Edwards Signaling 879EX User Manual

Cheshire, CT 06410 203-699-3300 (Ph) 203-699-3365 (Cust. Serv. Fax) 203-699-3078 (Tech. Serv. Fax)
Installation Instructions for Explosion-Proof
Adaptahorn Catalog Series 878EX and 879EX
Description and OperationDescription and Operation
Description and Operation
Description and OperationDescription and Operation
Edwards explosion-proof Adaptahorn is a heavy-duty high decibel vibrating horn intended for use where a distinc­tive audible signal is required in a hazardous location. It is UL and cUL listed and is designed for use in Class I, Division 1 and 2, Groups B, C, and D; and Class II, Division 1 and 2, Groups F and G, Class II, Division 1, Group E, and Class III, Division 1 and 2 hazardous locations.The horns are in an Outdoor Type 4X rated enclosure (Outdoor Type 4X applies to general signaling use in non-fire alarm ap­plications). The Adaptahorn may be mounted to any solid surface.
Electrical SpecificationsElectrical Specifications
Electrical Specifications
Electrical SpecificationsElectrical Specifications
dB Rating
Cat. Number Input Power Current at 10 ft.
878EX-R5 240V AC 0.065A 97 878EX-N5 120V AC 0.13A 97 878EX-G5 24V AC 0.625A 97 878EX-E5 12V AC 1.25A 97 879EX-P1 125V DC 0.025A 97 879EX-K1 48V DC 0.07A 97 879EX-J1 32V DC 0.13A 97 879EX-G1 24V DC 0.16A 97 879EX-E1 12V DC 0.27A 97 879EX-C1 6V DC 0.7A 97
One explosion-proof outlet box suitable to the hazardous location
Two 3/4-14 National Pipe Taper (NPT) nipple connectors.
1. Mark two mounting holes per dimensions in Figure 1. Secure Adaptahorn to solid surface using the furnished mounting brackets and hard ware suitable for the mounting location. The 3/8" diameter fasteners and washers are not supplied.
2. See Figure 1. Power source connections are made in the explosion-proof outlet box. Remove outlet box cover.
CAUTIONCAUTION
CAUTION
CAUTIONCAUTION
Do not apply power to the unit until installation is completed and cover is secured.
3. Feed external power wires through the 3/4 inch conduit which is attached to the outlet box with one of the 3/4-14 NPT connectors.
4. Feed Adaptahorn power connection wires through the other 3/4-14 NPT connector which connects the Adaptahorn to the outlet box.
6. Replace outlet box cover and tighten securely.
Ambient Temperature:
The UL Hazardous Locations Listing is “only for use under normal atmospheric conditions in an ambient tempera­ture within the range of -25C (-13F) to +40C (+104F)”; and within these ambient temperatures, Edwards recommends
-4C (+25F) and higher for its function as an audible signal appliance.
InstallationInstallation
Installation
InstallationInstallation
For power connections in a hazardous location, the fol­lowing external parts will be required:
3/4 inch conduit of sufficient length to contain power source wires within hazardous location
Maintenance and Maintenance and
Maintenance and
Maintenance and Maintenance and
Examine the unit periodically for accumulation of dirt. Clean if necessary.
The Adaptahorn should be tested monthly to ensure con­tinuous service.
TT
T
TT
estest
est
estest
P/N P-047550-0304 ISSUE 5 © 2003
PAGE 1
Figure 1. Signal Mounting Details
Contacting Edwards:
Phone: (203) 699-3000
E-Mail: techsupport@edwards-signals.com
customerservice@edwards-signals.com
Website: http://www.edwards-signals.com