E+E EE210 Specifications

Page 1
EE210
of BACnet International (BI). BTL is a registered trademark of BI.
Humidity and Temperature Transmitter
for Demanding Climate Control
The EE210 transmitter by E+E Elektronik meets the highest requirements in demanding climate control applications. Besides the accurate measurement of relative humidity (RH) and temperature (T), EE210 calculates various RH related parameters such as dew point, temperature, absolute humidity and mixing ratio. All measured and calculated values are available on the BACnet MS/TP or Modbus RTU interface, two of them are available on the analogue voltage or current outputs, while up to three values can be shown simultan­eously on the optional display.
Excellent performance of EE210 in polluted or aggressive environment is ensured by the encapsulated measurement electronics inside the sensing probe and the long-term stable HCT01 sensor with E+E proprietary coating.
EE210 is available as wall or duct mounted version as well as with remote probe.The IP65 / NEMA 4 enclosure minimizes installation costs and provides outstanding protection against contamination and condensation.
With an optional conguration kit, the user can set the RS485 interface parameters, the output scaling and perform one or two
point adjustment for RH and T.
Applications
agriculture
stables, incubators, hatchers
green houses
storage rooms, cooling chambers
Features
Appropriate for US mounting requirements
» Knockout for ½” conduit tting
External mounting holes
» Mounting with closed cover » Electronics protected against
construction site pollution
» Easy and fast mounting
EE210
indoor pools
demanding climate control
Display
» Selectable display layout » Measurands freely
selectable
» Backlight optional
Smooth cover surface
» No accumulation of dust
in protruding edges
Electronics on the underside of the PCB
» Optimum protection against mechanical
damage during installation
Bayonet Screws
» Open/closed with a ¼ rotation
Cast Electronics
» Mechanical protection » Condensation-resistant
E+E Humidity sensor HCT01
» Long-term stability » Protected solder pads » Tested according to automotive
standard AEC-Q200
36
IP65 / NEMA 4 Enclosure
Watertight cable outlet
BACnet is a registered trademark of ASHRAE. ASHRAE does not endorse, approve or test products for compliance with ASHRAE standards. Compliance of listed products to the requirements of ASHRAE Standard 135 is the responsibility
EE210
v2.5 / Modification rights reserved
EE210
Page 2
Protective Sensor Coating
The E+E proprietary sensor coating is a hygroscopic layer applied to the active surface of the HCT01 sensing element. The coating extends substan­tially the life-time and the measurement performance of the E+E sensor in corrosive environment (salts, off-shore applications). Additionally, it improves the sensor’s long term stability in dusty, dirty or oily applications by preventing stray impedances caused by deposits on the active sensor surface.
Technical Data
Measured Values
Relative Humidity (RH)
Sensor E+E Sensor HCT01-00D Working range 0...100 % RH RH accuracy Wall & duct version:
-15...40 °C (5...104 °F) ≤90 % RH ±(1.3 + 0.003*measured value) % RH
-15...40 °C (5...104 °F) >90 % RH ± 2.3 % RH
-40...60 °C (-40...140 °F) ±(1.5 + 0.015*measured value) % RH
Remote probe version
at 20 °C (68 °F) ±2.5 % RH
Temperature (T)
Sensor Pt1000 (tolerance class B, DIN EN 60751) integrated in HCT01
T-accuracy wall & duct remote probe
1)
(incl. hysteresis, non-linearity and repeatability)
∆ °C
∆ °C
°C
°C
Outputs
Analogue output 0-5 V / 0-10 V -1 mA < I 4-20 mA (2-wire) R
0-20 mA (3-wire) R
≤ 500 Ohm
L
≤ 500 Ohm
L
Digital output RS485 (BACnet MS/TP or Modbus RTU), max. 32 EE210 in one bus
< 1 mA
L
General
Power supply
for 4-20 mA, 2-wire 10 V + R
for 0-20 mA, 3-wire
15-35 V DC
for 0-5 V / 0-10 V / RS485
Current consumption at 24 V
Voltage output DC supply max. 12 mA; with display max. 23 mA AC supply max. 34 mA
Current output 2-wire DC supply max. 40 mA; with display max. 40 mA
3-wire DC supply typ. 33 mA; with display max. 44 mA
AC supply typ. 65 mA
Digital interface DC supply typ. 5 mA; with display max. 20 mA AC supply typ. 15 mA
1) Traceable to intern. standards, administrated by NIST, PTB, BEV,... The accuracy statement includes the uncertainty of the factory calibration with an enhancement factor k=2 (2-times standard deviation). The accuracy was calculated in accordance with EA-4/02 and with regard to GUM (Guide to the Expression of Uncertainty in Measurement).
