Edwards Signaling 57EDF Series Heavy Duty Double Flash Strobe Lights Installation Guide

EDWARDS
Installation Instructions for 57EDF Series Heavy Duty
Double Flash Strobe Lights
8
(203 mm)
6 1/2
(165 mm)
Figure 1. Dimensions
Description
The 57EDF series signaling a ppliances ar e hea vy duty, doubl e flash strobe lights intended for use in gener al signaling (non-fire alarm) a pplications. The str obe lights ar e UL listed and CSA Certified, have a NEMA 4X enclosure and are a vailable in 24V DC, 120V AC and 240V AC. See Table 1 for specifications.
The 23 joule strobe is rated at 2.3 million peak candela.
Installation
WARNING
To prevent electrical shock, do not connect power until installation has been completed and unit is tightly assembled and secured.
Install this unit in accordance with the applicable requirements in the latest edition of the National Electrical Code. See the unit's label and Table 1 for specif ications.
NOTE: For indoor applications, the strobe light can be
mounted vertically either facing up or facing down. For outdoor applications, the unit must be mounted vertically with the lens facing up.
1. Pull appropriate power source wir ing through 3/4" (19 mm) NPT conduit. Install the unit on the conduit.
2. Connect red positive (+) lead to positi ve power source wire and black ne gative (-) lead to ne gative power sour ce wire. Polarity m ust be observ ed on 24V DC unit. F or AC units, connect green ground wire to earth ground.
3. Apply power to the unit and ensur e proper operation.
Maintenance
Strobe Tube Replacement
WARNING
To prevent electrical shock, disconnect from the supply circuit and allow five (5) minutes for stored energy to dissipate before disassembling the unit.
Disassemble the unit as follo ws:
1. Remove the f our (4) scre ws from the lens assemb ly and remove the globe and lens as sho wn in Figure 2.
CAUTION
To prevent damage to the strobe tube, hold the tube only by its base;
2. Pry the strobe tube straight up and out of the strobe tube socket.
3. Refer to Table 1 for the correct replacement catalog n umber and replace the strobe tube.
4. Assemble the unit:
a. Ensure that the o-ring, part number 044001, is in place
around the base of the unit and replace the lens and dome (Figure 2).
do not
handle the tube .
P/N 500003 ISSUE 3 © 1998
g
g
g
g
b. Install four (4) scr ews removed in step 1.
5. After the unit is assembled, apply power and ensure the unit functions properl y.
Dome
Lens
(4) Screw s with washers for securin to base
Strobe Tube
dome and lens
Strobe Tube Socket
Base
(3) Screw s with washers for securin to base
base plate
Threaded Conduit En tra nc e Ho le
O-Rin P/N 044001
O-Rin P/N 044002
Base Plate
Figure 2. Replacing the Strobe Tube
Table 1. Specif ications
Strobe Tube Replacement Parts
Cat. No. Ratings Lens Color Life* Strobe Tube Lens Dome
57EDFA-G1 24V DC Amber 3,000 Hours 92-ST 57E-LA 57E-DC 57EDFB-G1 2.2A Blue 57E-LB 57EDFC-G1 Clear 57E-LC 57EDFG-G1 Green 57E-LG 57EDFR-G1 Red 57E-LR
57EDFA-N5 120V 50/60 Hz Amber 3,000 Hours 92-ST 57E-LA 57E-DC 57EDFB-N5 0.2A Blue 57E-LB 57EDFC-N5 Clear 57E-LC 57EDFG-N5 Green 57E-LG 57EDFR-N5 Red 57E-LR
57EDFA-R5 240V 50/60 Hz Amber 3,000 Hours 92-ST 57E-LA 57E-DC 57EDFB-R5 0.1A Blue 57E-LB 57EDFC-R5 Clear 57E-LC 57EDFG-R5 Green 57E-LG 57EDFR-R5 Red 57E-LR
*Calculated strobe tube life at operating power to 75% efficiency.