The Audio Notification System (ANS) is a self-contained
amplifier, tone generator, digital message repeater, and
supervisory interface. It is designed for use with a UL Listed
fire alarm control panel (FACP) to provide a listed voice
evacuation alarm system. See Table 1 for a list of ANS
models.
The FACP provides all initiating circuitry and a notification
appliance circuit (NAC) that connects to the ANS. The ANS
provides its own internal supervision and supervision for its
speaker lines. The ANS reports faults to the FACP by placing
an open on the FACP NAC. Optionally, faults can be reported
to the FACP by connecting a supervisory circuit to the ANS.
The ANS reports internal failures and speaker line faults by
placing an open on the supervisory circuit.
All models of the ANS are powered by a 120 V, 60 Hz supply.
Optionally, the ANS can be powered by 24 Vdc from a UL Listed
fire alarm power supply. Each model provides a different power
level, but all models can be configured for 25 or 70 Vrms
speakers (by jumper). The factory setting is for 25 Vrms.
ANS models
ANS model numbers have the format: ANS999MDC. Each
model is a complete audio notification panel, including a built-in
tone generator, power transformer, and cabinet. The 999
portion represents the output power: 25, 50, 100, 150, or
200 watts. M indicates the inclusion of a microphone. D
indicates the inclusion of a digital message repeater (DMR). C
indicates the cabinet color, either gray (G) or red (R).
Expander model numbers have the format ANS999XC. Each
model is a complete expander panel, including a built-in tone
generator, power transformer, and cabinet. The 999 portion
represents the output power. X indicates an expander module.
Expanders have no microphone and no DMR. C indicates the
cabinet color, either gray (G) or red (R).
Amplifier model numbers have the format AMS999AMD. The
amplifiers include a built-in tone generator, but no transformer
or cabinet. The 999 portion represents the power output. The A
designation indicates an amplifier. M indicates the inclusion of
a microphone. D indicates the inclusion of a digital message
repeater.
An Expander can operate as a slave amplifier when connected
to an ANS999AMD, which supplies source audio to the slave.
Expanders can also operate as stand-alone audio notification
systems with only tone and microphone amplification.
Table 1: ANS models
Description Amplifier
modules
25 W ANS ANS25AMD 1
50 W ANS ANS50AMD 1
100 W ANS ANS100AMD 1
150 W ANS ANS100AMD
ANS50A
200 W ANS ANS100AMD
ANS100A
25 W ExpanderANS25A 1
50 W ExpanderANS50A 1
100 W ExpanderANS100A 1
R)150 W ExpanderANS100A
ANS50A
R)200 W ExpanderANS100A
ANS100A
Specifications
Table 2: Specifications
ANS25 ANS50 ANS100
120 Vac at 60 Hz or 24 Vdc
1.4 A 0.8 A2.0 A
Standby 0.18 A0.13 A 0.18 A
Alarm 1.00 A 1.00 A 2.50 A
Standby with
aux. load
Standby 0.60 A0.60 A0.60 A
Alarm 1.00 A 1.00 A 2.60 A
Sine 2.90 A 3.40 A 6.50 A
0.31 A 0.26 A0.85 A
25 W 50 W 100 W
800 to 2800 Hz400 to 4000 Hz400 to 4000 Hz
25 or 70 Vrms selectable
Power-limited, open and short circuit protected
Audio
circuits
2
2
2
2
Some models use multiple amplifier configurations. These
models are configured and prewired at the factory.
[1] Input current measurements are determined using test conditions
specified in UL 1711.
unit produces a continuous, undistorted sine wave of 1 kHz into the
rated load of 25, 50, or 100 W at the rated output voltage.
average current the unit experiences delivering an alarm signal,
temporal w
unit with all normal power on and auxiliary terminals fully loaded.
Battery standby
in an otherwise normal standby state.
[2] All ANS cabine
require an external battery cabinet.
Terminal
TB1
TB1
TB1
TB1
TB2
TB2
TB2
TB2
TB2
TB2
TB2
TB2
TB2
TB2
TB2
TB3
TB3
Minimum 24 V, 7 Ah
Maximum 24 V, 18 Ah 24 V, 18 Ah 24 V, 24 Ah
10 mA maximum
Sine represents measurements made while the
Alarm is the
Note: if your system includes one or more ANSZS4B zone
splitters, the FACP EOLR must be relocated. See the
ANSZS4B installation sheet (P/N 3101185).
4. Connect the FACP signaling circuit to TB1-3(+) and
TB1-4(−), using the FACP alarm polarity.
5. Connect the mains power (120 Vac at 60 Hz) to the black
and white pigtail leads from transformer primary. Secure
the ground lead to the grounding stud in the cabinet.