2) USA & Canada: class 2 supply required, max. supply voltage 30 V
x 20 mA < V+ < 30 V DC
L
2)
or 24V AC ±20 %
rms
rms
rms
; with display max. 49 mA
; with display max. 84 mA
; with display max. 35 mA
rms
rms
rms
EE210
v2.5 / Modification rights reserved
37
Page 3
OUT1 OUT2
OUT1
OUT2
V
mA
V
mA
OUT1
OUT2
Display 1, 2 or 3 lines, user configurable, optional with backlight
Connection Screw terminals, max. 1.5 mm
2
Housing material Polycarbonate, UL94V-0 (with Display UL94HB) approved
Protection class IP65 / NEMA 4 Cable gland M16 x 1.5
Probe cable (type C) PVC, Ø 4.3 mm, 4 x 0.25 mm
2
, Length: 1.5 or 3 m (4.9 or 9.8 ft)
Sensor protection E+E Coating
Electromagnetic compatibility EN61326-1 EN61326-2-3
Industrial Environment Temperature ranges Operating: -40...60 °C Storage: -40...60 °C
(-40...140 °F) (-40...80 °C for remote probe EE210P)
(-40...140 °F)
Temperature ranges with display Operating: -20...50 °C (-4...122 °F) (-40...80 °C for remote probe EE210P) Storage: -20...60 °C
(-4...140 °F)
Dimensions (mm/inch)
Typ A
90
3.54
±0.3
mm
±0.11
46mm
1.81“
FOR CONDUIT INSTALLATION
Typ B
90
3.54
±0.3
mm
±0.11
Ø > 13mm
Ø > 0.51“
5mm
0.2“
~2.16“
~55mm
Typ C EE210P
Ø 12mm
Ø 0.47“
CABLE GLAND M16x1.5
80.6mm
106mm
4.17“
3.17“
34mm
1.34“
Connection Diagram
EE210-HT2/3/5 EE210-HT6
15...35 V DC
24 V AC ±20 %
Output:
0...5 V
0...10 V
0...20 mA
mA
V
mA
OUT1 OUT2
V
60
2.36
Ø > 16mm
Ø > 0.63“
15...35VDC 24VAC ±20%
20...30 V DC R
11...30 V DC RL<50 Ohm
±0.3
mm
±0.11
6mm
0.24“
GASKET
<500 Ohm
L
Output: 4...20 mA
L...according to ordering guide
19mm
0.75“
101mm
3.98“
OUT1
OUT2
EE210-HTx3
15...35 V DC
24 V AC ±20 %
38
Output: Modbus RTU or BACnet MS/TP
EE210P remote probe (for HT6/HTx3)
white
green yellow brown
v2.5 / Modification rights reserved
EE210
Page 4
Ordering Guide
MODEL OUTPUT TYPE PROBE LENGTH2)DISPLAY
humidity + (HT) 0-5 V (2x) wall mount (PA) 50 mm (1.97“) (B) without backlight4) (D) membrane (B) temperature 0-10 V (3x) duct mount (PB) 200 mm
0-20 mA (3-wire) (5x) remote probe (PC)
1)
(7.87“) (F) with backlight
Type A and C (x) none (x) for type C (x)
4-20 mA (2-wire) (6x)
RS485 (x3)
EE210-
Analogue outputs (2x, 3x, 6x) setup
OUTPUT 1 SCALING 1
relative humidity6) (Uw) -40...60 (002) relative humidity6) (Uw) -40...60 (002) metric (M) temperature (Tx) -10...50 (003) temperature (Tx) -10...50 (003) non-metric (N) dew point temperature (TD) 0...50 (004) dew point temperature (TD) 0...50 (004) frost point temperature (TF) 0...100 (005) frost point temperature (TF) 0...100 (005) water vapour partial pressure mixing ratio absolute humidity specific enthalpy
6)
(Rx) -40...140 (083) mixing ratio6) (Rx) -40...140 (083)
6)
(DV) absolute humidity6) (DV)
6)
(Hx) specific enthalpy6) (Hx)
Digital output (x3) setup
6)
(Ex) 32...122 (076) water vapour partial pressure6) (Ex) 32...122 (076)
