Edwards Signaling ANS User Manual

Model number
ANS25MD(G/R)
ANS50MD(G/R)
ANS100MD(G/R)
ANS150MD(G/R)
ANS200MD(G/R) ANS25X(G/R)
ANS50X(G/R)
ANS100X(G/R)
ANS150X(G/
ANS200X(G/
Model
Input voltage
Input current
(at 120 Vac)
Input current (battery)
Output power
Frequency response
Output voltage
Optional 24 Vdc input [1]
Output protection
ANS Audio Notification System Installation Sheet
Product description
The Audio Notification System (ANS) is a self-contained amplifier, tone generator, digital message repeater, and supervisory interface. It is designed for use with a UL Listed fire alarm control panel (FACP) to provide a listed voice evacuation alarm system. See Table 1 for a list of ANS models.
The FACP provides all initiating circuitry and a notification appliance circuit (NAC) that connects to the ANS. The ANS provides its own internal supervision and supervision for its speaker lines. The ANS reports faults to the FACP by placing an open on the FACP NAC. Optionally, faults can be reported to the FACP by connecting a supervisory circuit to the ANS. The ANS reports internal failures and speaker line faults by placing an open on the supervisory circuit.
All models of the ANS are powered by a 120 V, 60 Hz supply. Optionally, the ANS can be powered by 24 Vdc from a UL Listed
fire alarm power supply. Each model provides a different power level, but all models can be configured for 25 or 70 Vrms speakers (by jumper). The factory setting is for 25 Vrms.
ANS models
ANS model numbers have the format: ANS999MDC. Each model is a complete audio notification panel, including a built-in tone generator, power transformer, and cabinet. The 999 portion represents the output power: 25, 50, 100, 150, or 200 watts. M indicates the inclusion of a microphone. D
indicates the inclusion of a digital message repeater (DMR). C indicates the cabinet color, either gray (G) or red (R).
Expander model numbers have the format ANS999XC. Each model is a complete expander panel, including a built-in tone
generator, power transformer, and cabinet. The 999 portion
represents the output power. X indicates an expander module. Expanders have no microphone and no DMR. C indicates the cabinet color, either gray (G) or red (R).
Amplifier model numbers have the format AMS999AMD. The amplifiers include a built-in tone generator, but no transformer or cabinet. The 999 portion represents the power output. The A designation indicates an amplifier. M indicates the inclusion of a microphone. D indicates the inclusion of a digital message repeater.
An Expander can operate as a slave amplifier when connected
to an ANS999AMD, which supplies source audio to the slave. Expanders can also operate as stand-alone audio notification systems with only tone and microphone amplification.
Table 1: ANS models
Description Amplifier
modules
25 W ANS ANS25AMD 1
50 W ANS ANS50AMD 1
100 W ANS ANS100AMD 1
150 W ANS ANS100AMD
ANS50A
200 W ANS ANS100AMD
ANS100A
25 W Expander ANS25A 1
50 W Expander ANS50A 1
100 W Expander ANS100A 1
R) 150 W Expander ANS100A
ANS50A
R) 200 W Expander ANS100A
ANS100A
Specifications
Table 2: Specifications
ANS25 ANS50 ANS100
120 Vac at 60 Hz or 24 Vdc
1.4 A 0.8 A 2.0 A
Standby 0.18 A 0.13 A 0.18 A
Alarm 1.00 A 1.00 A 2.50 A
Standby with aux. load
Standby 0.60 A 0.60 A 0.60 A
Alarm 1.00 A 1.00 A 2.60 A
Sine 2.90 A 3.40 A 6.50 A
0.31 A 0.26 A 0.85 A
25 W 50 W 100 W
800 to 2800 Hz 400 to 4000 Hz 400 to 4000 Hz
25 or 70 Vrms selectable
Power-limited, open and short circuit protected
Audio circuits
2
2
2
2
Some models use multiple amplifier configurations. These models are configured and prewired at the factory.
