The EE431 duct and immersion sensor measures reliably the
temperature (T) in air and liquids and is optimized for building
automation, HVAC and process control.
Duct and Immersion Temperature Sensor
Analogue, Digital and Passive Outputs
EE431 + mounting flange
The T measured data is available on the voltage or current output,
as well as on the RS485 interface with Modbus RTU or BACnet MS/
TP protocol. In addition, EE431 features a wide choice of sensing
elements for passive T measurement.
Easy Installation
The device can be mounted either with the plastic mounting
EE431 +
immersion well
flange or via external mounting holes at the enclosure. The
innovative immersion well is dedicated for measurement in liquids
and allows for fast and safe replacement of the sensor. The EE431 with RS485 interface is appropriate for daisy-chain wiring.
Configurable and Adjustable
An optional adapter and the free EE-PCS Product Configuration Software facilitate the setup and adjustment of the EE431.
Features
Mounting flange
External mounting holes
» Mounting with closed cover
» Protection against construction
site pollution
Bayonet screws
» Open/closed with a ¼ rotation
Clamp ring
» No direct screwing onto probe
» Inclined screw for easy installation
Special sealing
» Foam gasket for good tightness
» No scratching of probe due to
alignment notch
IP65 / NEMA 4
Test report according to
DIN EN 10204 – 2.2
Immersion well
Innovative mounting spring
» For securing the probe inside the well
» No fastening screw, no tools required
Technical Data
Active Output
Operating temperature probe duct sensor: -40…+110 °C (-40...+230 °F)
electronics: -40…+70 °C (-40...+158 °F)Sensing element Pt1000 class A, DIN EN60751
Analogue output 0-10 V -1 mA < I
4-20 mA (two-wire) R
Digital interface RS485 with max. 32 unit load devices on one bus
Protocol Modbus RTU or BACnet MS/TP
Accuracy ±0.3 °C
±0.2 °C (±0.36 °F) at 20 °C (68 °F) (optional only for analogue output)
Supply voltage (Class III) 15-35 V DC or 24 V AC ±20% for RS485 and 0-10 V output
10 V DC + R
140
probe immersion sensor: -40…+150 °C (-40...+302 °F)
< 1 mA
L
<500 Ω R
L
(±0.54 °F) at 20 °C (68 °F)
x 20 mA < V+ < 35 V DC for 4-20 mA output
L
v1.6 / Modification rights reserved
= load resistance
L
EE431EE431
Page 2
Current demand (typ.) analogue 5 mA (DC) / 12 mA
RS485 3.5 mA (DC) / 12 mA
Immersion well: R½’’ ISO, stainless steel, 50 mm (1.97 “)
Accessories
Product configuration adapter
- for analogue output see data sheet EE-PCA
- for digital output - USB configuration adapter HA011066
Product configuration software EE-PCS
Power supply adapter V03(see data sheet Accessories)
Conduit adapter, M16x1.5 to 1/2“HA011110
(free download: www.epluse.com/configurator)
EE431
v1.6 / Modification rights reserved
143
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.