Edwards Signaling 5520D-N5 User Manual

11"
(279 mm)
To Point of Pivot
5 1/2"
(139 mm)
7" Diam.
(178 mm)
Description
8 3/4" Diam.
(222 mm)
14"
(355 mm)
11"
(279 mm)
Figure 1. Dimensions
Installation Instructions for Duotronic Signals
Catalog Numbers 5520D-AW and 5520D-N5
Installation
13 1/2"
(343 mm)
o
90
1. Bring signaling circuit wires into electrical box or:
For weatherproof installation, fasten the Cat. No. 349 weatherproof box to the mounting surface by installing the (3) #8 x 1-1/4" wood screws and three fiber washers (supplied with the box) through the mounting holes in the rear of the box. Note that "TOP" inside of box indicates required position for installation. Bring signaling circuit wires through conduit and through conduit entrance hole into box. Secure conduit to box.
For indoor installation, select a site that conforms to the requirements given in the latest edition of NFPA 72, National Fire Alarm Code.
Edwards' DUOTRONIC signals, catalog numbers 5520D-AW and 5520D-N5, are high decibel, diode-polarized, UL listed signaling appliances intended for public mode fire alarm signaling applications (per NFPA 72G) and other applica­tions requiring electrical supervision of signaling circuit field wiring. The 5520D-AW signal is dc powered and the 5520D-N5 signal is ac powered. The signals can operate either as a horn or a siren and provide a switch for select­ing the desired operating mode. The horn and siren tones are produced electronically. When operated in the horn mode, the signals can be used in coded signaling applica­tions. The signals can be installed on any standard single gang, 3-1/4", 3-1/2", 4" octagonal or 4" square electrical box, or they can be installed outdoors using the Cat. No. 349 Weatherproof Box (ordered separately).
Electrical Specifications
Catalog Rated Alarm dBA Rating at 10 ft* Number Voltage Current (A) Horn Siren
5520D-AW 20 - 24V DC 0.35 114 112 5520D-N5 120V AC 0.35 114 112
*Sound level rating as measured in an anechoic chamber on an "A" weighted decibel scale.
Mechanical Specifications
2. Disconnect the four-wire receptacle, shown in Figure 5, from the signal plug. Connect the leads from the receptacle to the signal circuit wires as shown in Figure 3 for the Cat. No. 5520D-N5 signal or Figure 4 for the 5520D-AW signal. Polarity must be observed.
CAUTION
Use all leads for connection. Make sure to break wire run to provide electrical supervision.
For additional information on wiring connections, refer to the installation instructions supplied with the fire alarm control panel or applicable system control panel.
3. See Figure 2. Loosen the screw at the bottom of the signal housing and remove the mounting plate from the signal.
MOUNTING PLATE
Dimensions ..................................................... See Figure 1
Weight .............................................. 7 1/2 Pounds (3.4 kg)
LOOSEN THIS NUT TO ADJUST SPEAKER DIRECTION
Figure 2. Mounting Plate Removal and
Speaker Directional Adjustment
CHESHIRE, CT 203-699-3300 FAX 203-699-3365 (CUST. SERV.) 203-699-3078 (TECH SERV.)
LOOSEN THIS SCREW TO REMOVE MOUNTING PLATE
P/N P-047550-0448 ISSUE 4 © 2001
NOTE
DC SUPERVISORY POLARITY SHOWN. ON ALARM,
VOLTAGE SWITCHES TO 120V AC
NOTE
DC SUPERVISORY POLARITY SHOWN. ON ALARM,
POLARITY REVERSES.
_
FROM FIRE ALARM OR SYSTEM CONTROL PANEL OR PREVIOUS SIGNAL
+
RED RED
WHITE WHITE
TO NEXT SIGNAL OR END-OF-LINE DEVICE
_
+
Figure 3. Wiring Diagram for
Cat. No. 5520D-N5 Signal
CAUTION
To prevent damage to the signal, always ensure that the signal is disconnected from the signaling circuit before operating the horn/siren switch.
4. Select the desired operating mode by sliding the handle of the horn/siren switch, located in the rear of the signal housing, fully to the position marked "HORN" or "SIREN".
5. Bring the four-wire receptacle through the center hole of the mounting plate as shown in Figure 5. Align appropriate holes in plate with mounting screw holes in electrical box or with holes in bosses of Cat. No. 349 weatherproof box. Note that "TOP" on mounting plate indicates required position for installation. Fasten plate to applicable type of box as follows:
_
FROM FIRE ALARM OR SYSTEM CONTROL PANEL OR PREVIOUS SIGNAL
+
RED RED
BLACK BLACK
TO NEXT SIGNAL OR END-OF-LINE DEVICE
_
+
Figure 4. Wiring Diagram for
Cat. No. 5520D-AW Signal
WARNING
This device will not operate without electrical power. As fires frequently cause power interruptions, discuss further safeguards with your local fire protection specialist.
Maintenance and Subsequent Testing
Maintenance and testing of the 5520D-AW and 5520D-N5 Duotronic Signals should conform to the requirements given in the latest edition of NFPA 72. The standard re­quires you to examine the signal annually for accumula­tion of dust and dirt and clean when necessary.
Test the signal annually or at the intervals required by applicable fire regulations and codes.
a. To single gang box--using the two #6-32 x 5/8"
screws supplied with signal.
b. To octagonal or square box--using screws supplied
with box.
c. To weatherproof box--using the four #8-32 x 7/16"
machine screws supplied with box.
6. Connect the signal plug with the receptacle and push through mounting plate into box. Then hook signal on mounting plate by engaging hanger on plate, shown in Figure 5, into slot in top of signal housing. Tighten screw, loosened in step 3, to secure signal to plate.
Adjusting Speaker Direction
To adjust the speaker direction, loosen the nut shown in Figure 2. Rotate the speaker to the desired posltion and then tighten the nut. The speaker position can be ad­justed within a 90 degree range vertically and 180 degree range horizontally.
Operational Test
Apply power to the fire alarm or system control panel. Initiate an alarm to activate the signal and verify that it sounds and that the selected type of signal is sounding. Reset the panel to silence the signal and return to the supervisory mode.
P/N P-047550-0448 ISSUE 4
CONNECT TO SIGNALING CIRCUIT WIRES IN BOX
Figure 5. Mounting Plate Details
HANGER--ENGAGE WITH SLOT IN TOP OF SIGNAL HOUSING
TOP
FOUR-WIRE RECEPTACLE
TO SIGNAL
SIGNAL PLUG