Edwards Signaling Triliptical Installation Guide

Installation Instructions for Triliptical
Stackable Beacon Lighting System
TM
Description
The Edwards Triliptical Stackable Beacon Lighting System is a unique audible-visual signaling device that can contain up to 5 light modules and either a single or multiple tone module in a single "stack."
All components of the Triliptical Stackable Beacon Lighting Sys­tem are UL and cUL listed subassemblies. The units, when as­sembled, are UL and cUL listed for indoor and outdoor applica­tions. The enclosures are NEMA 3R, 4X, and IP65 rated. CE Marked Visual Signal.
The optically designed lenses are available in five colors. See Table 1. Each lens module contains a removable cover to allow for easy relamping. The lens module cover features a molded-in gasket for weather tight reliability.
The unit's bases are available in three models. Two models fea­ture shorter bases that are used when a lower profile is desired: one for surface mounting and one for pendant mounting. The other model features a larger base with a terminal block for use with an optional horn assembly. The larger base also functions as a junction box.
A pipe mount kit, Cat. No. 102PMF (sold separately) and one of three extension pipes (sold separately) allows the status indicator to be raised above the mounting surface for increased visibility. It can be used with either the Cat. No. 102TBS or Cat. No. 102PMBS mounting bases.
PLC Compatibility
The electrical input characteristics for PLC compatible signals are listed in Table 2. Signals with these characteristics may be directly connected to PLC output cards that do not exceed these input characteristics.
insulation is protected from abrasion by the gasket (without interfering with the mounting screw holes), or provide other appropriate wire insulation abrasion protection as needed.
c. Screw the pipe extension (purchased separately) into the
mounting flange.
d. Ground the flange by pulling the ground wire through
the mounting surface clearance hole and center hole of the gasket. Connect earth ground to the bottom of the base mount flange using the ground screw (G) and wire retention terminal cup washer (H).
e. Pull the remaining field wiring through center clearance
hole of mounting surface, center hole of the gasket, pipe mount flange and extension pipe.
f. Align the mounting gasket (D) and flange (A) on the
panel. Secure using (4) #10-24 x 1" (25 mm) pan head screws (B), (4) external tooth #10 star washers (E) and (4) #10-24 hex nuts (F).
g. Mount the base as instructed below.
2. Mount the base using one of the following methods:
NOTE: For indoor applications, the base may be panel
mounted or conduit mounted. For NEMA3R, 4X, and outdoor applications, it is recommended that the unit be conduit mounted vertically facing up using either the Cat. No. 102TBS or Cat. No. 102PMBS base.
a. Cat. No. 102TBS Install base on 3/4" (19 mm) conduit
(not supplied). Pull field wiring through conduit entrance hole.
b. Cat. No. 102PMBS Install base on 3/4" (19 mm) conduit
(not supplied). Pull field wiring through conduit entrance hole.
Installation
Installation must be in accordance with the latest edition of the National Electrical Code and other governing standards and codes for standard installation.
WARNINGS
To prevent electrical shock, do not connect power until instructed to do so.
To prevent abrasion of wiring insulation, ensure that wire passage holes are adequately protected.
1. If using the 102PMF mounting kit, perform the following:
NOTE: All references below are to Figure 4.
a. Using the supplied gasket (D) as a guide, mark the four
mounting holes and the center clearance hole on an appropriate surface.
b. Punch the four mounting holes. Punch the wiring
clearance hole in the mounting surface to be sufficiently larger than that in the gasket to ensure the wiring
c. Cat. No. 102DMBS Using the supplied mounting gasket
as a template, punch the four mounting holes. Punch the wiring clearance hole in the mounting surface to be sufficiently larger than that in the gasket to ensure the wiring insulation is protected from abrasion by the gasket (without interfering with the mounting screw holes), or provide other appropriate wire insulation abrasion protection as needed. Mount the base to the surface using the (2) screws (supplied).
3. Connect field wiring.
a. Cat. No. 102TBS Connect field wiring to the terminal
block as shown in Figure 1.
b. Cat. No. 102PMBS or Cat. No. 102DMBS Using wire
nuts, connect 18" (457 mm) wire leads to field wiring. The six wire leads are marked as follows: Neutral, 1 Bottom, 2, 3, 4 & 5. 1 Bottom denotes the lead for the bottom-most signal in the stack.
c. If using the optional Cat. No. 102SIGST single tone
module or Cat No. 102SIGMT multi-tone module, connect additional field wiring to the terminal block mounted on the signal assembly as shown in Figure 2.
NOTE: The tone module may be wired to sound independently
or in conjunction with a light signal.
P/N 3100669 ISSUE 1 © 2003
(1) To sound tone module independently, connect to
separate hot lead.
(2) To sound tone module with a particular light, connect
horn hot terminal to selected light terminal on Cat. 102TBS terminal block.
4. Assemble the stackable beacon lighting system (Figure 3).
a. Pull the captive key in the lens module into the "out"
position.
b. Place the first lens module on top of the base.
c. Push in the captive key to secure the lens module.
bottom of lens module, ensuring that the four prongs on the PC board are aligned with the plug located in the back of the lens assembly.
NOTE: When using LED light sources, ensure that the color of
the LED light source and the lens assembly match.
e. Place the lens assembly cover on the front of the lens
module and secure using two captive screws.
f. Repeat steps a through e for any remaining modules (up
to 5).
g. Once the last module has been assembled, place the cap
on top and secure the cap with the captive screw.
WARNING
To prevent leakage, ensure the magnifier ring on the lens cover and the magnifier ring on the lens module are aligned (Figure 3).
d. Insert the appropriate light source into board grooves at
NEUTRAL/COMMON
MODULE 1
MODULE 2
BOTTOM
Figure 1. Wiring Cat. No. 102TBS
MODULE 3
MODULE 4
MODULE 5
15"
(381mm)
WARNING
To prevent electrical shock, disconnect power to all modules. Wait 5 minutes for stored energy in strobe modules to dissipate bef ore working on unit.
5. Apply power to the unit and verify proper operation.
Cap (supplied with base)
Magnifier
Ring
1/2"
(13mm)
Board Groove
Light Source Assembly
Lens Module Cover
(2) Captive Screws
TO NEUTRAL ON CAT. 102TBS TERMINAL BLOCK
NH
SEPARATE HOT LEAD OR CONNECTED TO APPROPRIATE LIGHT MODULE TERMINAL ON CAT. 102TBS TERMINAL BLOCK
Figure 2. Wiring Cat. No. 102SIG*T
P/N 3100669 ISSUE 1
Captive Key
3 5/8"
(92mm)
Signal Base (Cat. No. 10STBS shown)
3 5/8"
(92mm)
3"
(76mm)
Figure 3. Assembling the Stackable Status Indicator (Cat. No. 102TBS shown for
illustration purposes only)
Maintenance
Light Source Replacement
1. Loosen captive screws and remove cover of affected lens module.
2. Remove the light source assembly from the lens module.
3. Install new light source assembly ensuring that the four prongs on the PC board are aligned with the plug located in the back of the lens module.
WARNING
To prevent leakage, ensure the magnifier ring on the lens cover and the magnifier ring on the lens module are aligned (Figure 3).
4. Replace lens cover and secure using two captive screws.
Cleaning
The lens surfaces should be periodically dusted and cleaned with a dry soft clean cloth to maintain optimum light visibility. If necessary, the outside of the lens may be cleaned with water and a mild detergent on a well rung-out, soft, clean cloth.
