Edwards Signaling 393-BT User Manual

Page 1
www.ge-security.com/industrial
GE Interlogix
Industrial
GuardSwitch™ Series 300
Description
The 391-BT Series DPST safety interlock switch is designed for use with safety monitored relays or monitored circuits. To achieve the optimum Series 300 defeat resistance feature of the 391-BT, both the switch circuit (Circuit 1) and the tamper circuit (Circuit 2) must be connected. An optional third circuit can be provided to indicate at the panel which guard is open.
Notes:
1. Environmental: Pollution Degree II
2. Correct use of this control device is an essential part of proper machine cycle control.
3. Failure to follow ALL instructions could lead to serious bodily injury or death.
4. Maintenance to be done by qualified personnel only
5. The connecting cables between the INT devices and the switches must be located in an IP 23 type enclosure (minimum).
6. The mounting for the switch and the actuator magnet must be accomplished per this specification.
7. Non-removable hardware must be used for installation.
8. The housing of the 300-BT must be connected to the PE (Primary Earth) ground circuit via a lock washer on the mounting screw. The PE ground symbol must be placed adjacent to the screw.
To verify switch operation with an ohmmeter:
Set range at 20 mega ohms (switches with triac output, set ohm range at 20 kilo ohms). For a normally open switch, the meter will read a high impedance with the actuator away. It will read very high to infinity range (triac switches will read high kilo ohm to infinity range) with the actuator within sense range. You will see the opposite reading for a normally closed switch.
Dimensions
0.80''
2.03cm
0.05''
0.13cm
1.28''
3.25cm
Figure 1
0.11''
0.28cm
0.17''
0.43cm
0.55''
1.40cm
0.24''
0.61cm
4.22''
10.72cm
3.12''
7.92cm
3.75''
9.53cm
sensing face
sensing face
0.22''
0.56cm dia.
Safety Interlock Switch
391-BT
393-BT
391-BLT-12(J)(K)
Installation
Use non-removable screws, bolts, or nuts to mount the switch and actuator. Do not over-torque mounting hardware.
1. Position the switch and actuator so the labels are reading in the same direction (See Figure 1.)
2. Mount the switch on the stationary frame of the machine and mount the actuator on the moveable guard, door or gate. Keep the switch and actuator within listed sense range. (See Ordering Information.) See Figure 2 for recommended mounting configurations.
3. Mounting on a ferrous material will effect the sense range a minimum of 50%. However, a 1/4" non-ferrous spacer positioned under the magnet and/or switch should restore most of the lost sense range.
4. For best protection against operator defeat, mount with non-removable screws, bolts or nuts. See ordering information for details.
5. When not used with a GE INT safety relay, particular care must be taken to determine the actual load of the switch circuit. High voltage transients from coils, motors, contactors and solenoids must be considered. Transient protection, such as back-to-back zener diodes (TransZorb such loads to ensure that maximum ratings of the switch are not exceeded. Not recommended to be used with tungsten filament loads because of high current inrush surges. Line capacitance and load capacitance must be considered. Excessive line capacitance can be caused by cable lengths over 50' when using a maximum 48 VAC. A resistor can be added in series to limit
®
) or an RC network, is recommended for
391-B3LT-12J 391-B3LT-20J 391-B______ 393-B______
continued
Page 2
S1
BLK
WHT
BLUE
RED
D1
D2
S2 S3
S4
CIR.
2
CIR.
1
S5
ORG
BRN
CIR.
3
Optional LED
the inrush current (at least 48 ohms for 24 Volt applications). The resistor can be added in series just before the load. The voltage drop and the power rating of the resistor must be considered. Voltage drop = I•R; Watts = I
2
•R
(I = maximum continuous current of the load).
6. When mounting the switch on an ungrounded machine, ground the switch housing by connecting your ground lead to one of the switch mounting screws.
Mounting Configurations
The interlock switch and actuator magnet should be mounted in only three configurations for actuation.
CIR.1
CIR.2
CIR.3
BLK
WHT
BLUE
RED
BRN
ORG
Circuits *
without LED
S1
S2 S3
S5
Circuits 2*
with optional LED
S4
Figure 2
Perpendicular
Actuation
Door
Actuation Parallel Actuation
Pivot Actuation
*Circuits shown with actuator away from switch.
S1,S5 Normally open reed switch, closed when actuator is within 0.6" S2, S3 Normally open reed switches, will close if misaligned or tampered with a
standard magnet
S4 Biased closed reed switch, open when actuator is between 0.3" and 0.6"
N.O. circuit: Black and white wires. N.C. biased tamper circuit: Red and blue wires. N.O. monitor circuit: Orange and brown wires.
Best Best Not Recommended
Good
Three configurations are appropriate for safety interlock applications. The parallel actuation can result in on/off/on signal if the actuator passes by the switch rather than coming to rest in proximity to it. This is NOT a recommended configuration for safety interlock applications.
Wiring Diagram for Category 3
Inputs shown with safety gates/guards in closed position. One Series 300-BT GuardSwitch™ required for each safety gate.
(–)
INT-03-230: 230V AC INT-03-120: 120V AC INT-03-024: 24V DC
(+)
Required Fast or Slow-Acting Fuse: (250V, 5x20 mm F) INT-03-230: 40mA INT-03-120: 80mA INT-03-024: 1/4A
RESET
L1 L2 1 2 X1 X2 Y1 Y2
+
N.O. N.C.
