of BACnet International (BI). BTL is a registered trademark of BI.
Humidity and Temperature Transmitter
for Demanding Climate Control
The EE210 transmitter by E+E Elektronik meets the highest requirements in
demanding climate control applications. Besides the accurate measurement
of relative humidity (RH) and temperature (T), EE210 calculates various RH
related parameters such as dew point, temperature, absolute humidity and
mixing ratio. All measured and calculated values are available on the BACnet
MS/TP or Modbus RTU interface, two of them are available on the analogue
voltage or current outputs, while up to three values can be shown simultaneously on the optional display.
Excellent performance of EE210 in polluted or aggressive environment is
ensured by the encapsulated measurement electronics inside the sensing
probe and the long-term stable HCT01 sensor with E+E proprietary coating.
EE210 is available as wall or duct mounted version as well as with remote
probe.The IP65 / NEMA 4 enclosure minimizes installation costs and provides
outstanding protection against contamination and condensation.
With an optional conguration kit, the user can set the RS485 interface parameters, the output scaling and perform one or two
point adjustment for RH and T.
Applications
• agriculture
• stables, incubators, hatchers
• green houses
• storage rooms, cooling chambers
Features
Appropriate for US mounting
requirements
» Knockout for ½” conduit tting
External mounting holes
» Mounting with closed cover
» Electronics protected against
construction site pollution
» Easy and fast mounting
EE210
• indoor pools
• demanding climate control
Display
» Selectable display layout
» Measurands freely
selectable
» Backlight optional
Smooth cover surface
» No accumulation of dust
in protruding edges
Electronics on the underside of the PCB
» Optimum protection against mechanical
damage during installation
Bayonet Screws
» Open/closed with a ¼ rotation
Cast Electronics
» Mechanical protection
» Condensation-resistant
E+E Humidity sensor HCT01
» Long-term stability
» Protected solder pads
» Tested according to automotive
standard AEC-Q200
36
IP65 / NEMA 4
Enclosure
Watertight
cable outlet
BACnet is a registered trademark of ASHRAE. ASHRAE does not endorse,
approve or test products for compliance with ASHRAE standards. Compliance of
listed products to the requirements of ASHRAE Standard 135 is the responsibility
EE210
v2.5 / Modification rights reserved
EE210
Page 2
Protective Sensor Coating
The E+E proprietary sensor coating is a hygroscopic layer applied to the
active surface of the HCT01 sensing element. The coating extends substantially the life-time and the measurement performance of the E+E sensor in
corrosive environment (salts, off-shore applications). Additionally, it improves
the sensor’s long term stability in dusty, dirty or oily applications by preventing
stray impedances caused by deposits on the active sensor surface.
Technical Data
Measured Values
Relative Humidity (RH)
Sensor E+E Sensor HCT01-00D
Working range 0...100 % RH
RH accuracy
Wall & duct version:
-40...60 °C (-40...140 °F) ±(1.5 + 0.015*measured value) % RH
Remote probe version
at 20 °C (68 °F) ±2.5 % RH
Temperature (T)
Sensor Pt1000 (tolerance class B, DIN EN 60751) integrated in HCT01
T-accuracy wall & duct remote probe
1)
(incl. hysteresis, non-linearity and repeatability)
∆ °C
∆ °C
°C
°C
Outputs
Analogue output 0-5 V / 0-10 V -1 mA < I4-20 mA (2-wire) R
0-20 mA (3-wire) R
≤ 500 Ohm
L
≤ 500 Ohm
L
Digital outputRS485 (BACnet MS/TP or Modbus RTU), max. 32 EE210 in one bus
< 1 mA
L
General
Power supply
for 4-20 mA, 2-wire 10 V + R
for 0-20 mA, 3-wire
15-35 V DC
for 0-5 V / 0-10 V / RS485
Current consumption at 24 V
Voltage output DC supply max. 12 mA; with display max. 23 mA
AC supply max. 34 mA
Current output
2-wire DC supply max. 40 mA; with display max. 40 mA
3-wire DC supply typ. 33 mA; with display max. 44 mA
AC supply typ. 65 mA
Digital interface DC supply typ. 5 mA; with display max. 20 mA
AC supply typ. 15 mA
1) Traceable to intern. standards, administrated by NIST, PTB, BEV,... The accuracy statement includes the uncertainty of the factory calibration with an enhancement factor k=2
(2-times standard deviation). The accuracy was calculated in accordance with EA-4/02 and with regard to GUM (Guide to the Expression of Uncertainty in Measurement).