C
(4) o-rings
(4) #10-24 x 1" (25 mm)
B
pan head screws
A
Cat. No. 102PMF
Pipe mount flange
H
Wire retention
terminal cup washer
G
#10-16 x 3/8"
Pan head, thread forming,
ground ( ) screw
D
Mounting gasket
F
#10-24 Hex nut
E
External tooth
#10 Star washer
Figure 4. Optional 102PMF Mounting Kit Assembly
P/N 3100669 ISSUE 1
Table 1. Specifications
Electrical Manufacturers Replacement Lamp Life (hours)
Catalog No. Ratings Lamp Ratings Lamp Calculated#Projected
##
Base Units
102TBS-G1 24V DC, 1.75A 102TBS-N5 120V AC, 0.60A
102DMBS-G1 24V DC, 1.75A 102DMBS-N5 120V AC, 0.60A
102PMBS-G1 24V DC, 1.75A 102PMBS-N5 120V AC, 0.60A
+
+
+
+
+
+
N/A N/A N/A N/A
N/A N/A N/A N/A
N/A N/A N/A N/A
Optional Pipe Mount Flange
102PMF N/A N/A N/A N/A N / A
Optional Extension Pipes
102MP-4 N/A N / A N /A N/ A N/A 102MP-10 N/ A N / A N/ A N /A N/A 102MP-15 N/ A N / A N/ A N /A N/A
Optional Horn Assembly
102SIGST-G1 24V DC, 0.05A N/A N/A N/ A N/A
102SIGST-N5 120V AC, 0.07A 102SIGMT-G1 24V DC, 0.05A N/A N/ A N / A N/ A 102SIGMT-N5 120V AC, 0.07A
Lens Modules
102LM-* N/ A N / A N/ A N /A N/A
Light Sources
102LS-SINH-G1 24V DC, 0.32A 9 Watts 50LMP-9WH 12,000 --
or Ind. Trade 303*** 102LS-SINH-N5 120V AC, 0.11A 12 Watts 50LMP-12WH 20,000 -­102LS-SIN-G1 24V DC, 0.32A 10 Watts Ind. Trade 303 10,000 -­102LS-SIN-N5 120V AC, 0.08A 10 Watts 50LMP-10W 2,500 -­102LS-FINH-G1 24V DC, 0.32A 9 Watts 50LMP-9WH 12,000 15,000
or Ind. Trade 303*** 102LS-FINH-N5 120V AC, 0.11A 12 Watts 50LMP-12WH 20,000 25,000
102LS-FIN-G1 24V DC, 0.32A 10 Watts Ind. Trade 303 10,000 12,500 102LS-FIN-N5 120V AC, 0.08A 10 Watts 50LMP-10W 2,500 3,000 102LS-ST-G1 24V DC, 0.30A 3 Joule Strobe -- 3,000 102LS-ST-N5 120V AC, 0.12A 3 Joule Strobe -- 3,000
###
###
--
--
102LS-SLEDA-G1** 24V DC, 0.062A -- N/A 100,000 -­102LS-SLEDB-G1** 102LS-SLEDG-G1** 102LS-SLEDR-G1**
102LS-SLEDA-N5** 120V AC, 0.022A -- N/A 100,000 -­102LS-SLEDB-N5** 102LS-SLEDG-N5** 102LS-SLEDR-N5**
102LS-FLEDA-G1** 24V DC, 0.062A -- N/A 100,000 -­102LS-FLEDB-G1** 102LS-FLEDG-G1** 102LS-FLEDR-G1**
102LS-FLEDA-N5** 120V AC, 0.022A -- N/A 100,000 -­102LS-FLEDB-N5** 102LS-FLEDG-N5** 102LS-FLEDR-N5**
+
Currents shown are for a stackable indicator with 5 light modules. *Signifies lens module color (A - amber/orange, B - blue, C - clear, G - green, R - red, Y - yellow) **Signifies lens and LED module color (A - amber/orange, B - blue, G - green, R - red)
NOTE: LED light sources must be used with the
corresponding color lens module (e.g., a blue LED light source, 102LS-SLEDB-G1, must be used with a blue lens, 102LM-B).
***A non-halogen lamp, as listed, may be used in place of the halogen lamp.
#
At nominal operating voltage.
##
Projected lamp life based on manufacturer's calculated lamp life @ 65 fpm and 50% duty cycle.
###
Strobe tube life @ operating power to 75% ef ficiency.
P/N 3100669 ISSUE 1
Table 2. PLC Compatibility
Operating Maximum off state Continuous on Surge (inrush/duration)
Cat. No. voltage* leakage current (mA) current (mA) (A/ms**)
102SIGST-G1 24V DC 5 50 0.24/0.2 102SIGST-N5 120V AC 5 70 0.35/0.5 102SIGMT-G1 24V DC 5 50 0.24/0.2 102SIGMT-N5 120V AC 5 70 0.35/0.5 102LS-SIN-G1 24V DC 25 32 0.36/1 102LS-SIN-N5 120V AC 25 80 0.15/8 102LS-SINH-G1 24V DC 25 320 0.36/1 102LS-SINH-N5 120V AC 25 110 0.5/8 102LS-FIN-G1 24V DC 25 32 1.4/100 102LS-FIN-N5 120V AC 25 80 0.3/8 102LS-FINH-G1 24V DC 25 320 1.2/100 102LS-FINH-N5 120V AC 25 110 1.15/8 102LS-ST-G1 24V DC 1.5 300 0.33/1 102LS-ST-N5 120V AC 5 120 50/1 102LS-SLED( )-G1 24V DC 5 65 0.07/1 102LS-SLED( )-N5 120V AC 5 25 0.09/8 102LS-FLED( )-G1 24V DC 5 65 0.07/1 102LS-FLED( )-N5 120V AC 5 25 0.09/8 *All AC volts at 60 Hz
**Amps/milliseconds
P/N 3100669 ISSUE 1
Installation Instructions for Triliptical
TM
Stackable Beacon Lighting System Light Sources
Description
The Edwards Triliptical Stackable Beacon Lighting System is a unique audible-visual signaling device that can contain up to 5 light modules and either a single or multiple tone module in a single "stack."
All components of the Triliptical Stackable Beacon Lighting System are UL and cUL listed subassemblies. The units, when assembled, are UL and cUL listed for indoor and outdoor applications and CSA certified. The enclosures are NEMA 3R, 4X and IP65 rated. CE Marked Visual Signal.
Each light source module contains a removable cover to allow for easy relamping. The light module cover features a molded-in gas­ket for dust tight reliability.
WARNING
To prevent electrical shock, do not connect power until instructed to do so.
Installation
c. Place the lens module cover on the front of the lens module
and secure using two captive screws.
d. Repeat steps a through c for any remaining modules (up
to 5).
e. Once the last module has been assembled, place the cap
on top and secure the cap with the captive screw.
2. Apply power to the unit and verify proper operation.
NOTE: For further installation details, see the instructions supplied
with the lens modules, P/N 3100700, or the instructions supplied with the base, P/N 3100669.
Maintenance
WARNING
To prevent electrical shock, disconnect power to all modules. Wait 5 minutes for stored energy in strobe modules to dissipate working on unit.
Light Source Replacement
1. Loosen captive screws and remove cover of affected lens module.
Installation must be in accordance with local codes.
1. Assemble the stackable beacon lighting system (Figure 1). a. Loosen captive screws and remove cover of affected lens
module.
b. Insert the appropriate light source into board grooves at
bottom of lens ensuring that the four prongs on the PC board are aligned with the plug located in the back of the lens assembly.
NOTE: When using LED light sources, ensure that the color of the
LED light source and the color of the lens assembly match.
WARNING
To prevent leakage, ensure the magnifier ring on the lens cover and the magnifier ring on the lens module are aligned (Figure 1).
2. Remove the light source assembly from the lens module.
3. Install new light source assembly ensuring that the four prongs on the PC board are aligned with the plug located in the back of the lens module.
WARNING
To prevent leakage, ensure the magnifier ring on the lens cover and the magnifier ring on the lens module are aligned (Figure 1).
