E+E EE160 Specifications

EE160
B ap listed products to the re of
HVAC Humidity and Temperature Sensor
The EE160 is optimized for cost effective, accurate measurement of relative humidity (RH) and temperature (T) in building automation.
Reliable
Versatile The measured data is available on two voltage or current (2-wire) outputs, or on the RS485 interface with BACnet MS/TP or Modbus RTU protocol. Additionally, the EE160 features a passive T output.
Functional Design
EE160 is available for wall or duct mount. The IP65 / NEMA 4 enclosure minimizes installation costs and provides outstanding protection against contamination and condensation.
Comfortable Conguration and Adjustment
With an optional conguration adapter and the free EE-PCS Product Conguration Software, the user can set the RS485 interface
parameters, the output scaling and perform one or two point adjustment for RH and T.
Features
Appropriate for US mounting requirements
» Knockout for ½” conduit tting
External mounting holes
» Easy and fast mounting with
closed cover
» Electronics protected against
construction site pollution
Electronics on the underside of the board
» Optimum protection against mechanical
damage during installation
Encapsulated electronics
» Mechanical protection
» Waterproof
E+E humidity sensor HCT01
» Very robust
» Protected sensor surface and solder pads
» Tested according to automotive standard
AEC-Q200
IP65 / NEMA 4 Enclosure
Bayonet screws
» Open/close with
a ¼ rotation
56
Test report according to DIN EN 10204 – 3.1
ACnet is a registered trademark of ASHRAE. ASHRAE does not endorse,
prove or test products for compliance with ASHRAE standards. Compliance of
BACnet International (BI). BTL is a registered trademark of BI.
quirements of ASHRAE Standard 135 is the responsibility
v2.3 / Modification rights reserved
EE160
EE160
Protective Sensor Coating
The E+E proprietary sensor coating is a permeable layer applied to the active surface of the HCT01 sensing element. The coating extends substan­tially the life-time and the measurement performance of the E+E sensor in corrosive environment (salts, off-shore applications). Additionally, it improves the sensor’s long term stability in dusty, dirty or oily applications by preventing stray impedances caused by deposits on the active sensor surface.
Technical Data
Measurands
Relative humidity
Sensor E+E Sensor HCT01-00D
Working range 10...95 % RH Accuracy Temperature dependency typ. ±0.03 % RH/°C
Temperature
Sensor Pt1000 (tolerance class B, DIN EN 60751)
T-Accuracy at 20 °C ±0.3 °C
Outputs
Analogue output 0-10 V -1 mA < I (RH: 0...100%; T: see ordering guide) 4-20 mA (two-wire) R Digital interface RS485 (BACnet MS/TP or Modbus RTU) max. 32 unit load devices in one bus
Passive T-sensor 4-wire connection, see ordering guide
General
Power supply
for 0 - 10 V / RS485 15 - 35V DC or 24V AC ±20 % for 4 - 20 mA 10V + R
Typical current consumption
Connection Screw terminals, max. 1.5 mm
Housing material Polycarbonate, UL94V-0 approved Protection class IP65 / NEMA 4 Cable gland M16 x 1.5 Electromagnetic compatibility EN61326-1 EN61326-2-3 Temperature range Operation: -40...60 °C Storage: -20...60 °C (-4...140 °F)
1) Traceable to intern. standards, administrated by NIST, PTB, BEV,... The accuracy statement includes the uncertainty of the factory calibration with an enhancement factor k=2 (2-times standard deviation). The accuracy was calculated in accordance with EA-4/02 and with regard to GUM (Guide to the Expression of Uncertainty in Measurement).
1)
at 20 °C ±2.5 % RH
24V DC supply max. 40 mA 5 mA 5 mA
24V AC supply - 13 mA
< 500 Ohm
L
x 20 mA < UV < 35V DC
L
4 - 20 mA output 0 - 10 V output RS485
(-40...140 °F)
< 1 mA or
L
2
rms
15 mA
rms
EE160
v2.3/ Modification rights reserved
57
Loading...