© 2013 UTC Fire & Security. All rights reserved. 1 / 12 P/N 3101179 • REV 03 • REB 28FEB13
Model
ANS25 ANS50 ANS100
Battery charging capacity [2]
FACP NAC circuit current
[1] Input current measurements are determined using test conditions
specified in UL 1711.
unit produces a continuous, undistorted sine wave of 1 kHz into the
rated load of 25, 50, or 100 W at the rated output voltage.
average current the unit experiences delivering an alarm signal,
temporal w
unit with all normal power on and auxiliary terminals fully loaded.
Battery standby
in an otherwise normal standby state.
[2] All ANS cabine require an external battery cabinet.
Terminal
TB1
TB1 TB1
TB1
TB2
TB2 TB2
TB2
TB2
TB2
TB2
TB2
TB2 TB2
TB2
TB3
TB3
Minimum 24 V, 7 Ah
Maximum 24 V, 18 Ah 24 V, 18 Ah 24 V, 24 Ah
10 mA maximum
Sine represents measurements made while the
Alarm is the
Note: if your system includes one or more ANSZS4B zone
splitters, the FACP EOLR must be relocated. See the ANSZS4B installation sheet (P/N 3101185).
4. Connect the FACP signaling circuit to TB1-3(+) and TB1-4(−), using the FACP alarm polarity.
5. Connect the mains power (120 Vac at 60 Hz) to the black and white pigtail leads from transformer primary. Secure the ground lead to the grounding stud in the cabinet.
6. Connect the battery wiring harness, Red(+) and Black(−). Observe the correct polarity.
hoop, to the rated load. Standby is the current draw of the
is the current draw from the batteries on loss of power
ts hold two 12 V, 7 Ah batteries. Larger batteries
Installation instructions
Ensure that all wiring and devices installed in the system meet
the following standards:
NFPA 70 National Electrical Code
NFPA 72 National Fire Alarm and Signaling Code
NFPA 101 Life Safety Code
Applicable state and local codes
Install this equipment in a clean, dry environment. Avoid installation where the equipment could be subjected to vibration. Remove all electronic assemblies from the enclosure before drilling or punching the enclosure. Where possible,
make all cable entries from the rear or sides. Before making
any modifications to the enclosure, be certain that they will not interfere with the assemblies or batteries.
Wiring instructions
Refer to Figure 1 for terminal designations, and to diagrams in the “Applications” section for wiring diagrams.
1. Connect the speaker lines to TB1-5(+) and TB1-6(−).
Be sure to observe polarity and connect all speakers using
the same polarity. For Class A (Style Z) the returns are TB1-7(−) and TB1-8(+).
Note: When using 70 VRMS speakers, the speaker wiring
must be enclosed in grounded metal conduit.
2. Connect the microphone to connector P2.
If the microphone is not installed, ensure that switch SN2-8 is in the OFF position.
3. Attach the appropriate EOLR for the FACP to TB3-3 and 4
and for the speaker circuit to TB3-5 and 6.
You must use EOLR value specified for the FACP
notification appliance circuit (NAC). See the FACP installation instructions provided by the manufacturer.
2 / 12 P/N 3101179 • REV 03 • REB 28FEB13
Use two 12 V batteries connected in series. (See
Figure 4.) If the unit does not have its own batteries and
relies on an external power supply with battery backup,
ensure that switch SN2-7 is in the OFF position.
Note: Wiring for batteries is nonpower-limited. Maintain a
minimum spacing of 1/4 in. between power-limited wiring and nonpower-limited wiring.
If the batteries must be located in a separate enclosure, provide a separate conduit run for the battery wiring only.
7. When all power and circuits are connected, the green LED turns on (and stays on) to indicate that the ANS is fully operational and all circuits are normal.
Terminal designations
Refer to Figure 1 for the locations of the terminals.
