The EE211 is dedicated for accurate and long term stable measurement under
continuous high humidity (>85 % RH) and condensing conditions in demanding
climate control. It features a heated humidity, and an interchangeable
temperature (T) probe.
Reliability
Excellent performance of EE211 even in condensing polluted, aggressive
environment is ensured by the combination of IP65/NEMA 4 enclosure, encapsulated
electronics inside the humidity probe and the long-term stable HCT01 sensor with
E+E proprietary coating.
Versatility
All measured and calculated data is available on the Modbus RTU interface
whereas two of the values are available on the analogue voltage or current (3-wire)
output. Up to three values can be shown simultaneously on the illuminated display.
Congurable and Adjustable
An optional USB conguration adapter and the free EE-PCS Product Conguration
Software facilitate the conguration of the EE211 as well as the RH and T
adjustment. The T probe can also be separately adjusted, the reference can be a
high accuracy dry block calibrator.
Applications
• Fruit and vegetable storage
• Cooling, ripening and environmental chambers
• Green houses and incubators
• Mushroom industry
Continuous High Humidity
Features
Opening appropriate for 1/2”
US conduit tting
External mounting holes
» Mounting with closed cover
» Electronics protected against
construction site pollution
» Easy and fast mounting
Electronics on the bottom of
the PCB
» Optimum protection against
mechanical damage during
installation
Heated sensing head
E+E Humidity sensor HCT01
» Protected solder pads
» Tested according to
automotive standard
AEC-Q200
Cast Electronics
» Mechanical protection
» Condensation-resistant
» Best performance and
long term stability under
continious high RH and
condensing conditions
Display
» Shows up to 3 measurands
» Backlight
Smooth cover surface
» No accumulation of dust in
protruding edges
IP65 / NEMA 4 Enclosure
Bayonet Screws
» Open/closed with a ¼ rotation
Separate T probe EE07-MT
» Intelligent, interchangeable T probe
» Remote connection possible
» Suitable for dry block calibrator
Test report according
to DIN EN 10204 – 3.1
42
v1.4 / Modification rights reserved
EE211
EE211
Page 2
Protective Sensor Coating
The E+E proprietary sensor coating is a hygroscopic layer applied to
the active surface of the HCT01 sensing element. The coating extends
substantially the life-time and the measurement performance of the E+E sensor
in corrosive environment (salts, o-shore applications). Additionally, it improves
the sensor’s long term stability in dusty, dirty or oily applications by preventing
stray impedances caused by deposits on the active sensor surface.
Operation Principle
The humidity probe is continuously heated for avoiding the eects of condensation and high humidity onto the sensing
elements, such as corrosion, high humidity drift or stray impedances. Thus, the probe heating leads to outstanding long
term stability. Based on the measured RH and T values, the EE211 calculates the dew point temperature Td whereas the
separate, interchangeable T-probe measures the ambient temperature. Ultimately, out of Td and T, the device calculates
the relative humidity RH as well as several other parameters like absolute humidity, mixing ratio, wet bulb temperature or
enthalpy.
For details on the operation principle please refer to the EE211 user guide at www.epluse.com/ee211.
Dimensions in mm (inch)
± 0,3
90
(3.54
+0.11
“)
46
(1.81“)
5
(0.2“)
101
(3.98“)
CABLE GLAND M20
80.6
(3.17“)
75 (2.9”)
(2”)
M12x1
50
Ø6
0.24“)
(
8
(0.3”)
Ø12
(0.47”)
Ø 13
34
(Ø 0.51“)
(1.34“)
Ø 12
(Ø 0.47“)
~ 55
(~2.16“)
Technical Data
Measurands
Relative Humidity (RH)
Sensor E+E Sensor HCT01-00D, protected by E+E proprietary coating
Working range 0...100 % RH
RH accuracy
non-linearity and repeatability) ±(1.3 + 0.007*measured value) % RH -5...30 °C
Temperature (T)
Sensor Pt1000 (tolerance class A, DIN EN 60751)
T-accuracy
(at 20 °C (68 °F) : ±0,1 °C)
1) Traceable to intern. standards, administrated by NIST, PTB, BEV,...
The accuracy statement includes the uncertainty of the factory calibration with an enhancement factor k=2 (2-times standard deviation).
The accuracy was calculated in accordance with EA-4/02 and with regard to GUM (Guide to the Expression of Uncertainty in Measurement).
1)
(incl. hysteresis,
± ∆°C
°C
(23...86 °F)
EE211
v1.4 / Modification rights reserved
43
Page 3
Outputs
Analogue output0-5 V / 0-10 V -1 mA < IL < 1 mA I
(RH: 0...100 %; T: see ordering guide) 0-20 mA / 4-20 mA (3-wire) R
≤ 500 Ohm R
L
Digital interface RS485, Modbus RTU, max. 32 unit load devices in one bus
General
Power supply (Class III) 15 - 35 V DC1) or 24 V AC ±20 %
Current consumption at 24 V
Voltage ouput
Current ouput
Digital interface
without Displaywith Displaywithout Displaywith Display
max.
38 mA
75 mA
typ.
23 mA
typ.
Display 1, 2 or 3 lines, user configurable, with backlight
Connection Screw terminals, max. 1.5 mm2
Enclosure material Polycarbonate, UL94V-0 (with display UL94HB) approved
T-probe material Stainless steel 1.4571
Protection class IP65 / NEMA 4
Cable gland M20 x 1.5
Electromagnetic compatibility EN61326-1
(Industrial Environment) EN61326-2-3
Temperature range Operation / storage: -40...60 °C
Temperature range with display Operation: -20...50 °C
Storage: -20...60 °C
1) USA & Canada: class 2 supply required, max. supply voltage 30V
ACDC
max.49 mA
rms
typ.85 mA
rms
typ.40 mA
rms
(-40...140 °F)
(-4...122 °F)
(-4...140 °F)
max.13 mAmax.19 mA
rms
max.34 mAmax.40 mA
rms
typ.8 mAtyp.17 mA
rms
= load current
L
= load resistor
L
Ordering Guide
Modelhumidity + temperatureM1
Output
Hardware
2)
Display
Temperature probeMetal EE07-MTAM7
Output 1
Scaling 1 low
Scaling 1 high
Output 2
Scaling 2 low
Setup analogue outputs
Scaling 2 high
Unit
Setup
RS485
1) Factory setting: Baud rate 9600, Even Parity, Stopbits 1. Other factory settings available upon request. Baud rate choice: 9600 / 19200 / 38400.
Modbus Map and communication setting: See User Guide and Modbus Application Note at www.epluse.com/ee211
2) Factory setting: For analogue output versions the display shows the measurands selected for output 1 and output 2. For digital output versions the display shows RH and T