ANSBKUP Backup Amplifier Switcher Installation Sheet
Product description
The ANSBKUP provides a means to switch to a backup amplifier in the event of a primary amplifier failure. One backup amplifier can serve as a backup for several primary amplifiers.
All wiring is power-limited.
The ANSBKUP mounts on snap track, or using 5/8-inch nylon standoffs.
The ANSBUKP is compatible with both 25 Vrms and 70 Vrms audio signals.
Specifications
Voltage: 24 Vdc
Current
Standby: 40 mA Active: 10 mA
Installation instructions
Figure 1: Terminal and jumper block positions
The ANSBUKP is mounted in the same cabinet that houses the primary amplifier. It is designed to be mounted using standard, 3-inch snap track material.
The board also has mounting holes at the corners for standoff mounts where necessary. 5/8-inch nylon standoffs are
required.
Terminals and jumpers
Figure 1 shows the position of the terminal and jumper blocks on the ANSBKUP. Table 1 describes the terminal assignments, while Table 2 describes the jumper settings.
© 2013 UTC Fire & Security. All rights reserved. 1 / 2 P/N 3101188 • REV 02 • REB 28FEB13
Table 1: Terminal descriptions
Description
-1 Circuit negative
-2 V+ (24 Vdc)
-3 General purpose input
-4 V+ (24 Vdc)
-1 and 2 Audio output
-1 and 2 Audio input from backup amplifier
-3 and 4 Audio input from primary amplifier
Table 2: Jumper settings
Setting
With a jumper on J1-1 and 2, TS1-2 and TS1-4 are
internally connected. An external wire connecting TS1­and TS1-4 is not required.
Wiring diagram
(1) LED activates when backup audio is switched in. ( (
(4) If the primary amplifier is an ANS25, ANS50, or ANS100, turn DIP
If the primary amplifier is an ANS25A, ANS50A, or ANS100A, turn DIP switch SN1-5 ON.
Speaker
output
From primary amplifier
Input from primary amplifier (TB1-5 and 6) (4)
Input from backup amplifier (TB1-5 and 6)
TB2-10
TB3-7
TB2-1
TB1
TS1
TB2
LED (1)
1
2
3
4
J1
1
2
4
3
2 1
(2)
EOLR (3)
Figure 2: Typical wiring details
2) Install jumper J1 to eliminate TS1-2 to TS1-4 connection.
3) Backup amplifier EOLR is required at the ANSBKUP only.
switch SN2-5 ON.
2 / 2 P/N 3101188 • REV 02 • REB 28FEB13