8)
PROTOCOL BAUDRATE PARITY STOPBITS UNIT
Modbus RTU8) (1) 9600 (A) odd (O) 1 stopbit (1) metric (M) BACnet MS/TP
9)
(3) 19200 (B) even (E) 2 stopbit (2) non-metric (N)
38400 (C) no parity (N)
10)
57600
(D)
10)
76800
(E)
10)
115200
(F)
7)
OUTPUT 2 SCALING 2
Remote probe for EE210 Type C:
MODEL CABLE LENGTH FILTER
humidity + temperature (HT) 1.5 m (4.9 ft) (C) membrane (B)
3 m (9.8 ft) (E) stainless steel sintered (D)
3)
5)
(E) stainless steel sintered (D)
FILTER (Type A and B)
7)
UNIT
EE210P-
1) The EE210P probe has to be ordered as seperate position
2) Selectable probe lenght only for duct mount version available; see dimensions
3) Factory setup:
For analogue output versions the display shows the measurands selected for output 1 and output 2. For digital output versions the display shows RH and T
4) Not with output 5x
5) Not with output 6x
6) Factory Scaling relative humidity 0...100 % RH water vapour partial pressure 0...200 mbar 0...3 psi mixing ratio 0...400 g/kg 0...2800 gr/lb absolute humidity 0...150 g/m³ 0...60 gr/ft³ specific enthalpy -50...400 kJ/kg -10...190 BTU/lb
Order Examples
Type A and B Type C
EE210-HT3xPAxEB-UwTx005M
Model: Humidity+Temperature Output: 0-10 V Type: wall mount Display: with backlight Filter: membrane
Output scaling 1: relative humidity Scaling 1: 0...100 % RH Output scaling 2: temperature Scaling 2: 0...100 °C Unit: metric
7) For Tx, TD und TF; see data sheet „Scaling of the outputs“ at www.epluse.com
8) Modbus Map and setup instructions:
See User Guide and Modbus Application Note at www.epluse.com/EE210
9) Product Implementation conformance Statement (PICS) availbale at www.epluse.com/EE210
10) Only for BACnet
Position 1:
EE210-HT6xPCxxx-UwTx005M
Model: Humidity+Temperature Basic Device Output: 4-20 mA Type: remote probe (Pos. 2) Display: none
Output scaling 1: relative humidity Scaling 1: 0...100 % RH Output scaling 2: temperature Scaling 2: 0...100 °C Unit: metric
Position 2:
EE210P-HTCB
Model: Humidity+Temperature Probe Cable length: 1.5 m Filter: membrane
EE210
v2.5 / Modification rights reserved
39
Page 5
Scope of supply
EE210
EE210 according ordering guide
Cable gland
Mounting kit
Mounting ange
Inspection certicate according to DIN EN10204 - 3.1
Quick Guide -
EE210 RS485 Setup
* EE210-P is not included in the Scope of Supply of the EE210 Type C
Wall mount (Type A)
Duct mount (Type B)
Accessories
Product configuration adapter see data sheet EE-PCA Product configuration software EE-PCS (free download: www.epluse.com/EE210) Power supply adapter V03 (see data sheet Accessories) Protection cap for 12 mm probe HA010783
Remote version (Type C)*
(2 pcs.)
EE210-P
Remote probe*
for Type C
Additionally for models with
RS485 interface
40
v2.5 / Modification rights reserved
EE210