6. Connect the battery wiring harness, Red(+) and Black(−).
Observe the correct polarity.
hoop, to the rated load. Standby is the current draw of the
is the current draw from the batteries on loss of power
ts hold two 12 V, 7 Ah batteries. Larger batteries
Installation instructions
Ensure that all wiring and devices installed in the system meet
the following standards:
• NFPA 70 National Electrical Code
• NFPA 72 National Fire Alarm and Signaling Code
• NFPA 101 Life Safety Code
• Applicable state and local codes
Install this equipment in a clean, dry environment. Avoid
installation where the equipment could be subjected to
vibration. Remove all electronic assemblies from the enclosure
before drilling or punching the enclosure. Where possible,
make all cable entries from the rear or sides. Before making
any modifications to the enclosure, be certain that they will not
interfere with the assemblies or batteries.
Wiring instructions
Refer to Figure 1 for terminal designations, and to diagrams in
the “Applications” section for wiring diagrams.
1. Connect the speaker lines to TB1-5(+) and TB1-6(−).
Be sure to observe polarity and connect all speakers using
the same polarity. For Class A (Style Z) the returns are
TB1-7(−) and TB1-8(+).
Note: When using 70 VRMS speakers, the speaker wiring
must be enclosed in grounded metal conduit.
2. Connect the microphone to connector P2.
If the microphone is not installed, ensure that switch
SN2-8 is in the OFF position.
3. Attach the appropriate EOLR for the FACP to TB3-3 and 4
and for the speaker circuit to TB3-5 and 6.
You must use EOLR value specified for the FACP
notification appliance circuit (NAC). See the FACP
installation instructions provided by the manufacturer.
2 / 12 P/N 3101179 • REV 03 • REB 28FEB13
Use two 12 V batteries connected in series. (See
Figure 4.) If the unit does not have its own batteries and
relies on an external power supply with battery backup,
ensure that switch SN2-7 is in the OFF position.
Note: Wiring for batteries is nonpower-limited. Maintain a
minimum spacing of 1/4 in. between power-limited wiring
and nonpower-limited wiring.
If the batteries must be located in a separate enclosure,
provide a separate conduit run for the battery wiring only.
7. When all power and circuits are connected, the green LED
turns on (and stays on) to indicate that the ANS is fully
operational and all circuits are normal.
Terminal designations
Refer to Figure 1 for the locations of the terminals.
Table 3: Terminal descriptions
Description
-1, -2 Power input 24 to 32 Vac/Vdc [1][4]
-3, -4 FACP NAC input. 10 mA max. Alarm polarity is shown.
[1][4]
-7 Aux signal activate. +24 Vdc, 32 Vdc, 5 mA max. [1][3]
-8Alarm voltage. +24 Vdc, 0.1 A when unit is in alarm condition. [2][3][5]
-9 Interrupted V+. +24 Vdc, 0.1 A. Disconnected in alarm condition. [2][3]
-10 V+. +24 Vdc, 0.1 A. [2][3]
-11 Microphone PTT. +24 Vdc, 0.1 A. [5]
-1, -2 Optional FACP supervisory circuit. See installation
instructions for details. 32 Vdc, 0.4 A max.). Must be
configured using J1. [1][4]
-3, -4 FACP Signal/Supervisory circuit EOLR
Terminal
TB3
TB3
TB3
[1]
limited)
sources only
[2]
[3]
[4]
[5]
ANS
Switch
SN1
SN1
SN1
SN1
SN1
SN1
SN1
SN1
SN2
SN2
SN2
SN2
SN2
SN2
SN2
SN2
ON
OFF
DIP switch detail
A
B
TB1
TB3
MSG
GAIN
MIC
GAIN
FAULT (yellow)
NORMAL (green)
ALARM (red)
LED1
LED4
GND
FAULT
(yellow)
LED2
LED3
TB2
P2
U6
S1
SN2SN1
1 2 3
J2
J5
J1
1
2
70V 25V
++++
––––
123
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
9
10
11
1 2 3 45678
Description
-5, -6Matching EOLR for speaker supervisory circuit
-7 General purpose output. Pulls to circuit negative on
-8Trouble input. +24 Vdc, 5 mA. [1][3][5]
Intended for connection to listed Class 2 or Class 3 (power-
Power-limited
Unsupervised
Supervised
Terminating equipment must be installed in the same room as the
Figure 1: ANS features
fault conditions. 32 Vdc, 0.2 A max. Not for fire
protective signaling use. [1][3][5]
MSG GAIN and MIC GAIN
The MSG GAIN (message gain) and MIC GAIN (microphone
gain) potentiometers are factory set and should only be
adjusted by trained technicians with the proper test equipment.
To increase the output of a speaker, change the speaker tap
connection or setting to a higher wattage.
Switch S1
Pressing switch S1 performs a hard reset of the ANS
microprocessor. This is not required during normal operation,
and should only be done at the request of our support
technicians.
