89)
55.3 (2.18)
42 (1.65)
Ø4 (0.16)
cable gland
M16x1.5
42.5 (1.67)
(-40...+230 °F)
Hose clamp (included in the scope of supply)
Ordering Guide
Model
Output
T-sensor passive
(see www.epluse.com/R-T_Characteristics)
Hardware Configuration
Unit
Scale T low
Scale T high
Protocol
Setup Outputs
Baud rate
1) Factory setting: Even parity, Stopbits 1. Modbus Map and communication setting: see User Guide and Modbus Application Note at www.epluse.com/ee441
2) Factory setting: No parity, Stopbits 1. Product Implementation Conformance Statement (PICS) available at www.epluse.com/ee441
3) Only for BACnet MS/TP
EE441
v1.5 / Modification rights reserved
active M3 passive M7 0-10 V A3 4-20 mA A6 RS485 J3 Pt100 DIN B TP2 Pt1000 DIN B TP4 NTC 1.8k TP7
Ni1000, TK6180 DIN B TP9
NTC 10k, B3950 TP11
KTY81-210 TP13
NTC 10k, B3435 TP14
Ni1000, TK5000 DIN B TP19
NTC 2.2k TP21 °C no code °F MA2 0 no code value
(within working range) SAL value
50 no code value
(within working range) SAH value
Modbus RTU BACnet MS/TP
1)
2)
9.600 BD5
19.200 BD6
38.400 BD7
3)
57.600
3)
76.800
EE441-
P1 P3
BD8 BD9
151
Loading...
+ 1 hidden pages