4. Replace lens cover and secure using two captive screws.
Cleaning
The lens surfaces should be periodically dusted and cleaned with a dry soft clean cloth to maintain optimum light visibility. If neces­sary, the outside of the lens may be cleaned with water and a mild detergent on a well rung out soft clean cloth.
P/N 3100701 ISSUE 2 © 2003
Cap (supplied with base)
Magnifier
Ring
Board Groove
(2) Captive
Light Source Assembly
Screws
Figure 1. Assembling the Stackable Beacon Lighting System
Table 1. Specifications
Lens Module Cover
Electrical Lamp Replacement Lamp Life (hours)
Catalog No. Ratings Ratings Lamp Calculated#Projected
##
Light Sources
102LS-SINH-G1 24V DC, 0.32A 9 Watts, 52 Lumens 50LMP-9WH 12,000 --
or Ind. Trade 303** 102LS-SINH-N5 120V AC, 0.11A 12 Watts, 70 Lumens 50LMP-12WH 20,000 -­102LS-SIN-G1 24V DC, 0.32A 10 Watts Ind. Trade 303 10,000 -­102LS-SIN-N5 120V AC, 0.08A 10 Watts 50LMP-10W 2,500 -­102LS-FINH-G1 24V DC, 0.32A 9 Watts 50LMP-9WH 12,000 15,000
or Ind. Trade 303** 102LS-FINH-N5 120V AC, 0.11A 12 Watts 50LMP-12WH 20,000 25,000 102LS-FIN-G1 24V DC, 0.32A 10 Watts Ind. Trade 303 10,000 12,500 102LS-FIN-N5 120V AC, 0.08A 10 Watts 50LMP-10W 2,500 3,000 102LS-ST-G1 24V DC, 0.30A 3 Joule Strobe -- 3,000 102LS-ST-N5 120V AC, 0.12A 3 Joule Strobe -- 3,000
### ###
--
--
102LS-SLEDA-G1* 24V DC, 0.062A -- N/A 100,000 -­102LS-SLEDB-G1* 102LS-SLEDG-G1* 102LS-SLEDR-G1*
102LS-SLEDA-N5* 120V AC, 0.022A -- N/A 100,000 -­102LS-SLEDB-N5* 102LS-SLEDG-N5* 102LS-SLEDR-N5*
102LS-FLEDA-G1* 24V DC, 0.062A -- N/A 100,000 -­102LS-FLEDB-G1* 102LS-FLEDG-G1* 102LS-FLEDR-G1*
102LS-FLEDA-N5* 120V AC, 0.022A -- N/A 100,000 -­102LS-FLEDB-N5* 102LS-FLEDG-N5* 102LS-FLEDR-N5*
*Signifies lens and LED module color (A - amber, B - blue, G - green, R - red) NOTE: LED light sources must be used with the
corresponding color lens module (e.g., a blue LED light source, 102LS-SLEDB-N5, must be used with a blue lens, 102LM-B).
**A non-halogen lamp, as listed, may be used in place of the halogen lamp.
#
At nominal operating voltage.
##
Projected lamp life based on manufacturer's calculated lamp life @ 65 fpm and 50% duty cycle.
##
Strobe tube life @ operating power to 75% efficiency.
P/N 3100701 ISSUE 2
Installation Instructions for Mounting Flange Kit
for use with the 102 Series Triliptical
TM
Stackable Status Indicator
Contents
A (1) 102PMF pipe mount flange B (4) #10-24 x 1" (25 mm) pan head, phillips screws C (4) o-rings D (1) mounting gasket E (4) external tooth #10 star washers F (4) #10-24 hex nuts G (1) green #10-16 x 3/8" pan head, thread forming ground
screw
H (1) brass terminal cup washer
Accessories
102MP-4 4" Extension Pipe 102MP-10 10" Extension Pipe 102MP-15 15" Extension Pipe
Description
The Edwards Triliptical Stackable Beacon Lighting System is a unique audible-visual signaling device that can contain up to 5 light modules and either a single or multiple tone module in a single "stack."
The pipe mount flange, 102PMF, and one of the thr ee extension pipes (sold separately) allow the status indicator to be raised above the mounting surface for increased visibility. It can be used with either the Cat. No. 102TBS or Cat. No. 102PMBS mounting bases.
Installation
Installation must be in accordance with the latest edition of the National Electrical Code and other governing standards and codes for standard installation.
1. Panel mount the 102PMF pipe mount flange (A) as follows. a. Using the supplied gasket (D) as a guide, mark the four
mounting holes and the center clearance hole on an appropriate surface.
b. Punch the four mounting holes. Punch the wiring
clearance hole in the mounting surface to be sufficiently larger than that in the gasket to ensure the wiring insulation is protected from abrasion by the gasket (without interfering with the mounting screw holes), or provide other appropriate wire insulation abrasion protection as needed.
c. Screw the pipe extension (purchased separately) into the
mounting flange.
d. Ground the flange by pulling the ground wire through
the mounting surface clearance hole and center hole of the gasket. Connect earth ground to the bottom of the base mount flange using the ground screw (G) and wire retention terminal cup washer (H).
e. Pull the remaining field wiring through center clearance
hole of mounting surface, center hole of the gasket, pipe mount flange and extension pipe.
f. Align the mounting gasket (D) and flange (A) on the
panel. Secure using (4) #10-24 x 1" (25 mm) pan head screws (B), (4) external tooth #10 star washers (E) and (4) #10-24 hex nuts (F). See Figure 1.
2. Mount the base as follows. a. Install either Cat. No. 102TBS or Cat. No. 102PMBS
base on 3/4" (19 mm) conduit (not supplied). Pull field wiring through conduit entrance hole.
3. Connect field wiring as instructed in the installation instructions, P/N 500002, provided with themounting base.
4. Assemble the stackable beacon lighting system as described in the installation instructions provided with either the mounting base or the appropriate components.
WARNINGS
To prevent electrical shock, do not connect power until instructed to do so.
To prevent abrasion of wiring insulation, ensure that wire passage holes are adequately protected.
P/N 500034 ISSUE 2 © 1998
C
(4) o-rings
(4) #10-24 x 1" (25 mm)
B
pan head screws
A
Cat. No. 102PMF
Pipe mount flange
H
Wire retention
terminal cup washer
G
#10-16 x 3/8"
Pan he a d , thread form i ng,
ground ( ) screw
Mounting g a s ket
#10-24 Hex nut
P/N 500034 ISSUE 2
D
E
External tooth
#10 Star washer
F
Figure 1. Mounting Kit Assembly
Installation Instructions for 102 Series Triliptical
®
DeviceNet Stackable Beacon Lighting System
DescriptionDescription
Description
DescriptionDescription
The Edwards Triliptical DeviceNet Stackable Beacon Lighting System is a unique audible-visual signaling device that can contain up to 5 light modules and a multiple tone module in a single "stack."
All components of the Lighting System are UL listed subassemblies and cUL Listed. The enclosures are Type 3R, Type 4X and IP65 Rated. The unit has been tested by ODVA's authorized independent test lab and found to comply with ODVA conformance test software.
The optically designed lenses are available in five colors. Each lens module contains a removable cover to allow for easy relamping. The lens module cover features a molded-in gasket for weather tight reliability.
The Lighting System's base is supplied with a terminal block and may be used with an optional horn assembly. See Tables 1 and 2 for specification information.
NOTE: The DeviceNet Electronic Data Sheet is available on the Edwards Signaling website at:
http://www.edwards-signals.com/index.cfm?Level=147&PG=3&PID=19. Scroll down to "Installation Instructions" and click on "102 DeviceNet Electronic Data Sheet"
Device Profile
Revision 1.00 Firmware Revision 1.02
The DeviceNet interface is in the Triliptical DeviceNet Base, 102TBS-DN. The base interfaces between the network and all installed stacklight modules.
The Triliptical DeviceNet Stackable Beacon is a slave device. It is a general purpose status indicator designed to indicate the status of a machine or process.
