Edwards Signaling 876 Series, 877 Series Catalog Page

HORNS & SIRENS
FEATURES
AdaptaHorn® Grille Type Vibrating Horn
Weatherproof, NEMA Type 4X
876 & 877 Series
> PLC compatible models
> Convenient plug-in assembly
> Corrosion resistant finish
> Completely assembled
> Volume adjustable
> NEMA 4X enclosure
AGENCY APPROVALS
> UL Listed
> FM Approved
SPECIFICATIONS
> Operating range: -20% to +10%
of nominal voltage
876 AC Series
> Adjustable output: 78 to 103 dB
The Edwards 876 AC & 877 DC Series are low-current, high deci-
bel, vibrating horns for heavy-duty use and is UL listed to NEMA 4X
enclosure requirements. The die-cast weatherproof box has a du-
rable, corrosion resistant, electrostatic heat flowed powder epoxy
Mount on conduit or to any flat surface. A hole on the top has been
drilled and tapped for 3/4" (19mm) - 14 NPT conduit. Knockouts are
located on the bottom and rear of the unit.
Used where a distinctive, urgent signal is required for outdoor or
weatherproof requirements such as: timing scheduling, paging, gen-
eral alarm, personnel warning, and emergency evacuations.
872-PO Plastic Projector
AdaptaHorn Accessory
Plastic projector snaps onto any
AdaptaHorn. Available as separate item.
> 400 hour rating at 50% duty cycle
877 DC Series
> Adjustable output: 78 to 101 dB
> 200 hour rating
D-04
6-16
© Copyright 2004 Edwards
TECHNICAL INFORMATION
4 7/8"
(124mm)
Volume adjustment set screw
1/16" (2mm) allen wrench supplied
HORNS & SIRENS
3 5/16"
(84mm)
DC coil dB at
Cat. No. Volts Amps V A Res. (Ohms) 10 Ft.
876-E5 12V AC 1.25 15 1.5 876-G5 24V AC .63 15.1 5.2 103
876-N5
120V AC .13 15.6 150
876-R5 240V AC .07 16.8 580
877-E1 12V DC .27 3.2 6 877-G1 24V DC .16 3.8 24 877-J1 32V DC .13 4.2 40 101 877-K1 48V DC .07 3.5 96 877-P1 125V DC .025 3.1 600
Diode polarized version available in red. Order 886D-N5
PLC COMPATIBILITY - SIGNAL INPUT LOAD CHARACTERISTICS*
Operating Max. off state Continuous on Surge
voltage leakage current current (inrush/duration)
Cat. No. Volts mA mA Amps/milliseconds
876-N5 120V AC 25 120 1.02/.000026
877-G1 24V DC 25 150 1.7/.000042
*This device is PLC compatible and may be operated by PLCs with output characteristics that match the input load requirements of this signal.