![](/html/dc/dca2/dca2fcc0beb18307ae47b33adc9d7e9839ebc633536cdb137c498abb8fbc6fc3/bg1.png)
EE10-T / EE10-P
EE10 is the ideal solution for room temperature measurement
in residential and commercial HVAC applications. The very
stylish, snap-on enclosure allows for easy installation and
replacement of the sensing unit for service purposes.
The EE10 transmitters supply a 0-10 V or 4-20 mA output,
while the EE10 sensors have passive temperature output.
An optional LCD display is available for the EE10 transmitters.
Two different enclosure designs ensure professional
appearance according to regional standards.
Room Temperature
Transmitters and Sensors
EE10-T / EE10-P
Typical Applications
Residential and commercial building automation
Switching cabinets
Indoor climate control
Excellent price / performance ratio
Technical Data
Measuring Quantities
Temperature (active output)
Analogue output 0...50 °C (32...122 °F)
4-20 mA (two wires) R
Accuracy at 20 °C (68 °F) ±0.3 °C (±0.54 °F)
Temperature (passive output)
Type of T-Sensor please see ordering guide
General Data
Voltage supply (UV)
for 0-10 V 15-40 VDC or 24 VAC ±20 %
for 4-20 mA 28 VDC > U
Current consumption
for DC supply: typical 4 mA
for AC supply: typical 15 mA
Electrical connection Screw terminals max. 1.5 mm2 (AWG 16)
Housing material Polycarbonat
US Version: UL94V-0 approved / EU Version: UL94HB approved
Protection class PC / IP30
Display only for EE10-Tx version: temperature
CE compatibility according EN61326-1 FCC Part15 ClassB
EN61326-2-3 ICES-003 ClassB
Temperature ranges Working temperature range: -5...55 °C
Storage temperature range: -25...60 °C (-13...140 °F)
1) other scalings see datasheet „Scaling of the outputs“
1)
0-10 V -1 mA < l
< (UV-10)/0.02 < 500 Ohm
L
> 10 + 0.02 x RL (RL < 500 Ohm)
V
eff
< 1mA
L
Features
Easiest installation
Modern design
(23...131 °F)
64
v2.7 / Modification rights reserved
EE10-T
EE10-T
![](/html/dc/dca2/dca2fcc0beb18307ae47b33adc9d7e9839ebc633536cdb137c498abb8fbc6fc3/bg2.png)
Connection Diagram
EE10-T3
EE10-P
Dimensions
EE10-T6
Housing colour: cover: RAL 9003 (signal white)
back: RAL 7035 (light grey)
EU: W x H x D = 85 x 100 x 26mm (3.3 x 3.9 x 1")
US: W x H x D = 85 x 136 x 26mm (3.3 x 5.4 x 1")
Ordering Guide
MODEL OUTPUT T-SENSOR PASSIVE1)DISPLAY HOUSING T-UNIT T-SCALE
temperature active (T) 0 - 10 V (3) without display (--) Europe (--) °C (--) 0...50 (T04)
temperature passive (P) Pt100 DIN A (A) Europe (--)
4 - 20 mA (6) with display (D04) USA (US) °F (E01) -5...55 (T31)
Pt1000 DIN A (C) USA (US)
Pt1000 DIN B (D)
NTC10k (L)
Ni1000 TK6180 DIN B (J)
Ni1000 TK5000 DIN B (T)
EE10-
1) T-Sensor details see www.epluse.com/R-T_Characteristics
2) other scalings see datasheet „Scaling of the outputs“
Order Example
Passive OutputActive Output
EE10-T6D04/T04 EE10-PCUS
Model: Temperature transmitter
Output: 4-20 mA
Display: with display
T-Scale: 0...50°C
(32...122°F)
Model: Temperature sensor
T-Sensor passive: Pt1000 DIN A
Housing: USA
Scope of supply
- EE10 transmitter or sensor according ordering guide
- Mounting material
- Test report according DIN EN10204 - 2.2 (for EE10-T)
2)
0...40 (T55)
20...120 (T15)
32...132 (T96)
EE10-T
v2.7 / Modification rights reserved