DIP switch settings
Factory settings
Refer to Figure 1 for DIP switch locations. The following table
shows the factory settings and descriptions for the switches.
Table 4: Factory DIP switch settings
Setting Description
-1 Off 8 second initial delay
-2 On
-3 Off
-4 On 8 second repeat delay
-5 Off
-6On Message on
-7 Off Three repeats
-8On
-1 Off Temporal whoop signal
-2 Off
-3 Off
-4 Off Fault code lock off
-5 Off Factory set. Do not change.
-6Off AC fault delay
-7 On Battery connected
-8On Microphone connected
P/N 3101179 • REV 03 • REB 28FEB133 / 12
Custom settings
Switches
SN1
Sets the initial delay before the message starts to
SN1
SN1
SN1
SN2
SN2
SN2
SN2
SN2
SN2
Jumper
J1
and B)
J1 (A
and B)
J2
J2
J5
J5
Jumper settings
Table 5: Custom DIP switch settings
Settings
-1/2/3
-4/5 Sets the delay between repetitions of the
-6Sets the message play mode. There are two
-7/8Sets the number of times the message plays.
-1/2/3 Sets the evacuation tone. There are eight
-4 Sets the diagnostics mode. With diagnostics ON
-5 Not used
-6AC power failure report delay. There are two
-7 Batteries. There are two options.
-8Microphone. There are two options.
4 / 12 P/N 3101179 • REV 03 • REB 28FEB13
play. The tone sounds during this delay. There
are eight options.
Off | Off | Off = No delay
On | Off | Off = 4 second delay
Off | On | Off = 8 second delay
On | On | Off = 12 second delay
Off | Off | On = 16 second delay
On | Off | On = 20 second delay
Off | On | On = 24 second delay
On | On | On = 28 second delay
message. The tone sounds during this delay.
There are four options.
Off | Off = 4 second delay
Off | On = 8 second delay
On | Off = 12 second delay
On | On = 16 second delay
options.
Off = Message off
On = Message on
There are four options.
Off | Off = 1 play
Off | On = 3 plays
On | Off = 2 plays
On | On = Continuous play
options.
Off | Off | Off = Temporal slow whoop
On | Off | Off = Hi-lo
Off | On | Off = Horn
On | On | Off = Bell
Off | Off | On = None
On | Off | On = Chime
Off | On | On = None
On | On | On = 1 kHz sine
the last fault condition is displayed even if the
fault is no longer present. There are two options.
Off = Diagnostics off
On = Diagnostics on
options.
Off = No delay
On = 6-hour delay
Off = Batteries are not connected
On = Batteries are connected
Off = Microphone is not connected
On = Microphone is connected
Refer to Figure 1 for the locations of the jumpers. Table 6
shows the settings and descriptions for the jumpers.
Table 6: Jumper settings
Setting Description
(A
1 to 2 70 Vrms speaker output
2 to 3 25 Vrms speaker output (factory setting)
In Ground fault detection enabled (factory setting)
Out Ground fault detection disabled
In No FACP supervision. See “Optional supervisory
Out FACP provides supervision. See “Optional
circuit” below
supervisory circuit” below
Options
Aux +24 Vdc output
Terminals TB2-4, -8, -9, and -10 provide a maximum of 200 mA
of regulated 24 Vdc power for auxiliary functions. Do not
exceed a combined load of 200 mA on these terminals. These
terminals are for connection to ANS accessory modules and
listed general signal devices only and are not for use with fire
protective signaling applications. Terminal TB2-4 activation is
programmed in the U6 EPROM chip. Standard chips are
programmed for TB2-4 to go active (+24 Vdc) under the
following conditions:
• Aux signal active
• Aux audio enable
• Bell circuit active
• RSI active
Reprogramming of these functions must be done at the factory
and requires replacing the EPROM U6.
Aux audio source connection
Terminals TB2-1 and -2 allow connection of an aux audio
source from additional paging equipment to augment an
existing paging system. This option is not intended for
continuous signal input, but may be used for paging
applications. For such an operation the aux audio enable input,
TB2-6, must be powered from the interrupted V+, TB2-9. This
ensures that in the event of an alarm, the aux audio will not
override the evacuation signal. See Figure 9 for connection
details. Use of an ANSAUX Audio Transponder Module may
be required for some audio sources (to match the auxiliary
audio line signal.)
Optional supervisory circuit
Terminals TB3-1 and -2 can be used to connect a supervisory
circuit from the FACP to the ANS. In place of normal
supervision via the notification appliance circuit, an alternate
method may be employed using any supervisory circuit from
the FACP. TB3-1 and -2 provide a normally closed connection
to the EOLR on TB3-3 and -4. The relay contact in the circuit
opens on any trouble condition and reports an open circuit
trouble to the FACP.
Loading...
+ 8 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.