The Triliptical DeviceNet Stackable Beacon has LED, halogen, incandescent or strobe light sources which display the status of the machine or the process. The power required to drive the lamps is supplied separately from the bus power for the 120V AC (N5) version. DC power for the 24V DC (G1) version may be taken locally or from the DeviceNet Network. A standard open style 2 pin connector is used to connect 24V DC @ 1.75A (max) or 120V AC at
0.6A (max) to drive the 5 light sources.
The unisolated physical layer contains DeviceNet required mis-wiring protection circuitry. A standard open style (unsealed) 5 pin connector is used to connect the Stackable Beacon to the DeviceNet bus. The current draw from the bus is 0.12A for both the AC and DC versions.
The Triliptical DeviceNet Stackable Beacon contains a preprogrammed microcontroller which implements the Group 2 pre-defined Master/Slave Connection Set. This allows for one Explicit Messaging Connection and one Poll Connec­tion. The objects (classes) supported are described in the next section. The Stackable Beacon resets automatically when DeviceNet power is applied.
1.0 Object Model
1.1 Object Present in the 102TBS-DN:
OBJECT Optional/Required # of Instances
Identity (1) Required 1 Message Router (2) Required 1 Devicenet (3) Required 1 Assembly (4) Required 1 Connection (5) Required 1
1.2 Object that Effect Behavior:
OBJECT Effect on Behavior
Identity (1) Supports the reset service Message Router (2) No effect Devicenet (3) Configures port attributes Assembly (4) I/O assembly for lamps Connection (5) Establishes the number of connections
P/N 3100125 ISSUE 3 © 2003
PAGE 1
1.3 Object Interfaces:
OBJECT Effect on Behavior
Identity (1) Message router Message Router (2) Explicit message connection instance Devicenet (3) Message router Assembly (4) I/O connection or message router Connection (5) Message router
1.4 Identification of I/O Assembly Interfaces:
Instance Number Type Name
1 Input/Output Lamps ON/OFF, Lamp diagnostics, and sounder control
1.5 Format of I/O Assembly data Attribute:
Input to the DeviceNet bus as a response to the poll command from master node.
Data Byte 0 value indicates the lamp is OK or it is either burned out or missing.
Data Byte 1 value indicates the lamp was on or off when last poll command was received.
Data Byte 2 value indicates the current sounder module control value.
For Units Configured with 5 Light Modules
BYTE BIT7 BIT6 BIT5 BIT4 BIT3 BIT2 BIT1 BIT0
0 PWR FAIL DON'T DON'T LMP 5 LMP 4 LMP 3 LMP 2 LMP 1
1=PWR LOST CARE CARE 1 = REP 1 = REP 1 = REP 1 = REP 1 = REP 2=PWR OK 0 = OK 0 = OK 0 = OK 0 = OK 0 = OK
1 DON'T DON'T DON'T LMP 5 LMP 4 LMP 3 LMP 2 LMP 1
CARE CARE CARE 1 = ON 1 = ON 1 = ON 1 = ON 1 = ON
0 = OFF 0 = OFF 0 = OFF 0 = OFF 0 = OFF
2 DON'T DON'T DON'T DON'T Sounder Tone Tone Tone
CARE CARE CARE CARE 1 = ON MSB LSB
0 = OFF
For Units Configured with 4 Light Modules
BYTE BIT7 BIT6 BIT5 BIT4 BIT3 BIT2 BIT1 BIT0
0 PWR FAIL DON'T DON'T DON'T LMP 4 LMP 3 LMP 2 LMP 1
1=PWR LOST CARE CARE CARE 1 = REP 1 = REP 1 = REP 1 = REP 2=PWR OK 0 = OK 0 = OK 0 = OK 0 = OK
1 DON'T DON'T DON'T DON'T LMP 4 LMP 3 LMP 2 LMP 1
CARE CARE CARE CARE 1 = ON 1 = ON 1 = ON 1 = ON
0 = OFF 0 = OFF 0 = OFF 0 = OFF
2 DON'T DON'T DON'T DON'T Sounder Tone Tone Tone
CARE CARE CARE CARE 1 = ON MSB LSB
0 = OFF
P/N 3100125 ISSUE 3 PAGE 2
For Units Configured with 3 Light Modules
BYTE BIT7 BIT6 BIT5 BIT4 BIT3 BIT2 BIT1 BIT0
0 PWR FAIL DON'T DON'T DON'T DON'T LMP 3 LMP 2 LMP 1
1=PWR LOST CARE CARE CARE CARE 1 = REP 1 = REP 1 = REP 2=PWR OK 0 = OK 0 = OK 0 = OK
1 DON'T DON'T DON'T DON'T DON'T LMP 3 LMP 2 LMP 1
CARE CARE CARE CARE CARE 1 = ON 1 = ON 1 = ON
0 = OFF 0 = OFF 0 = OFF
2 DON'T DON'T DON'T DON'T Sounder Tone Tone Tone
CARE CARE CARE CARE 1 = ON MSB LSB
0 = OFF
For Units Configured with 2 Light Modules
BYTE BIT7 BIT6 BIT5 BIT4 BIT3 BIT2 BIT1 BIT0
0 PWR FAIL DON'T DON'T DON'T DON'T DON'T LMP 2 LMP 1
1=PWR LOST CARE CARE CARE CARE CARE 1 = REP 1 = REP 2=PWR OK 0 = OK 0 = OK
1 DON'T DON'T DON'T DON'T DON'T DON'T LMP 2 LMP 1
CARE CARE CARE CARE CARE CARE 1 = ON 1 = ON
0 = OFF 0 = OFF
2 DON'T DON'T DON'T DON'T Sounder Tone Tone Tone
CARE CARE CARE CARE 1 = ON MSB LSB
0 = OFF
For Units Configured with 1 Light Module
BYTE BIT7 BIT6 BIT5 BIT4 BIT3 BIT2 BIT1 BIT0
0 PWR FAIL DON'T DON'T DON'T DON'T DON'T DON'T LMP 1
1=PWR LOST CARE CARE CARE CARE CARE CARE 1 = REP 2=PWR OK 0 = OK
1 DON'T DON'T DON'T DON'T DON'T DON'T DON'T LMP 1
CARE CARE CARE CARE CARE CARE CARE 1 = ON
0 = OFF
2 DON'T DON'T DON'T DON'T Sounder Tone Tone Tone
CARE CARE CARE CARE 1 = ON MSB LSB
0 = OFF
P/N 3100125 ISSUE 3PAGE 3
Output to the 102TBS-DN with the poll command from master node.
Data Byte 0 value indicates the lamps to be turned ON or OFF.
Data Byte 1 value indicates the ON lamps to be Steady ON or Flashing and the Flashing rate (45, 60 or 80 flashes per minute) selected. Strobe units should always be set to Steady ON.
Data Byte 2 value indicates the sounder to be turned ON or OFF and the tone to be chosen.