Table 3: Terminal descriptions
Description
-1, -2 Power input 24 to 32 Vac/Vdc [1][4]
-3, -4 FACP NAC input. 10 mA max. Alarm polarity is shown. [1][4]
-5, -6 Speaker loop, Style Y/Z (Class A/B start) [2][4]
-7, -8 Speaker loop Style Z (Class A return) [2][4]
-1 Circuit negative
-2 Aux audio input. 0.5 Vrms nominal, 1 Vrms, 1 mA max. [1][3]
-3 Preamp in/out. 600 Ω, 0 dBm. [1][3][5]
-4 Factory Programmable output [1][3][5]
-5 Signal active [1][3][5]
-6 Aux audio enable. +24 Vdc, 32 Vdc, 5 mA max. [1][3]
-7 Aux signal activate. +24 Vdc, 32 Vdc, 5 mA max. [1][3]
-8 Alarm voltage. +24 Vdc, 0.1 A when unit is in alarm condition. [2][3][5]
-9 Interrupted V+. +24 Vdc, 0.1 A. Disconnected in alarm condition. [2][3]
-10 V+. +24 Vdc, 0.1 A. [2][3]
-11 Microphone PTT. +24 Vdc, 0.1 A. [5]
-1, -2 Optional FACP supervisory circuit. See installation
instructions for details. 32 Vdc, 0.4 A max.). Must be configured using J1. [1][4]
-3, -4 FACP Signal/Supervisory circuit EOLR
Terminal
TB3
TB3
TB3
[1]
limited)
sources only
[2] [3] [4] [5]
ANS
Switch
SN1
SN1
SN1
SN1
SN1
SN1
SN1
SN1
SN2
SN2
SN2
SN2
SN2
SN2
SN2
SN2
ON
OFF
DIP switch detail
A
B
TB1
TB3
MSG GAIN
MIC
GAIN
FAULT (yellow)
NORMAL (green)
ALARM (red)
LED1
LED4
GND
FAULT
(yellow)
LED2
LED3
TB2
P2
U6
S1
SN2 SN1
1 2 3
J2
J5
J1
1 2
70V 25V
+ + + +
1 2 3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
9
10
11
1 2 3 45678
Description
-5, -6 Matching EOLR for speaker supervisory circuit
-7 General purpose output. Pulls to circuit negative on
-8 Trouble input. +24 Vdc, 5 mA. [1][3][5]
Intended for connection to listed Class 2 or Class 3 (power-
Power-limited Unsupervised Supervised Terminating equipment must be installed in the same room as the
Figure 1: ANS features
fault conditions. 32 Vdc, 0.2 A max. Not for fire protective signaling use. [1][3][5]
MSG GAIN and MIC GAIN
The MSG GAIN (message gain) and MIC GAIN (microphone gain) potentiometers are factory set and should only be adjusted by trained technicians with the proper test equipment.
To increase the output of a speaker, change the speaker tap connection or setting to a higher wattage.
Switch S1
Pressing switch S1 performs a hard reset of the ANS microprocessor. This is not required during normal operation, and should only be done at the request of our support technicians.
DIP switch settings
Factory settings
Refer to Figure 1 for DIP switch locations. The following table shows the factory settings and descriptions for the switches.
Table 4: Factory DIP switch settings
Setting Description
-1 Off 8 second initial delay
-2 On
-3 Off
-4 On 8 second repeat delay
-5 Off
-6 On Message on
-7 Off Three repeats
-8 On
-1 Off Temporal whoop signal
-2 Off
-3 Off
-4 Off Fault code lock off
-5 Off Factory set. Do not change.
-6 Off AC fault delay
-7 On Battery connected
-8 On Microphone connected
P/N 3101179 • REV 03 • REB 28FEB13 3 / 12
Custom settings
Switches
SN1
Sets the initial delay before the message starts to
SN1
SN1
SN1
SN2
SN2
SN2
SN2 SN2
SN2
Jumper
J1
and B)
J1 (A
and B)
J2
J2
J5
J5
Jumper settings
Table 5: Custom DIP switch settings
Settings
-1/2/3
-4/5 Sets the delay between repetitions of the
-6 Sets the message play mode. There are two
-7/8 Sets the number of times the message plays.
