1. Put switches A and B on the programming dipswitch in the
proper position for the message to be recorded (Figure 6).
For programming a message longer than five seconds,
use Message Location 1.
Description
Edwards Adaptatone Millennium is intended for industrial
applications where high audible output and microcomputer
reliability are required. The Adapatatone Millennium series are
UL and cUL Listed as Audible Signal Appliances for use in the
hazardous locations listed in Table 1.
The Adaptatone operates from local power. It accommodates
up to four normally-open contacts on its inputs. The tone that
sounds in response to an active input is determined by setting
miniature programming switches inside the unit. Table 6 has
switch settings for setting tones.
Four tones may be programmed into the unit at any time.
These tones operate on a pyramid-type priority system. The
tone programmed on SW1 overrides the tones programmed on
SW2, SW3, and SW4. The tone on SW2 overrides the tones
programmed on SW3 and SW4. Likewise, the tone on SW3
overrides the tone programmed on SW4. The tone
programmed on SW4 has the lowest priority and cannot
override any other programmed tone.
Speaker direction and the output level are easily adjustable.
Message
Location
1 0 Sec CLOSED CLOSED
2 5 Sec OPEN CLOSED
3 10 Sec CLOSED OPEN
4 15 Sec OPEN OPEN
2. Put switch PGM on the programming dipswitch in the
“CLOSED” position for programming mode (Figure 6).
3. Press and hold the record button while speaking clearly
into the microphone to record your message. Release the
button when recording is complete.
4. To test the message, press and hold PLAY while in
programming mode.
NOTE: This will play only the current location.
WARNING: High volume may cause harm to personnel in
close proximity.
5. Adjust the volume as necessary. Set the main volume
using the potentiometer on the main board (Figure 5 and
Figure 6) and then set the voice volume using the
potentiometer on the voice module board (Figure 6).
Installation
The Adaptatone may be mounted to any flat surface or may be
used as a freestanding unit mounted to a rigid pipe. The
Adaptatone must be installed in accordance with the latest
edition of the National Electrical Code or other regulations
applicable to the country and locality of installation and by a
trained and qualified electrician.
Start Switch A
Settings
Switch B
Settings
For catalog numbers ending in "AQ", 24 VAC power must be
transformer isolated from mains or line power.
WARNING: To prevent fire, shock and component damage,
NO work, including circuit board removal, should be performed
while the circuit is energized.
NOTE: Any kind of service or maintenance performed
while unit is energized will void the warranty.
1. Mount Adaptatone as shown in Figure 1.
a. Flat Surface Mounting. Secure unit to mounting
surface using the (4) mounting holes in the mounting
plate on the rear of the box. Use the #10 x 3" (76
mm) wood screws (furnished loose) or other hardware
(not supplied) suitable for the mounting surface.
b. Rigid Pipe Mounting. Loosen the (4) cover screws
from the signal box and lift off signal box cover.
NOTE: Cover screws are captive. Do not remove from cover.
Remove the center knockout in lower wall of box and
mount box to a 1/2” (12.7 mm) conduit pipe using
suitable connector.
2. Wire in accordance with the instructions in “Wiring.”
3. Refer to Figure 5 and Table 6 and select desired tones.
Set miniature programming switches on the input board.
For input connected to IN1, set on SW1; IN2, set on SW2;
IN3, set on SW3, and IN4, set on SW4, in order of priority
desired.
WARNINGS: HIGH VOLTAGE is present when product is
energized.
High volume may cause harm to personnel in close proximity.
4. Adjust volume level, if desired, by turning potentiometer
located on the main board (Figure 5 and Figure 6).
WARNING: To ensure integrity of the Adaptatone assembly
when adjusting the speaker direction, make sure threads in the
enclosure remain fully engaged and do not turn speaker more
than 360 degrees from the original factory installed position.
5. To adjust speaker direction, loosen large star nut
(Figure 1) and turn speaker to the approximate desired
position. Retighten nut and turn speaker slightly clockwise
until locked into place.
6. Tightly secure the signal box cover using (4) retained
cover screws.
7. Torque signal box cover screws to a minimum of 20 in-lbs.
8. Verify operability.
Wiring
1. Install wires through a knockout hole in the bottom of the
box from a raceway that is, with its connections to the 1/2"
conduit knockout hole, approved for the same degree of
protection and enclosure type needed by the application.
