Edwards Signaling ZG4RB User Manual

Product information
Genesis Speaker
Table 1: Models
Description Model number
The Genesis Speaker is an audible fire alarm notification appliance designed for indoor walls. See Table 1 for a list of model numbers.
The speaker includes a field configurable switch for selecting the desired wattage tap. The wattage tap setting remains visible after final installation.
Install this device in accordance with applicable requirements in the latest editions of the NFPA codes and standards; Canadian Electrical Code, Part 1, Section 32; and in accordance with the local authorities having jurisdiction.
These instructions apply to the following model numbers:
Table 1: Models
Description Model number
Speaker, 25 Vrms, white
Speaker, 25 Vrms, white, with FIRE marking
Speaker, 70 Vrms, white
Speaker, 70 Vrms, white, with FIRE marking
Surface mount box, white
ADTG4-S2 MG4-S2 EG4-S2 XLSG4-S2 G4-S2 ZG4-S2 G4-S2-LG
ADTG4F-S2 MG4F-S2 EG4F-S2 XLSG4F-S2 G4F-S2 ZG4F-S2 G4F-S2-LG
ADTG4-S7 MG4-S7 EG4-S7 XLSG4-S7 G4-S7 ZG4-S7 G4-S7-LG
ADTG4F-S7 MG4F-S7 EG4F-S7 XLSG4F-S7 G4F-S7 ZG4F-S7 G4F-S7-LG
ADTG4B MG4B EG4B XLSG4B G4B ZG4B G4B-LG
Surface mount box, red
ADTG4RB MG4RB EG4RB XLSG4RB G4RB ZG4RB G4RB-LG
Specifications
Operating voltage: 25 Vrms (model S2), 70 Vrms (model S7) Supervisory voltage: 30 V maximum Sound level output: See Table 2 Speaker response: 400 to 4,000 Hz Wire size: 12 to 18 AWG (2.50 to 0.75 sq mm) Compatible electrical boxes
North American 4 in square electrical box, 2-1/8 in deep (UL/ULC listed flush mounted with no extension ring) Surface mount box: See Table 1
Operating environment
Temperature: 32 to 120 °F (0 to 49 °C)
Humidity: 0 to 93% RH, noncondensing at 90 °F (32 °C) Intended installation environment: Indoor dry Agency listings: Meets ULC-S541 and UL 1480 fifth edition
Table 2: Sound level output (dBA)
Wattage Output
1/4 W 80
1/2 W 83
1 W 86
2 W 89
dBA = Decibels, A-weighted UL 1480: Sound level output at 10 ft (3.05 m) measured in a
reverberant room using 400 to 4,000 Hz band limited pink noise.
ULC-S541: Meets or exceeds 85 dBA in an anechoic chamber at 10 ft (3.05 m).
Directional characteristics: Within 6 dB of on-axis sound level when measured 90° off-axis (horizontal).
Installation instructions
Caution: Electrical supervision requires the wire run to be
broken at each terminal. Do not loop the signaling circuit field wires around the terminals.
To install the speaker:
1. Remove the cover by depressing the tabs on top of the
unit by inserting a small screwdriver from the top and
twisting slightly.
2. Connect wires as shown. Strobe terminals S+ and S- are
not used for speaker only devices. See the Figure 1.
Installation Sheet 28JAN05 P/N: 3100272 REV: 3.0 Genesis Speaker 1 / 2
3. Slide the wattage switch to the desired wattage tap (2 W, 1 W, 1/2 W, or 1/4 W) by aligning it with the indicator notch below the switch. See Figure 2.
4. Mount the unit onto a compatible electrical box. See Figure 3.
5. Replace the cover by aligning it at the bottom and snapping it in at the top.
6. Test the unit for proper operation.
Input voltage matching the voltage rating of the speaker (25 or 70 Vrms)
++
To listed fire
alarm control
panel
SPKRS+C
S-
SPKRS+C
device or end of line device
S-
To next
Maintenance
This unit is not serviceable or repairable. Should the unit fail to operate, contact the supplier for replacement.
Perform a visual inspection and an operational test twice a year or as directed by the local authority having jurisdiction.
S
Figure 1: Wiring diagram
Bottom View
Figure 2: Wattage switch
Grounding plate
S
Wattage switch
Indicator notch
Standard electrical box
2
1
1/2
1/4
Surface mount box
Figure 3: Mounting diagram
Caution: With surface mount box, do not install conduit into back center knockout. Only install conduit into knockouts with grounding plate. Verify that the grounding plate provides continuity with conduit.
2 / 2 28JAN05 P/N: 3100272 REV: 3.0