-1/2/3 Sets the evacuation tone. There are eight
-4 Sets the diagnostics mode. With diagnostics ON
-5 Not used
-6 AC power failure report delay. There are two
-7 Batteries. There are two options.
-8 Microphone. There are two options.
4 / 12 P/N 3101179 • REV 03 • REB 28FEB13
play. The tone sounds during this delay. There are eight options.
Off | Off | Off = No delay On | Off | Off = 4 second delay Off | On | Off = 8 second delay On | On | Off = 12 second delay Off | Off | On = 16 second delay On | Off | On = 20 second delay Off | On | On = 24 second delay On | On | On = 28 second delay
message. The tone sounds during this delay. There are four options.
Off | Off = 4 second delay Off | On = 8 second delay On | Off = 12 second delay On | On = 16 second delay
options.
Off = Message off On = Message on
There are four options.
Off | Off = 1 play Off | On = 3 plays On | Off = 2 plays On | On = Continuous play
options.
Off | Off | Off = Temporal slow whoop
On | Off | Off = Hi-lo Off | On | Off = Horn On | On | Off = Bell
Off | Off | On = None On | Off | On = Chime Off | On | On = None On | On | On = 1 kHz sine
the last fault condition is displayed even if the fault is no longer present. There are two options.
Off = Diagnostics off On = Diagnostics on
options.
Off = No delay
On = 6-hour delay
Off = Batteries are not connected On = Batteries are connected
Off = Microphone is not connected On = Microphone is connected
Refer to Figure 1 for the locations of the jumpers. Table 6 shows the settings and descriptions for the jumpers.
Table 6: Jumper settings
Setting Description
(A
1 to 2 70 Vrms speaker output
2 to 3 25 Vrms speaker output (factory setting)
In Ground fault detection enabled (factory setting)
Out Ground fault detection disabled
In No FACP supervision. See “Optional supervisory
Out FACP provides supervision. See “Optional
circuit” below
supervisory circuit” below
Options
Aux +24 Vdc output
Terminals TB2-4, -8, -9, and -10 provide a maximum of 200 mA of regulated 24 Vdc power for auxiliary functions. Do not exceed a combined load of 200 mA on these terminals. These
terminals are for connection to ANS accessory modules and listed general signal devices only and are not for use with fire
protective signaling applications. Terminal TB2-4 activation is programmed in the U6 EPROM chip. Standard chips are programmed for TB2-4 to go active (+24 Vdc) under the
following conditions:
Aux signal active
Aux audio enable
Bell circuit active
RSI active
Reprogramming of these functions must be done at the factory and requires replacing the EPROM U6.
Aux audio source connection
Terminals TB2-1 and -2 allow connection of an aux audio source from additional paging equipment to augment an
existing paging system. This option is not intended for
continuous signal input, but may be used for paging
applications. For such an operation the aux audio enable input, TB2-6, must be powered from the interrupted V+, TB2-9. This ensures that in the event of an alarm, the aux audio will not
override the evacuation signal. See Figure 9 for connection
details. Use of an ANSAUX Audio Transponder Module may
be required for some audio sources (to match the auxiliary audio line signal.)
Optional supervisory circuit
Terminals TB3-1 and -2 can be used to connect a supervisory circuit from the FACP to the ANS. In place of normal supervision via the notification appliance circuit, an alternate method may be employed using any supervisory circuit from
the FACP. TB3-1 and -2 provide a normally closed connection to the EOLR on TB3-3 and -4. The relay contact in the circuit
opens on any trouble condition and reports an open circuit trouble to the FACP.
Loading...
+ 8 hidden pages