Edwards Signaling 6536-G5 Horn/Strobe Installation Instructions

Installation Instructions for the
6536-G5 Horn/Strobe
Description
The 6536-G5 is an audible/visual signal UL Listed for general purpose signaling applications.
Installation
W ARNING
T o reduce the risk of shock, do not remove lens or tamper with unit when the circuit is energized. Do not connect AC power until installation is complete.
The 6536-G5 horn/strobe (Figure 1) can be mounted on any single gang 2" x 4" (51 mm x 102 mm) electrical box, double gang 4" x 4" (102 mm x 102 mm) electrical box, or standard 4" x 4" (102 mm x 102 mm) junction box with a plaster ring.
1. Install an appropriate electrical box using suitable hardware.
2. Connect the horn/strobe wire leads and terminals (Figure 2). The horn and strobe are connected together at the factory.
NOTE: To connect the horn and strobe to different circuits,
loosen the terminals, remove the two wires and cap off with wire nuts.
3. Mount the horn/strobe onto the electrical box. Secure it using two screws (supplied).
4. Perform an operational test.
Maintenance
WARNING
T o reduce the risk of shock, do not remo ve lens or tamper with unit when the circuit is energized. Disconnect power and allow five (5) minutes for stored energy to dissipate before starting work or disassembly . High energy could be stored in the strobe circuit once it is energized.
Perform regularly scheduled testing at least twice a year or more often as dictated by local authorities having jurisdiction.
FRONT VIEW
Horn
Mounting screws
SIGNAL
STROBE
Red (+)
Single 24V AC or
24V DC Power Source
Table 1. Specifications
Operating V oltage 24V 50/60 Hz 24V DC Alarm Current 175 mA 125 mA
4 9/16"
(116 mm)
Strobe
4 1/2"
(114 mm)
_
+
Figure 1. Details of Horn/Strobe
Electrical Box
Factory
S
Connected
BACK VIEW
To separate 24V AC or 24V DC power source
Factory installed wires
+
White (-)
CHESHIRE, CT 203-699-3300 FAX 860-677-7746
-
Figure 2. Connecting the Horn and Strobe
P-047550-1872 ISSUE 1 © 1999