2) USA & Canada: class 2 supply required, max. supply voltage 30 V
x 20 mA < V+ < 30 V DC
L
2)
or 24V AC ±20 %
rms
rms
rms
; with display max. 49 mA
; with display max. 84 mA
; with display max. 35 mA
rms
rms
rms
EE210
v2.5 / Modification rights reserved
37
Page 3
OUT1OUT2
OUT1
OUT2
V
mA
V
mA
OUT1
OUT2
Display 1, 2 or 3 lines, user configurable, optional with backlight
Connection Screw terminals, max. 1.5 mm
2
Housing material Polycarbonate, UL94V-0 (with Display UL94HB) approved
Protection class IP65 / NEMA 4
Cable gland M16 x 1.5
Industrial Environment
Temperature ranges Operating: -40...60 °C
Storage: -40...60 °C
(-40...140 °F) (-40...80 °C for remote probe EE210P)
(-40...140 °F)
Temperature ranges with display Operating: -20...50 °C (-4...122 °F) (-40...80 °C for remote probe EE210P)Storage: -20...60 °C
(-4...140 °F)
Dimensions (mm/inch)
Typ A
90
3.54
±0.3
mm
±0.11
“
46mm
1.81“
FOR CONDUIT
INSTALLATION
Typ B
90
3.54
±0.3
mm
±0.11
“
Ø > 13mm
Ø > 0.51“
5mm
0.2“
~2.16“
~55mm
Typ CEE210P
Ø 12mm
Ø 0.47“
CABLE GLAND M16x1.5
80.6mm
106mm
4.17“
3.17“
34mm
1.34“
Connection Diagram
EE210-HT2/3/5EE210-HT6
15...35 V DC
24 V AC ±20 %
Output:
0...5 V
0...10 V
0...20 mA
mA
V
mA
OUT1
OUT2
V
60
2.36
Ø > 16mm
Ø > 0.63“
15...35VDC 24VAC ±20%
20...30 V DC R
11...30 V DC RL<50 Ohm
±0.3
mm
±0.11
6mm
0.24“
GASKET
“
<500 Ohm
L
Output: 4...20 mA
L...according to ordering guide
19mm
0.75“
101mm
3.98“
OUT1
OUT2
EE210-HTx3
15...35 V DC
24 V AC ±20 %
38
Output:
Modbus RTU or
BACnet MS/TP
EE210P remote probe (for HT6/HTx3)
white
green
yellow
brown
v2.5 / Modification rights reserved
EE210
Page 4
Ordering Guide
MODELOUTPUTTYPEPROBE LENGTH2)DISPLAY
humidity + (HT) 0-5 V (2x) wall mount (PA) 50 mm (1.97“)(B) without backlight4) (D) membrane (B)
temperature0-10 V (3x) duct mount (PB) 200 mm
0-20 mA (3-wire) (5x) remote probe (PC)
1)
(7.87“) (F) with backlight
Type A and C (x) none (x) for type C (x)
4-20 mA (2-wire) (6x)
RS485 (x3)
EE210-
Analogue outputs (2x, 3x, 6x) setup
OUTPUT 1SCALING 1
relative humidity6) (Uw) -40...60 (002) relative humidity6) (Uw) -40...60 (002) metric (M)
temperature (Tx) -10...50 (003) temperature (Tx) -10...50 (003) non-metric (N)
dew point temperature (TD) 0...50 (004) dew point temperature (TD) 0...50 (004)
frost point temperature (TF) 0...100 (005) frost point temperature (TF) 0...100 (005)
water vapour partial pressure
mixing ratio
absolute humidity
specific enthalpy
(3) 19200 (B) even (E) 2 stopbit (2) non-metric (N)
38400 (C) no parity (N)
10)
57600
(D)
10)
76800
(E)
10)
115200
(F)
7)
OUTPUT 2SCALING 2
Remote probe for EE210 Type C:
MODELCABLE LENGTHFILTER
humidity + temperature (HT) 1.5 m (4.9 ft) (C) membrane (B)
3 m (9.8 ft) (E) stainless steel sintered (D)
3)
5)
(E) stainless steel sintered (D)
FILTER (Type A and B)
7)
UNIT
EE210P-
1) The EE210P probe has to be ordered as seperate position
2) Selectable probe lenght only for duct mount version available; see dimensions
3) Factory setup:
For analogue output versions the display shows the measurands selected for output 1 and output 2.
For digital output versions the display shows RH and T
Output scaling 1: relative humidity
Scaling 1: 0...100 % RH
Output scaling 2: temperature
Scaling 2: 0...100 °C
Unit: metric
Position 2:
EE210P-HTCB
Model: Humidity+Temperature Probe
Cable length: 1.5 m
Filter: membrane
EE210
v2.5 / Modification rights reserved
39
Page 5
Scope of supply
EE210
EE210 according ordering guide
Cable gland
Mounting kit
Mounting ange
Inspection certicate according to
DIN EN10204 - 3.1
Quick Guide -
EE210 RS485 Setup
* EE210-P is not included in the Scope of Supply of the EE210 Type C
Wall mount
(Type A)
Duct mount
(Type B)
Accessories
Product configuration adapter see data sheet EE-PCA
Product configuration software EE-PCS (free download: www.epluse.com/EE210)
Power supply adapter V03 (see data sheet Accessories)
Protection cap for 12 mm probe HA010783
Remote version
(Type C)*
(2 pcs.)
EE210-P
Remote probe*
for Type C
Additionally for
models with
RS485 interface
40
v2.5 / Modification rights reserved
EE210
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.