For Units Configured with 5 Light Modules
BYTE BIT7 BIT6 BIT5 BIT4 BIT3 BIT2 BIT1 BIT0
0 DON'T DON'T DON'T LMP 5 LMP 4 LMP 3 LMP 2 LMP 1
CARE CARE CARE 1 = ON 1 = ON 1 = ON 1 = ON 1 = ON
0 = OFF 0 = OFF 0 = OFF 0 = OFF 0 = OFF
1 0 0 1 LMP 5 LMP 4 LMP 3 LMP 2 LMP 1
45 1 = FLSH 1 = FLSH 1 = FLSH 1 = FLSH 1 = FLSH FPM 0 = STDY 0 = STDY 0 = STDY 0 = STDY 0 = STDY
1 0 1 0 LMP 5 LMP 4 LMP 3 LMP 2 LMP 1
60 1 = FLSH 1 = FLSH 1 = FLSH 1 = FLSH 1 = FLSH FPM 0 = STDY 0 = STDY 0 = STDY 0 = STDY 0 = STDY
1 1 DON'T DON'T LMP 5 LMP 4 LMP 3 LMP 2 LMP 1
80 CARE CARE 1 = FLSH 1 = FLSH 1 = FLSH 1 = FLSH 1 = FLSH FPM 0 = STDY 0 = STDY 0 = STDY 0 = STDY 0 = STDY
1 0 0 0 LMP 5 LMP 4 LMP 3 LMP 2 LMP 1
80 FPM 80 FPM 80 FPM 1 = FLSH 1 = FLSH 1 = FLSH 1 = FLSH 1 = FLSH DEFLT DEFLT DEFLT 0 = STDY 0 = STDY 0 = STDY 0 = STDY 0 = STDY
2 DON'T DON'T DON'T DON'T Sounder Tone Tone Tone
CARE CARE CARE CARE 1 = ON MSB LSB
0 = OFF
For Units Configured with 4 Light Modules
BYTE BIT7 BIT6 BIT5 BIT4 BIT3 BIT2 BIT1 BIT0
0 DON'T DON'T DON'T DON'T LMP 4 LMP 3 LMP 2 LMP 1
CARE CARE CARE CARE 1 = ON 1 = ON 1 = ON 1 = ON
0 = OFF 0 = OFF 0 = OFF 0 = OFF
1 0 0 1 DON'T LMP 4 LMP 3 LMP 2 LMP 1
45 CARE 1 = FLSH 1 = FLSH 1 = FLSH 1 = FLSH FPM 0 = STDY 0 = STDY 0 = STDY 0 = STDY
1 0 1 0 DON'T LMP 4 LMP 3 LMP 2 LMP 1
60 CARE 1 = FLSH 1 = FLSH 1 = FLSH 1 = FLSH FPM 0 = STDY 0 = STDY 0 = STDY 0 = STDY
1 1 DON'T DON'T DON'T LMP 4 LMP 3 LMP 2 LMP 1
80 CARE CARE CARE 1 = FLSH 1 = FLSH 1 = FLSH 1 = FLSH FPM 0 = STDY 0 = STDY 0 = STDY 0 = STDY
1 0 0 0 DON'T LMP 4 LMP 3 LMP 2 LMP 1
80 FPM 80 FPM 80 FPM CARE 1 = FLSH 1 = FLSH 1 = FLSH 1 = FLSH DEFLT DEFLT DEFLT 0 = STDY 0 = STDY 0 = STDY 0 = STDY
2 DON'T DON'T DON'T DON'T Sounder Tone Tone Tone
CARE CARE CARE CARE 1 = ON MSB LSB
0 = OFF
P/N 3100125 ISSUE 3 PAGE 4
For Units Configured with 3 Light Modules
BYTE BIT7 BIT6 BIT5 BIT4 BIT3 BIT2 BIT1 BIT0
0 DON'T DON'T DON'T DON'T DON'T LMP 3 LMP 2 LMP 1
CARE CARE CARE CARE CARE 1 = ON 1 = ON 1 = ON
0 = OFF 0 = OFF 0 = OFF
1 0 0 1 DON'T DON'T LMP 3 LMP 2 LMP 1
45 CARE CARE 1 = FLSH 1 = FLSH 1 = FLSH FPM 0 = STDY 0 = STDY 0 = STDY
1 0 1 0 DON'T DON'T LMP 3 LMP 2 LMP 1
60 CARE CARE 1 = FLSH 1 = FLSH 1 = FLSH FPM 0 = STDY 0 = STDY 0 = STDY
1 1 DON'T DON'T DON'T DON'T LMP 3 LMP 2 LMP 1
80 CARE CARE CARE CARE 1 = FLSH 1 = FLSH 1 = FLSH FPM 0 = STDY 0 = STDY 0 = STDY
1 0 0 0 DON'T DON'T LMP 3 LMP 2 LMP 1
80 FPM 80 FPM 80 FPM CARE CARE 1 = FLSH 1 = FLSH 1 = FLSH DEFLT DEFLT DEFLT 0 = STDY 0 = STDY 0 = STDY
2 DON'T DON'T DON'T DON'T Sounder Tone Tone Tone
CARE CARE CARE CARE 1 = ON MSB LSB
0 = OFF
For Units Configured with 2 Light Modules
BYTE BIT7 BIT6 BIT5 BIT4 BIT3 BIT2 BIT1 BIT0
0 DON'T DON'T DON'T DON'T DON'T DON'T LMP 2 LMP 1
CARE CARE CARE CARE CARE CARE 1 = ON 1 = ON
0 = OFF 0 = OFF
1 0 0 1 DON'T DON'T DON'T LMP 2 LMP 1
45 CARE CARE CARE 1 = FLSH 1 = FLSH FPM 0 = STDY 0 = STDY
1 0 1 0 DON'T DON'T DON'T LMP 2 LMP 1
60 CARE CARE CARE 1 = FLSH 1 = FLSH FPM 0 = STDY 0 = STDY
1 1 DON'T DON'T DON'T DON'T DON'T LMP 2 LMP 1
80 CARE CARE CARE CARE CARE 1 = FLSH 1 = FLSH FPM 0 = STDY 0 = STDY
1 0 0 0 DON'T DON'T DON'T LMP 2 LMP 1
80 FPM 80 FPM 80 FPM CARE CARE CARE 1 = FLSH 1 = FLSH DEFLT DEFLT DEFLT 0 = STDY 0 = STDY
2 DON'T DON'T DON'T DON'T Sounder Tone Tone Tone
CARE CARE CARE CARE 1 = ON MSB LSB
0 = OFF
P/N 3100125 ISSUE 3PAGE 5
For Units Configured with 1 Light Module
BYTE BIT7 BIT6 BIT5 BIT4 BIT3 BIT2 BIT1 BIT0
0 DON'T DON'T DON'T DON'T DON'T DON'T DON'T LMP 1
CARE CARE CARE CARE CARE CARE CARE 1 = ON
0 = OFF
1 0 0 1 DON'T DON'T DON'T DON'T LMP 1
45 CARE CARE CARE CARE 1 = FLSH FPM 0 = STDY
1 0 1 0 DON'T DON'T DON'T DON'T LMP 1
60 CARE CARE CARE CARE 1 = FLSH FPM 0 = STDY
1 1 DON'T DON'T DON'T DON'T DON'T DON'T LMP 1
80 CARE CARE CARE CARE CARE CARE 1 = FLSH FPM 0 = STDY
1 0 0 0 DON'T DON'T DON'T DON'T LMP 1
80 FPM 80 FPM 80 FPM CARE CARE CARE CARE 1 = FLSH DEFLT DEFLT DEFLT 0 = STDY
2 DON'T DON'T DON'T DON'T Sounder Tone Tone Tone
CARE CARE CARE CARE 1 = ON MSB LSB
0 = OFF
2.0 Standard Objects.
2.1 Identity Object (Class ID = 1).
There is a single instance of the identity object for the Triliptical DeviceNet Stackable Beacon. No class attributes are supported. All of the instance attributes are contained in rom and are gettable but not settable. The table below shows the values.
ATTRIBUTE ACCESS DATA
ID RULES NAME TYPE VALUE
1 Get Vendor Code Uint 0x201 (513) 2 Get Product Type Uint 0x0000 3 Get Product Code Uint 0x0001 4 Get Revision Word 01.01 5 Get Status UDINT 0x0000 6 Get Serial # Uint UNIQUE SERIAL # 7 Get Product Name STRUCT 102
Identity Object Services:
SERVICE SERVICE CODE PARAMETERS
Get Attribute Single 0x0E Attribute ID Reset 0x05 0, 1
2.2 Message Router Object (Class ID = 2).
There is no externally visible interface to the Message Router Object.
