VISUAL SIGNALS
FEATURES
> NEMA Type 4X Enclosure
> Diode polarized for use in
electrically supervised circuits
> Optically designed fresnel lens
> Heavy duty, high profile
> Immune to shock and vibration
AdaptaBeacon
®
Heavy Duty Strobe
Div. 2 Hazardous Location
Diode Polarized
94DDV2 Series
The Edwards 94DDV2 Series Division 2 AdaptaBeacons are high
profile visual signals, ideal for outdoor and wet locations requiring a
diode polarized, UL Listed, NEMA Type 4X enclosure. A series of
complementing fresnels cause the dome to "fill" with light each time
the strobe flashes. This design feature increases the AdaptaBeacon
"on-time", thus improving viewer perception. Beam distance is also
increased with external fresnel lenses.
> Cast base may be used as a
junction box
> Shatter resistant clear
polycarbonate dome
AGENCY APPROVALS
> UL 1638 and 1604 Listed
> UL Listed NEMA Type 4X
enclosure
> cUL Listed
The units' series trigger and timing circuits are included as integral
parts of the power supply. Replacement costs are reduced as it is
necessary to replace only the strobe tube.
Designed for indoor or outdoor installation on 3/4" (19mm) conduit.
For weatherproof installations, unit must be mounted vertically, with
the lens facing up. Mount on 3/4" (19mm) conduit with the lens
facing up.
The 94DDV2 is often used to signal warning, evacuation,
manufacturing processes, stop start, equipment malfunction,
personnel danger, visual communications, work breaks, and phone
calls. They are also ideally suited for installations where a larger,
brighter visual signal is specified. The gasketed weatherproof
design assures installation acceptability in most industrial and
commercial locations.
D-04
3-46
© Copyright 2004 Edwards
TECHNICAL INFORMATION
7 7/8"
(200mm)
3/4" (19mm)
conduit hole
VISUAL SIGNALS
8 1/16"
(205mm)
Lens Replacement Flash Electrical Replacement Replacement Peak
Cat. No. Color Lens Rate Rating Dome Strobe Tube Candlepower
94DDV2R-G1 Red 93-LR 65 fpm 24V
94DDV2A-G1 Amber 93-LA 1.2 Amps 3,000 hour*
94DDV2B-G1 Blue 93-LB
94DDV2G-G1 Green 93-LG
94DDV2M-G1 Magenta 93-LM
94DDV2C-G1 Clear 93-LC
*Calculated at operating power to 75% efficiency.
DC 94DV2-DC 92-ST 800,000 cd
HAZARDOUS LOCATION LISTINGS
Class Division Group Operating Temperature Code
I 2 A,B,C,D T3 (200C, 392F)
II 2 F,G T6 (85C, 185F)
III T6 (85C, 185F)
© Copyright 2004 Edwards