Edwards Signaling 393-BT User Manual

www.ge-security.com/industrial
GE Interlogix
Industrial
GuardSwitch™ Series 300
Description
The 391-BT Series DPST safety interlock switch is designed for use with safety monitored relays or monitored circuits. To achieve the optimum Series 300 defeat resistance feature of the 391-BT, both the switch circuit (Circuit 1) and the tamper circuit (Circuit 2) must be connected. An optional third circuit can be provided to indicate at the panel which guard is open.
Notes:
1. Environmental: Pollution Degree II
2. Correct use of this control device is an essential part of proper machine cycle control.
3. Failure to follow ALL instructions could lead to serious bodily injury or death.
4. Maintenance to be done by qualified personnel only
5. The connecting cables between the INT devices and the switches must be located in an IP 23 type enclosure (minimum).
6. The mounting for the switch and the actuator magnet must be accomplished per this specification.
7. Non-removable hardware must be used for installation.
8. The housing of the 300-BT must be connected to the PE (Primary Earth) ground circuit via a lock washer on the mounting screw. The PE ground symbol must be placed adjacent to the screw.
To verify switch operation with an ohmmeter:
Set range at 20 mega ohms (switches with triac output, set ohm range at 20 kilo ohms). For a normally open switch, the meter will read a high impedance with the actuator away. It will read very high to infinity range (triac switches will read high kilo ohm to infinity range) with the actuator within sense range. You will see the opposite reading for a normally closed switch.
Dimensions
0.80''
2.03cm
0.05''
0.13cm
1.28''
3.25cm
Figure 1
0.11''
0.28cm
0.17''
0.43cm
0.55''
1.40cm
0.24''
0.61cm
4.22''
10.72cm
3.12''
7.92cm
3.75''
9.53cm
sensing face
sensing face
0.22''
0.56cm dia.
Safety Interlock Switch
391-BT
393-BT
391-BLT-12(J)(K)
Installation
Use non-removable screws, bolts, or nuts to mount the switch and actuator. Do not over-torque mounting hardware.
1. Position the switch and actuator so the labels are reading in the same direction (See Figure 1.)
2. Mount the switch on the stationary frame of the machine and mount the actuator on the moveable guard, door or gate. Keep the switch and actuator within listed sense range. (See Ordering Information.) See Figure 2 for recommended mounting configurations.
3. Mounting on a ferrous material will effect the sense range a minimum of 50%. However, a 1/4" non-ferrous spacer positioned under the magnet and/or switch should restore most of the lost sense range.
4. For best protection against operator defeat, mount with non-removable screws, bolts or nuts. See ordering information for details.
5. When not used with a GE INT safety relay, particular care must be taken to determine the actual load of the switch circuit. High voltage transients from coils, motors, contactors and solenoids must be considered. Transient protection, such as back-to-back zener diodes (TransZorb such loads to ensure that maximum ratings of the switch are not exceeded. Not recommended to be used with tungsten filament loads because of high current inrush surges. Line capacitance and load capacitance must be considered. Excessive line capacitance can be caused by cable lengths over 50' when using a maximum 48 VAC. A resistor can be added in series to limit
®
) or an RC network, is recommended for
391-B3LT-12J 391-B3LT-20J 391-B______ 393-B______
continued
S1
BLK
WHT
BLUE
RED
D1
D2
S2 S3
S4
CIR.
2
CIR.
1
S5
ORG
BRN
CIR.
3
Optional LED
the inrush current (at least 48 ohms for 24 Volt applications). The resistor can be added in series just before the load. The voltage drop and the power rating of the resistor must be considered. Voltage drop = I•R; Watts = I
2
•R
(I = maximum continuous current of the load).
6. When mounting the switch on an ungrounded machine, ground the switch housing by connecting your ground lead to one of the switch mounting screws.
Mounting Configurations
The interlock switch and actuator magnet should be mounted in only three configurations for actuation.
CIR.1
CIR.2
CIR.3
BLK
WHT
BLUE
RED
BRN
ORG
Circuits *
without LED
S1
S2 S3
S5
Circuits 2*
with optional LED
S4
Figure 2
Perpendicular
Actuation
Door
Actuation Parallel Actuation
Pivot Actuation
*Circuits shown with actuator away from switch.
S1,S5 Normally open reed switch, closed when actuator is within 0.6" S2, S3 Normally open reed switches, will close if misaligned or tampered with a
standard magnet
S4 Biased closed reed switch, open when actuator is between 0.3" and 0.6"
N.O. circuit: Black and white wires. N.C. biased tamper circuit: Red and blue wires. N.O. monitor circuit: Orange and brown wires.
Best Best Not Recommended
Good
Three configurations are appropriate for safety interlock applications. The parallel actuation can result in on/off/on signal if the actuator passes by the switch rather than coming to rest in proximity to it. This is NOT a recommended configuration for safety interlock applications.
Wiring Diagram for Category 3
Inputs shown with safety gates/guards in closed position. One Series 300-BT GuardSwitch™ required for each safety gate.
(–)
INT-03-230: 230V AC INT-03-120: 120V AC INT-03-024: 24V DC
(+)
Required Fast or Slow-Acting Fuse: (250V, 5x20 mm F) INT-03-230: 40mA INT-03-120: 80mA INT-03-024: 1/4A
RESET
L1 L2 1 2 X1 X2 Y1 Y2
+
N.O. N.C.
W
B
H
L
T
K
Series Circuit
R
B
E
L
D
U
R
W H T
B
B
E
L
L
D
U
K
Parallel Circuit
R
W
B
E
H
L
D
T
K
B L U
GE Security Industrial
Required Fast or Slow­Acting Fuses: 4A (250V, 5x20 mm F
230 VAC
60 VDC
Safety Monitor Relay INT-03
SAFE AUX.
A
BCD
LOADS
OUTPUTS
EFG
*300-BLT-
*Or other DPST GuardSwitch
(See the 300-BT Series installation instructions)
Note – The LED on the BLT model will be ON when the guard is open
Fuses: 1 A (250 v)
Multiple DPST GuardSwitches – Shown with actuators in position, all guards closed.
120 VAC
30 VDC
The L.E.D of the BLT model will be on when the guard is open. If multiple guards
are open, L.E.D will be dimmer. The maximum number of GuardSwitches that can
be used is 50, although troubleshooting and line resistance must be considered.
(Do not exceed 30 Ohms of combined contact and line resistance. Each GuardSwitch
will have less than 0.5 Ohms of resistance.)