2.3 DeviceNet Object (Class ID = 3).
There is a single instance of the DeviceNet Object for the Triliptical DeviceNet Stackable Beacon.
DeviceNet Object Class Attributes:
ATTRIBUTE ACCESS DATA
ID RULES NAME TYPE VALUE
1 Get Revision Uint 0x0002
P/N 3100125 ISSUE 3 PAGE 6
DeviceNet Object Class Services:
SERVICE SERVICE CODE PARAMETERS
Get Attribute Single 0x0E Attribute ID
DeviceNet Object Instance Attributes:
ATTRIBUTE ACCESS DATA
ID RULES NAME TYPE VALUE
1 Get Macid Uint Dipswitch 2 Get Baud rate USINT Dipswitch 3 Get BOI BOOL 0x01 Auto-Reset 0x00 Hold 4 Get/Set Bus off counter USINT 0x00 (Set) Value (Get) 5 Get Allocation info STRUCT Allocate Serv
DeviceNet Object Instance Services:
SERVICE SERVICE CODE PARAMETERS
Get Attribute Single 0x0E Attribute ID Set Attribute Single 0x10 Attribute ID Allocate 0x4B Allocation Choice Master MACID Release 0x4C Release Choice
2.4 Assembly Object (Class ID = 4)
There is a single instance of the Assembly Object for the Triliptical DeviceNet Stackable Beacon. No class attributes or services are supported for the Assembly Class.
Assembly Object Instance Attributes:
ATTR ACCESS DATA
ID RULES NAME TYPE VALUE
3 Get/Set Data Struct See Sect 1.5
Assembly Object Instance Services:
SERVICE SERVICE CODE PARAMETERS
Get Attribute Single 0x0E Attribute ID Set Attribute Single 0x10 Attribute ID
P/N 3100125 ISSUE 3PAGE 7
2.5 Connection Object (Class ID = 5).
There are two instances of the Connection object in the 102TBS-DN. Instance #1 is assigned to the Explicit Messaging Connection. Instance #2 is assigned to the Polled I/O Connection. The following table shows the attributes and the pre-defined values where applicable. No class attributes are supported.
Connection Object - Explicit Message Connection (Instance #1)
ATTR ACCESS DATA
ID RULES NAME TYPE VALUE
1 Get State USINT 0x03 2 Get Instance type USINT 0x00 3 Get Xport class trigger USINT 0x83 4 Get Produced CONN. ID UINT 0x5FB for MACID 63 5 Get Consumed CONN. ID UINT 0x5FC for MACID 63 6 Get Initial COMM. Characteristics UINT 0x21 7 Get Produced CONN. size UINT 0x0007 8 Get Consumed CONN. size UINT 0x0007
9 Get/Set Expected packet rate UINT Application dependent 10 N/A N/A N/A Not used 11 N/A N/A N/A Not used 12 Get/Set Watchdog timeout action USINT 0x01 Default 13 Get Produced path length UINT 0x0000 14 Get Produced path ARRAY OF USINT <NULL> 15 Get Consumed path length UINT 0x0000 16 Get Consumed path ARRAY of USINT <NULL>
Connection Object - Poll I/O Message Connection (Instance #2)
ATTR ACCESS DATA
ID RULES NAME TYPE VALUE
1 Get State USINT State Dependent
2 Get Instance type USINT 0x01
3 Get Xport class trigger USINT 0x82
4 Get Produced CONN. ID UINT 0x3FF for MACID 63
5 Get Consumed CONN. ID UINT 0x5FD for MACID 63
6 Get Initial COMM. Characteristics UINT 0x01
7 Get/Set Produced CONN. size UINT 0x03
8 Get/Set Consumed CONN. size UINT 0x03
9 Get/Set Expected packet rate UINT Application dependent 10 N/A N/A N/A Not used 11 N/A N/A N/A Not used 12 Get/Set Watchdog timeout action USINT (0x00 Default) 0, 1, 2 13 Get Produced path length UINT 0x0006 14 Get Produced path ARRAY OF USINT 20.04.24.01.30.03 15 Get Consumed path length UINT 0x0006 16 Get Consumed path ARRAY of USINT 20.04.24.01.30.03
Connection Object Services:
SERVICE SERVICE CODE PARAMETERS
Get Attribute Single 0x0E Attribute ID Set Attribute Single 0x10 Attribute ID
P/N 3100125 ISSUE 3 PAGE 8
InstallationInstallation
Installation
InstallationInstallation
WARNING
To prevent electrical shock, do not connect po wer until instructed to do so.
Safety Message to Installers, Users, and Maintenance Personnel
The Triliptical DeviceNet Status Indicator must be installed in accordance with the latest edition of the National Electrical Code and/or other applicable local regulations, by a trained and qualified electrician. The selection of the mounting location, its controls and the routing of the wiring is to be accomplished under the direction of the facilities engineer.
WARNING
To prevent electrical shock, do not connect to the system when power is on.
NOTE: For NEMA Type 4X applications, it is recommended that the unit be conduit mounted vertically facing up.
1. Mount the Triliptical DeviceNet Stackable Beacon Base (102TBS-DN) by installing on 3/4" (19 mm) conduit (not supplied). Pull field wiring (if required) and DeviceNet wiring through the conduit entrance hole.
2. Assemble the stackable beacon lighting system (Figure 1).
a. Pull the captive key in the lens module into the "out" position.
b. Place the first lens module on top of the base.
c. Push in the captive key to secure the lens module.
d. Insert the appropriate light source into board grooves at bottom of lens module, ensuring that the four
prongs on the PC board are aligned with the plug located in the back of the lens assembly.
WARNING
Ensure the magnifier ring on the lens co ver and the magnifier ring on the lens module are aligned (Figure 1).
NOTE: When using LED light sources, ensure that the color of the LED light source and the lens assembly match.
e. Place the lens assembly cover on the front of the lens module and secure using two captive screws.
f. Repeat steps a through e for any remaining modules (up to 5).
g. Once the last module has been assembled, place the cap on top and secure the cap with the captive screw.
Network & Field ConnectionsNetwork & Field Connections
Network & Field Connections
Network & Field ConnectionsNetwork & Field Connections
CAUTION
Observe precautions for handling electrostatic sensitive devices while handling printed cir cuit boards.
P/N 3100125 ISSUE 3PAGE 9
WARNING
To avoid electrical shock hazards, do not connect wires when po wer is applied.
1. Make DeviceNet connections to the 5 position female terminal block plug as indicated in the below table. The 5 DeviceNet bus terminals are silkscreened near the terminals on the printed circuit board. Make connections as follows:
Pin 5 V + Red Wire Pin 4 CAN_H White Wire Pin 3 Drain Bare Wire Pin 2 CAN_L Blue Wire Pin 1 V - Black Wire
2. A two (2) position screw terminal is provided to connect either separate 24V DC or 120V AC (depending on version
-G1 (24V DC) or -N5 (120V AC) light source operating power to the Triliptical DeviceNet Stackable Beacon. The terminals for the 24V DC unit are labeled as "+" and "-". Polarity is not important for the 120V AC unit. Make connections as follows:
Pin 1 (+) + 24V DC Red Wire Pin 2 (-) - 24V DC Black Wire
or
Pin 1 120V AC Black Wire Pin 2 120V AC White Wire
3. For the 24V DC unit only, if it is desired to power the light sources from DeviceNet power, jumper (V+) and (V-) on the 5 position DeviceNet terminal block to (+) and (-) respectively on the 2 position screw terminal.