Use the provided plastic tie-wrap, on the barrier to the
electronics, to separate incoming power leads from signal
and tone initiating leads, per NEC (Figure 4).
WARNING: To prevent fire and shock, wire the Adaptatone
only as described in this installation instruction.
2. Wire as follows referring to Figure 4.
If Edwards Signal Actuator catalog number 5538-4 is used
to manually initiate tones, connect its four normally-open
switches to the Tone Generator as shown on instructions
provided with the Signal Actuator unit.
a. Connect green and yellow-striped earth-ground wires
to earth-ground.
b. Select the appropriate method for wiring to the input
board from Figure 7 - Figure 11 models with 24 V
input boards and Figure 12 and Figure 13 for models
with 120 V input board. Connect the Adaptatone as
shown.
c. Connect incoming power to wire leads using a butt
splice or other method listed, certified, or otherwise
approved by local authorities. Leads are both black
for -AQ and -N5 models and are black and white for
-Y6 models.
d. Optional. Connect external 24 VDC battery (not
supplied) in series with separate diode assembly part
2600010 (supplied) to TB1 terminals 3 and 4 on the
main board as shown in Figure 3 and marked on the
diode assembly.
NOTE: Terminal Block TB1 can be unplugged from the main
board to complete wiring as shown in Figure 2 and Figure 3.
WARNINGS: To ensure integrity of the enclosure: Ensure the
cover gasket, part number P-007549-0069, is adhered into
groove at cover perimeter before replacing the signal box
cover.
Ensure that the (4) collar gaskets, part number P-0419300362, are in place on each cover screw before securing the
signal box cover.
When securing cover, start screws by hand, making sure they
are threaded into tapped holes in housing bosses before
securing with a screwdriver. Torque signal box cover screws
to a minimum of 20 in-lbs. This ensures the required tight fit.
2 / 8 P/N 3100008 • REV 4 • ISS 09AUG10
Maintenance and testing
WARNINGS: To prevent fire, shock and component damage,
NO work, including circuit board removal, should be performed
while the circuit is energized.
NOTE: Any kind of service or maintenance performed
while unit is energized will void the warranty.
Examine the unit semi-annually for accumulation of dirt. Clean
if necessary.
The Adaptatone should be tested annually or as required by
the authority having jurisdiction to ensure continuous service.
Page 3
Figure 1: Mounting the Adaptatone
Figure 4: Wiring the Adaptatone
Figure 2: Terminal block TB1
Figure 3: Wiring to terminal block TB1 input circuit
Figure 5: PC board locations
Figure 6: PC board locations (voice messaging models)
P/N 3100008 • REV 4 • ISS 09AUG10 3 / 8
Page 4
Figure 7: Installing with multiple dry relay contacts to 24 V input
board method 1 (Refer to Applications Engineering for
compatibility with earlier versions of Adaptatone)
Figure 9: Installing with an open collector transistor, 24 V input
board
Figure 10: Connecting to a “B” Version Adaptatone, 24 V input
board (maximum 5 “M” versions)
NFPA Whoop OFF ON ON OFF ON ON Three 422 – 775 Hz upward sweeps, 850 ms each, 1 s
3 Pulse Horn* OFF ON ON ON OFF OFF 470 Hz, 3 0.5 s pulses separated by 0.5 s followed by
3 Pulse Air Horn* OFF ON ON ON OFF ON 370 Hz, 3 0.5 s pulses separated by 0.5 s followed by
3 Pulse Dual
Tone*
3 Pulse Chime 2* OFF ON ON ON ON ON 575 Hz, 3 0.5 s pulses separated by 0.5 s followed by
