USER GUIDE
EE040 – Miniature Humidity and Temperature Transmitter
SCOPE OF SUPPLY
EE040 according to the ordered type number, with mounting ange included.
CAUTION
• Avoid strong mechanical stress onto the device and mainly onto its front-end (filter side).
• Do not attempt to open the EE040 enclosure.
• For accurate measurement it is of paramount importance to avoid temperature gradients along the device. This is particularly
relevant when installing the device into a separation wall between zones with different temperature. In such a case make sure
to thermally isolate the back-end (connector side) of the device looking out of the wall.
CONNECTION DIAGRAM
Optional connecting cable:
- 2 m (6.6 ft) (HA010305)
- 5 m (16.4 ft) (HA010306)
DIMENSIONS in mm (inch)
60 (2.36")
only for duct mount
with lateral opening
35.1 (1.38")
(1.52")
38.6
43.2 (1.7")
52 (2.05")
Ø 4.4
(0.17")
48 (1.89")
Ø 24 (0.94")
MAINTENANCE
A clogged filter leads to long response time.
Periodical check of filter is recommended, especially in case of installation in polluted environment.
If cleaning of filter is necessary, plug off the device and clean the filter with soft brush.
Do not clean the filter with pressurized water.
(0.12")
3
TECHNICAL DATA
Measurands
Relative Humidity
Working range 0...100 % RH
Accuracy
Output signal (0...100 %) 0 - 2.5 V
Output load
Response time τ
< 30 s duct mount with lateral openings
1)
at 20 °C (68 °F) ± 3 % RH (30...70 % RH) ± 5 % RH (0...95 % RH)
< 45 s duct mount
63
≥ 5 kΩ
Temperature
Output signal 0 - 2.5 V
Output load ≥ 5 kΩ
Accuracy
1)
at 20 °C (68 °F) ± 0.3 °C (0.54 °F)
General Data
Supply voltage U
Current consumption typical 2 mA without load
< 3.5 mA at 5 kΩ load
Start up time typ. 4 sec.
Electrical connection appropriate for Molex 6471 (4 pins) and female crimp contacts 4809 555L
Housing material PPO – GF20, UL94HB approved
Protection class connector side: IP30
front side: IP50 (duct mount)
IP20 (duct mount with lateral openings)
CE compatibility according
Industrial environment
Working conditions T = -40…+85 °C
RH = 0…100 % (non condensing)
Storage conditions T = -40…+60 °C
RH = 0…95 % (non condensing)
5 V DC ±10%
V
2)
EN61326-1 EN61326-2-3
(-40…185 °F)
(-40…140 °F)
1) Traceable to intern. standards, administrated by NIST, PTB, BEV... . The accuracy statement includes the uncertainty of the factory calibration with an enhancement factor k=2
(2-times standard deviation). The accuracy was calculated in accordance with EA-4/02 and with regard to GUM (Guide to the Expression of Uncertainty in Measurement).
2) EE040 is not protected against surge
EMC note USA (FCC):
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with
the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is
likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
EMC note Canada (ICES-003):
CAN ICES-3 (A) / NMB-3 (A)