Set DIPSWITCH S1 for the BAUD RATE and MAC ID required as follows:
Note the legend on the dipswitch for the sense of 0 and 1 (0 = OFF and 1 = ON)
SW1 SW2 SW3 SW4 SW5 SW6 SW7 SW8
BAUD RATE - 125 Kbps 0 0 BAUD RATE - 250 Kbps 0 1 BAUD RATE - 500 Kbps 1 0 BAUD RATE - 125 Kbps 1 1 MAC ID 0 000000 MAC ID 1 000001 MAC ID 2 000010 MAC ID 3 000011 MAC ID 4 000100 MAC ID 5 000101 MAC ID 6 000110 MAC ID 7 000111 MAC ID 8 001000 MAC ID 9 001001 MAC ID 10 (0x0A) 001010 MAC ID 11 (0x0B) 001011 MAC ID 12 (0x0C) 001100 MAC ID 13 (0x0D) 001101 MAC ID 14 (0x0E) 001110 MAC ID 15 (0x0F) 001111 MAC ID 16 (0x10) 010000
P/N 3100125 ISSUE 3 PAGE 10
SW1 SW2 SW3 SW4 SW5 SW6 SW7 SW8
MAC ID 17 (0x11) 010001 MAC ID 18 (0x12) 010010 MAC ID 19 (0x13) 010011 MAC ID 20 (0x14) 010100 MAC ID 21 (0x15) 010101 MAC ID 22 (0x16) 010110 MAC ID 23 (0x17) 010111 MAC ID 24 (0x18) 011000 MAC ID 25 (0x19) 011001 MAC ID 26 (0x1A) 011010 MAC ID 27 (0x1B) 011011 MAC ID 28 (0x1C) 011100 MAC ID 29 (0x1D) 011101 MAC ID 30 (0x1E) 011110 MAC ID 31 (0x1F) 011111 MAC ID 32 (0x20) 100000 MAC ID 33 (0x21) 100001 MAC ID 34 (0x22) 100010 MAC ID 35 (0x23) 100011 MAC ID 36 (0x24) 100100 MAC ID 37 (0x25) 100101 MAC ID 38 (0x26) 100110 MAC ID 39 (0x27) 100111 MAC ID 40 (0x28) 101000 MAC ID 41 (0x29) 101001 MAC ID 42 (0x2A) 101010 MAC ID 43 (0x2B) 101011 MAC ID 44 (0x2C) 101100 MAC ID 45 (0x2D) 101101 MAC ID 46 (0x2E) 101110 MAC ID 47 (0x2F) 101111 MAC ID 48 (0x30) 110000 MAC ID 49 (0x31) 110001 MAC ID 50 (0x32) 110010 MAC ID 51 (0x33) 110011 MAC ID 52 (0x34) 110100 MAC ID 53 (0x35) 110101 MAC ID 54 (0x36) 110110 MAC ID 55 (0x37) 110111 MAC ID 56 (0x38) 111000 MAC ID 57 (0x39) 111001 MAC ID 58 (0x3A) 111010 MAC ID 59 (0x3B) 111011 MAC ID 60 (0x3C) 111100 MAC ID 61 (0x3D) 111101 MAC ID 62 (0x3E) 111110 MAC ID 63 (0x3F) 111111
P/N 3100125 ISSUE 3PAGE 11
4. If using the optional Cat No. 102SIGMT-DN multi-tone module, connect the five position female connector on the tone module to the upper set of male pins in the Triliptical DeviceNet Stackable Beacon Base. Set the selected tone in accordance with the table below. Set the third Byte (Data Byte 2) in accordance with the table below in order to access the required tone. "X" is the "Don't Care" State.
Switch Settings*
Tone Bit3 Bit2 Bit1 Bit0
Tone Off 0 X X X Stutter Beep 1 0 0 0 Continuous 1 0 0 1 3 Pulse Horn 1 0 1 0 Rapid Siren 1 0 1 1 Hi/Lo 1 1 0 0 Fast Whoop 1 1 0 1 Yeow 1 1 1 0 Beep 1 1 1 1 *1 is ON. 0 is OFF.
5. Install the 102TBS-* front cover or the optional 102SIGMT-DN-G1 multi-tone module by tightening the two captive front screws.
6. Test the Triliptical DeviceNet Stackable Beacon to ensure that it operates as intended.
To test the device for functionality the unit must be connected to a DeviceNet network via the five (5) pin connector. Turn on the network power supply and local power (if so configured) for the lamps. All lamps will flash instantaneously (some lamps may not be visible) as the unit checks for proper lamp operation. The value of the data byte in the master poll will be displayed on the lamps until it is changed by subsequent poll command. The pre-defined poll connection has consume size of three (3) bytes, and a produce size of three (3) bytes. When all the connections are released the lamps will display the last poll command data before release of the connection.
7. The following is an Output Data Byte example
Byte 2
XXXX 1 001
Set
Tone
On
Set
Tone
Value 1
8. The following is an Input Data Byte example:
Byte 2
XXXX 1001
Sounder is
ON with
Tone
Value 1
Byte 1
000 00001
Set
Flash
Rate =
8OFPM
Set
Lamp 1
to
Flashing
Byte 1
XXX 00011
Lamp 2
was ON
before last poll
command
Byte 0
XXX 11111
Byte 0
0XX 00001
Local
Power
is OK
Lamp 1 is
burned out
or missing
Set
Five
Lamps
ON
P/N 3100125 ISSUE 3 PAGE 12
MaintenanceMaintenance
Maintenance
MaintenanceMaintenance
WARNING
To prevent electrical shock, disconnect network and local power to the unit. Wait 5 minutes for stored energy in str obe modules to dissipate before working on unit.
Light Source Replacement
1. Loosen captive screws and remove cover of affected lens module.
2. Remove the light source assembly from the lens module.
3. Install new light source assembly ensuring that the four prongs on the PC board are aligned with the plug located in the back of the lens module.
WARNING
Ensure the magnifier ring on the lens co ver and the magnifier ring on the lens module are aligned (Figure 1).
4. Replace lens cover and secure using two captive screws.
Cleaning
The lens surfaces should be periodically dusted and cleaned with a dry soft clean cloth to maintain optimum light visibility. If necessary, the outside of the lens may be cleaned with water and a mild detergent on a well rung out soft clean cloth.
P/N 3100125 ISSUE 3PAGE 13
15"
(381mm)
1/2"
(13mm)
3 5/8"
(92mm)
3 5/8"
(92mm)
Cap (supplied with base)
Magnifier
Ring
Board Groove
Light Source Assembly
Captive Key
Signal Base (Cat. No. 10STBS shown)
Lens Module Cover
(2) Captive Screws
3"
(76mm)
Figure 1. Assembling the Stackable Status Indicator
P/N 3100125 ISSUE 3 PAGE 14
Table 1. Triliptical DeviceNet Status Indicator Specifications
Electrical Manufacturers Replacement Lamp Life (hours)
Catalog No. Ratings Lamp Ratings Lamp Calculated#Projected
##
Base Units
102TBS-DN-G1 24V DC, 1.75A 102TBS-DN-N5 120V AC, 0.60A
+
+
N/A N/A N/A N/A
Optional Horn Assembly
102SIGMT-DN-G1 24V DC, 0.05A N/A N/A N/A N/A
Lens Modules
102LM-* N/A N/A N/A N/A N/A
Light Sources
102LS-SINH-G1 24V DC, 0.32A 9 Watts 50LMP-9WH 12,000 --
or Ind. Trade 303*** 3,000 -­102LS-SINH-N5 120V AC, 0.11A 12 Watts 50LMP-12WH 20,000 -­102LS-SIN-G1 24V DC, 0.32A 10 Watts 50LMP-10W or 10,000 --
Ind. Trade 303 3,000 -­102LS-SIN-N5 120V AC, 0.08A 10 Watts 50LMP-10W 2,500 - ­102LS-ST-G1 24V DC, 0.30A 3 Joule Strobe -- 3,000 102LS-ST-N5 120V AC, 0.12A 3 Joule Strobe - - 3,000
###
###
--
--
102LS-SLEDA-G1** 24V DC, 0.062A -- N/A 100,000 -­102LS-SLEDB-G1** 102LS-SLEDG-G1** 102LS-SLEDR-G1** 102LS-SLEDW-G1**
102LS-SLEDA-N5** 120V AC, 0.022A -- N/A 100,000 -­102LS-SLEDB-N5** 102LS-SLEDG-N5** 102LS-SLEDR-N5** 102LS-SLEDW-N5**
+
Currents shown are for a stackable indicator with 5 light modules. *Signifies lens module color (A - amber, B - blue, C - clear, G - green, R - red) **Signifies lens and LED module color (A - amber, B - blue, G - green, R - red) NOTE: LED light sources must be used with
the corresponding color lens module (e.g., a blue LED light source, 102LS-SLEDB-G1, must be used with a blue lens, 102LM-B).