European Police ON OFF OFF OFF OFF OFF 969 Hz and 800 Hz alternately 0.250 s each 20
European Fire ON OFF OFF OFF OFF ON 982 Hz and 864 Hz downward sweep in 0.134 s 21
European Slow
Whoop
European General ON OFF OFF OFF ON ON 1087 Hz for 0.5 s followed by 0.5 s delay and repeat 23
European Toxic ON OFF OFF ON OFF OFF 982 Hz continuous 24
European Police 2 ON OFF OFF ON OFF ON 554 Hz and 440 Hz alternately, 0.8 s each 25
European Stutter ON OFF OFF ON ON OFF 3876 Hz for 0.146 s followed by 0.102 s delay and
European Sweep ON OFF OFF ON ON ON 1315 Hz – 413 Hz downward sweep in 1.17 s and
Telephone 2 ON OFF ON OFF OFF OFF Alternate tones at 567 Hz and 326 Hz 28
Buzzer ON OFF ON OFF OFF ON 1315 Hz and 746 Hz alternating for 0.003 s each 29
Genesis Horn Cont ON OFF ON OFF ON OFF Continuous Genesis horn 2A
Genesis Horn
Temp
Warning 1 ON OFF ON ON OFF OFF 1207 Hz and 493 Hz, alternately 0.002 s each 2C
Warning 2 ON OFF ON ON OFF ON 2336 Hz and 493 Hz, alternately 0.005 s each 2D
Warning 2 Beep ON OFF ON ON ON OFF 0.500 s of 2336 Hz and 493 Hz each alternating for
Caution ON OFF ON ON ON ON 453 Hz for 0.040 s, 235 Hz for 0.020 s, 235 Hz for 0.160
Multi-tone ON ON OFF OFF OFF OFF 376, 357, 352, 382, 355, 375, 384, 375 and 364 Hz
Attention ON ON OFF OFF OFF ON 2232, 4545, 3704, 2777, 4347, 3704, 2500 Hz
High Freq. Steady
Alert
High Freq. Fast
Siren
High Freq. Slow
Siren
DIN PFEER ON ON OFF ON OFF ON Ramp downward from 1336 Hz to 522 Hz in 1.2 s and
NF S 32 001 ON ON OFF ON ON OFF 584 Hz for 0.100 s and 461 Hz for 0.400 s 36
Ode to Joy ON ON OFF ON ON ON 6.45 s of melody followed by 1 s delay and repeat 37
Twinkle Little Star ON ON ON OFF OFF OFF 13.2 s of melody followed by 1 s delay and repeat 38
Dueling Banjos ON ON ON OFF OFF ON 10.84 s of melody followed by 1 s delay and repeat 39
La Cucaracha ON ON ON OFF ON OFF 7.10 s of melody followed by 1 s delay and repeat 3A
Yellow Rose of TX ON ON ON OFF ON ON 19.34 s of melody followed by 1 s delay and repeat 3B
*3 Pulse Tones are for Evacuation Use Only
OFF ON ON ON ON OFF 450 – 500 Hz, 0.4 to 0.5 s cycle, 3 0.5s pulses
ON OFF OFF OFF ON OFF 658 – 1312 Hz upward sweep in 3 s followed by 0.5 s
ON OFF ON OFF ON ON Temporal Genesis horn 2B
ON ON OFF OFF ON OFF 2500 Hz continuous 32
ON ON OFF OFF ON ON 2500 – 3048 Hz up and down sweep in 0.130 s 33
ON ON OFF ON OFF OFF 2500 – 3048 Hz up and down sweep in 0.500 s 34
delay and repeat
1.5 s delay and repeat
1.5 s delay and repeat
separated by 0.5 s followed by 1.5 s delay and repeat
1.5 s delay and repeat
delay and repeat
repeat
repeat
0.005 s followed by 1 s delay
s, 260 Hz for 0.050 s, 260 Hz for 0.1009 s, 235 Hz for
0.050 s
alternately on for 0.050 s
alternately on for 0.003 s
repeat
1B
1C
1D
1E
1F
22
26
27
2E
2F
30
31
35
CAUTION: The use of evacuation signals on this product, that is not specifically listed for fire alarm use, is subject to the approval
of the authority having jurisdiction.
P/N 3100008 • REV 4 • ISS 09AUG10 7 / 8
Page 8
Regulatory information
Edwards Signaling Edwards, A Division of UTC Fire & Security
UL and cUL Rated Audible Signal Appliance
Americas Corporation, Inc.
8985 Town Center Parkway, Bradenton, FL
34202, USA
Contact information
For contact information, see www.edwardssignaling.com.
8 / 8 P/N 3100008 • REV 4 • ISS 09AUG10
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.