Edwards Signaling ANSZS4B User Manual

ANSZS2A and ANSZS4B Zone Splitter Installation Sheet
Product description
The ANSZS2A and ANSZS4B Zone Splitter modules are intended for use with the ANS25, ANS50, and ANS100 Audio Notification Systems. Their purpose is to enable the output of the ANS to be split into multiple zones for paging and alarm selection.
The modules accept input from the ANS speaker output and use selectable output relays to distribute the output to the individual zones. The modules can be cascaded to increase the number of zones.
The modules provide supervision of the individual zones for open and short conditions. Indicator LEDs display active or fault conditions for the individual zones. A fault condition is reported to the FACP through the same supervisory path as the ANS25, ANS50, or ANS100.
Zones can be selected manually by switches or through pull­down inputs. In the event of an alarm condition, the module defaults to All Call operation. The All Call feature can only be overridden if the accompanying panel has zone control
features.
Each zone is limited to no more than 25 W and the total speaker load must not to exceed the output rating of the ANS. Speaker output can be set to 25 or 70 Vrms, selected by a jumper position on the ANS25, ANS50, or ANS100.
Operation
In normal standby, the ANSZS2A and ANSZS4B supervise each speaker zone wire loop. The ANSZS2A provides Style Y supervision, and the ANSZS4B provides Style Z supervision.
Caution: Do not leave a zone switch turned on when
unattended, as this leaves the zone unsupervised.
In an alarm state, the ANSZS2A and ANSZS4B default to All
Call operation. On activation of the ANS “Alarm voltage” output, all zones are automatically selected, and receive the EVAC tone and message. Modules have a field-selectable option for alarm zone activation only if the FACP has the ability to provide separate pull-down inputs.
If a zone has a short fault, a PTC thermistor for the zone opens, excluding the zone from output and allowing the other zones to continue operation. Once the short is removed, the speaker line must be disconnected for 30 seconds to reset the
PTC.
Specifications
Voltage: 24 Vdc
Current
Standby: 45 mA Active (All Call): 130 mA
Aux. trouble relay (TB2-7, -8, and -9)
Contact rating: 1 A at 30 Vdc (resistive load) Connections: Restricted to Class II or power-limited sources. Interconnected equipment is unsupervised so it must be in the same room and mounted within 20 feet of the module.
Speaker circuit EOL: 10 kΩ
When an open or short fault is detected in a zone, the yellow LED for that zone turns on. A NC relay contact opens to present a corresponding fault signal to the FACP providing supervision of the ANS.
Ground faults in zone circuits are not reported by the ANSZS2A or ANSZS4B, but are detected and reported by the ANS25, ANS50, or ANS100.
To manually select a zone, the operator turns on the corresponding zone switch. The red LED for the switch lights, and output relay activation is enabled. On activation of the PTT signal from the ANS the output relay connects the zone to the ANS speaker output. While the zone is selected, supervision is suspended.
© 2013 UTC Fire & Security. All rights reserved. 1 / 4 P/N 3101185 • REV 02 • REB 28FEB13
Features and functions
Terminal
TB1
TB1
TB1
TB1
TB1
TB1
TB1
TB1
TB1
TB2
TB2
TB2
Terminal
TB2
TB2
TB2
TB2
TB2
TB2
TB2
TB2
TB3
TB3
TB3
TB3
TB3
TB3
TB3
TB3
[1] See “ [2] See J1 settings under Jumpers” for optional zone activation
Switch
S1
S2
S3
S4
S5
Jumper
J1
Installed
Removed
J1
TB1
TB2
TB3
S1
S2
S3
S4
S5
+ + + +
1 2
3
4
5
6 8
7
1 2 3 4 5 6
7
8
9 10 11
1 2
34567
2
PTCs
4 6 8
Figure 1 shows the location of the terminal blocks, zone
selection switches, configuration jumpers, and PTCs. This topic describes the functions of each component.
Figure 1: Features of the ANSZS2A and ANSZS4B cards
Description
-4 24 Vdc power supply +
-5 Alarm active signal
-6 Circuit negative
-7 Aux. trouble relay N.O. [1]
-8 Aux. trouble relay C.
-9 Aux. trouble relay N.C.
-10 Supervisory circuit input
-11 Supervisory circuit input
-1 Supervisory circuit output or EOLR
-2 Supervisory circuit output or EOLR
-3 to 7 Optional zone activation (pull-down) [2]
-3 All Call activation
-4 Zone 4 activation
-5 Zone 3 activation
-6 Zone 2 activation
-7 Zone 1 activation
Specifications” for more information on the Aux. trouble relay
Terminals
Table 1: Terminal descriptions
Description
Speaker output terminals, at either 25 or 70 Vrms, per
PTC setting.
-1 + Zone 1 output Zone 1 output
-2 Zone 1 output Zone 1 output
-3 + Zone 2 output Zone 1 return
-4 Zone 2 output Zone 1 return
-5 + Zone 3 output Zone 2 output
-6 Zone 3 output Zone 2 output
-7 + Zone 4 output Zone 2 return
-8 Zone 4 output Zone 2 return
-1 Signal source +
-2 Signal source −
-3 PTT (push to talk) signal
ANSZS4B: Output terminals for four zones. (Class B,
Style Z.)
ANSZS2A: Output and return terminals for two zones. (Class A, Style Y.)
Polarity ANSZS4B ANSZS2A
Switches
Switches S1 through S4 provide manual zone activation when an operator is in attendance. Switch S5 activates all zones (All Call) on all interconnected ANSZS2A or ANSZS4B zone splitters. Switching S5 on any zone splitter generates an all call for all zone splitters in the system.
Caution: Do not leave a zone switch turned on when
unattended, as this leaves the zone unsupervised.
Table 2: Switch descriptions
Description
Zone 1 activation
Zone 2 activation
Zone 3 activation
Zone 4 activation
All Call activation
Jumpers
Table 3: Jumper settings
Setting
Determines zone activation on alarm active (0 Ω
jumper)
All Call operation on alarm active
Zone-by-zone activation using pull-down inputs on TB3
2 / 4 P/N 3101185 • REV 02 • REB 28FEB13
Loading...
+ 2 hidden pages