***A non-halogen lamp, as listed, may be used in place of the halogen lamp.
#
At nominal operating voltage.
##
Projected lamp life based on manufacturer's calculated lamp life @ 65 fpm and 50% duty cycle.
###
Strobe tube life @ operating power to 75% efficiency.
Table 2. Pertinent DeviceNet Specifications
Operating DeviceNet Bus Current 0.12A Current Draw supplied by separate power supply (per Light Module) DC: 0.062 to 0.320A
AC: 0.022 to 0.120A
In-Rush Current supplied by separate power supply (per Light Module) DC: 1.2A
AC: 0.5A Flash Rate (selectable via second data byte of POLL command) 45, 60 or 80 fpm Operating Temperature 32F to 158F (0C to 70C)
P/N 3100125 ISSUE 3PAGE 15
Installation Instructions for Triliptical
TM
Stackable Beacon Lighting System Lens Modules
Description
The Edwards Triliptical Stackable Beacon Lighting System is a unique audible-visual signaling device that can contain up to 5 light modules and either a single or multiple tone module in a single "stack."
All components of the T riliptical Stackable Beacon Lighting System are UL and cUL listed subassemblies. The units, when assembled, are UL and cUL listed for indoor and outdoor applications. The enclosures are NEMA 3R, 4X, and IP65 rated. CE Marked Visual Signal.
The optically designed lens modules are available in five colors-­amber, blue, clear, green and red. Each lens module contains a removable cover to allow for easy relamping. The lens module cover features a molded-in gasket for weather tight reliability.
NOTE: LED light sources must be used with the matching lens
color and are only available in four colors--amber , blue, red and green.
Installation
WARNING
To prevent electrical shock, do not connect power until instructed to do so.
Installation must be in accordance with local codes.
1. Assemble the stackable beacon lighting system (Figure 1).
NOTE: When using LED light sources, ensure that the color of the
LED light source and the lens assembly match.
NOTE: For further details, see the instructions supplied with the
light source, P/N 3100701, or the instructions supplied with the base, P/N 3100669.
WARNING
To prevent leakage, ensure the magnifier ring on the lens cover and the magnifier ring on the lens module are aligned (Figure 1).
e. Place the lens module cover on the front of the lens module
and secure using two captive screws.
f. Repeat steps a through e for any remaining modules (up
to 5).
g. Once the last module has been assembled, place the cap
on top and secure the cap with the captive screw.
4. Apply power to the unit and verify proper operation.
WARNING
To prevent electrical shock, disconnect power to all modules. Wait 5 minutes for stored energy in strobe modules to dissipate bef ore working on unit.
a. Pull the captive key in the lens module into the "out"
position. b. Place the first lens module on top of the base. c. Push in the captive key to secure the lens module. d. Insert the appropriate light source into board grooves at
bottom of lens ensuring that the four prongs on the pc
board are aligned with the plug located in the back of the
lens module.
Maintenance
Cleaning
The lens surfaces should be periodically dusted and cleaned with a dry soft clean cloth to maintain optimum light visibility. If neces­sary, the outside of the lens may be cleaned with water and a mild detergent on a well rung out soft clean cloth.
P/N 3100700 ISSUE 1 © 2003
15"
(381mm)
1/2"
(13mm)
3 5/8"
(92mm)
3 5/8"
(92mm)
Cap (supplied with base)
Magnifier
Ring
Board Groove
Light Source Assembly
Captive Key
Signal Base (Cat. No. 102TBS shown)
Lens Module Cover
(2) Captive Screws
3"
(76mm)
Figure 1. Assembling the Stackable Status Beacon Lighting System (Cat. No. 102TBS shown for
illustration purposes only)
P/N 3100700 ISSUE 1
Installation Instructions for Triliptical
TM
Stackable Status Indicator Tone Modules
Description
The Edwards Triliptical Stackable Status Indicator is a unique au­dible-visual signaling device that can contain up to 5 light modules and either a single or multiple tone module in a single "stack."
All components of the Triliptical Stackable Status Indicator are UL and cUL listed subassemblies. The units, when assembled, are UL and cUL listed for indoor and outdoor applications. The enclo­sures are NEMA 3R, 4X, and IP65 rated. See Table 1 for specifica­tions.
The indicator bases are available in three models. Two models feature a shorter base that is used when a lower profile is desired; the other model features a larger base with a terminal block de­signed to function as a junction box for use with an optional horn assembly.
Installation
WARNING
To prevent electrical shock, do not connect power until instructed to do so.
Installation must be in accordance with local codes.
1. Mount the base using one of the following methods:
NOTE: For NEMA 3R, 4X, and outdoor applications, it is
recommended that the unit be conduit mounted vertically facing up.
a. Cat. No. 102TBS Pull field wiring through conduit entrance
hole. Install base on 3/4" (19 mm) conduit (not supplied).
2. Connect field wiring.
a. Cat. No. 102TBS Connect field wiring to the terminal block
as shown in Figure 1.
b. Connect additional field wiring to the terminal block
mounted on the signal assembly as shown in Figure 2.
NOTE: The tone module may be wired to sound independently or in
conjunction with a light signal.
(1) To sound tone independently, connect to separate
hot lead.
(2) To sound tone with a particular light, connect tone
module hot terminal to selected light terminal on Cat. 102TBS terminal block.
3. If using the multi-tone module, Cat. No. 102SIGMT, set the selected tone. See Table 2 and Figure 3.
NOTE: For further installation details, see the instructions supplied
with the lens modules, P/N 3100700, with the base, P/N
Table 1. Specifications
Catalog No. Voltage Current (A)
102SIGST-G1 24V DC 0.05 102SIGST-N5 120V AC 0.07 102SIGMT-G1 24V DC 0.05 102SIGMT-N5 120V AC 0.07
Table 2. Switch Settings
Tone 1 2 3
Stutter beep OFF OFF OFF Hi / Lo ON OFF OFF 3 Pulse Horn OFF ON OFF Continuous OFF OFF ON Yeow ON ON OFF Fast Whoop ON OFF ON Rapid Siren OFF ON ON Beep ON O N ON *ON is in the "UP" position (see Figure 3).
3100669, or with the light sources, P/N 3100701.
Switch Settings*
P/N 3100702 ISSUE 1 © 2003
NEUTRAL/COMMON
MODULE 1
MODULE 2
BOTTOM
MODULE 3
Figure 1. Wiring Cat. No. 102TBS
TERMIN AL
BLOCK
MODULE 4
MODULE 5
TO NEUTRAL ON CAT. 102TBS TERMINAL BLOCK
NH
SEPARATE HOT LEAD OR CONNECTED TO APPROPRIATE LIGHT MODULE TERMINAL ON CAT. 102TBS TERMINAL BLOCK
Figure 2. Wiring Cat. No. 102SIG*T with Optional
Tone Module
COM
VAC
120
ON
123
TONE SELECTI DIPSWITCH (SEE TABLE 2))
Figure 3. Cat. No. 102SIGMT PC Board (120V version shown)
P/N 3100702 ISSUE 1
Loading...