W
B
H
L
T
K
Series Circuit
R
B
E
L
D
U
R
W H T
B
B
E
L
L
D
U
K
Parallel Circuit
R
W
B
E
H
L
D
T
K
B L U
GE Security Industrial
Required Fast or Slow­Acting Fuses: 4A (250V, 5x20 mm F
230 VAC
60 VDC
Safety Monitor Relay INT-03
SAFE AUX.
A
BCD
LOADS
OUTPUTS
EFG
*300-BLT-
*Or other DPST GuardSwitch
(See the 300-BT Series installation instructions)
Note – The LED on the BLT model will be ON when the guard is open
Fuses: 1 A (250 v)
Multiple DPST GuardSwitches – Shown with actuators in position, all guards closed.
120 VAC
30 VDC
The L.E.D of the BLT model will be on when the guard is open. If multiple guards
are open, L.E.D will be dimmer. The maximum number of GuardSwitches that can
be used is 50, although troubleshooting and line resistance must be considered.
(Do not exceed 30 Ohms of combined contact and line resistance. Each GuardSwitch
will have less than 0.5 Ohms of resistance.)
*300-BLT-
*300-BLT-
GuardSwitchTM Series 300 www.ge-security.com/industrial
Page 3
CE Compliance Information
These switches are TUV certified for CE applications only when used with the INT Safety Monitor Relays. See Risk Category 3 and Category 4 wiring diagrams above.
European Directives
Machinery Directive (89/392/EEC) EMC Directive (89/336/EEC) Low Voltage Directive (73/23/EEC)
Specific European Standards
EN60204-1 Safety of electrical equipment of industrial machines EN292 Part 1, 2 Safety of Machinery, basic
Declaration of Conformity
available upon request.
terminology, technical principles EN954-1 Risk Assessment Category 3 or 4 depending on wiring method, see diagrams EN55081-2 Electromagnetic Emissions EN50082-2 Electromagnetic Immunity EN1088 Interlocking Devices EN947-5-3 Control Circuit Devices EN50178 Safety of Electrical Equipment IEC 664-1 Insulation requirements IEC 68, part 2-1, 2-2, 2-3, 2-8, 2-14, 2-27, 2-30
General Specifications
Enclosure Seamless 304 Stainless Steel
Temperature Range -40°F to 180°F (-40°C to 80°C)
Environmental Hermetically Sealed Contact Switch
Encapsulated in Polyurethane
NEMA Rating 1, 2, 4, 4X, 5, 12, 12K
Protection Class IP 67
Response Time 1 msec
Individual circuits The two circuits do not switch simultaneously, and depend
on the speed of the guard closure. Based on closure speed
of 1' per second and a gap of 1/8", a delay less than
50 msec is typical.
Life Cycles 100,000 Under Full Load;
Up to 200,000,000 Under Dry Circuit
Lead Type 18/4 SJTOW(K)/0.34" (0.86cm)
22/4 PVC Jacketed (J)/0.19" (0.48cm)
22/6 PVC Jacketed (J)/0.21" (0.53cm)
UL/CSA/TUV All Models
For additional options and alternate specifications, consult factory.
File E 122942
LR89176
Wiring Diagram for Category 4
Inputs shown with safety gate/guard in closed position. Two Series 300-BT GuardSwitches™ with one INT relay are required for each safety gate.
When first applying the INT Safety Monitor Relay, the inputs must be cycled to check for proper operation before the output contacts close. To cycle the inputs, the guard must be opened and then closed. This start-up test is sufficient; however, we recommend that the proper operation of the switches and relay be checked at least every 24 hours.
(–)
INT-03-230: 230V AC INT-03-120: 120V AC INT-03-024: 24V DC
(+)
Required Fast or Slow-Acting Fuse: (250V, 5x20 mm F) INT-03-230: 40mA INT-03-120: 80mA INT-03-024: 1/4A
Required Fast or Slow-Acting Fuses: 4A (250V, 5x20 mm F
230 VAC
60 VDC
LOADS
RESET
L1 L2 1 2 X1 X2 Y1 Y2
+
Safety Monitor Relay INT-03
SAFE AUX.
A
BCD EFG
N.O. N.C.
OUTPUTS
W H T
*Or other DPST GuardSwitch
(See the 300-BT Series
installation instructions)
120 VAC
30 VDC
R
B
B
E
L
L
D
U
K
*300-BLT-
Note – The LED on the BLT model
will be ON when the guard is open
Fuses: 1A (250V)
W H T
B L K
*300-BLT-
R
B
E
L
D
U
GE Security Industrial
GuardSwitchTM Series 300 www.ge-security.com/industrial
Page 4
Electrical Specifications
CIRCUIT CIRCUIT CONTACT LOAD SWITCHING SWITCHING NUMBER TYPE CONFIGURATIO RATING VOLTAGE CURRENT
1 Switch: S1 N.O. 40W/VA 48VAC/VDC 1.0ADC, 0.7AAC
2 Tamper: S2, S3, S4 N.C. 10W/VA 48VAC/VDC 0.3A
2 w/optional LED: D1 N.C. 0.1–1.4W 48VDC(3V drop) 30mA
3 Monitor: S5 N.O. 10W/VA 48VAC/VDC 0.3ADC, 0.3AAC
Ordering Information
PART NUMBER 391 or 393 CONFIGURAT MINIMUM MAXIMUM RANGE NOMINAL
391-BT-06(J)(K) DPST: 1 N.O., 1 N.C. 0.3"(0.8cm) 0.6"(1.5cm) 1.2"(3.0cm) 6' (1.8m)
391-BT-12(J)(K) DPST: 1 N.O., 1 N.C. 0.3"(0.8cm) 0.6"(1.5cm) 1.2"(3.0cm) 12' (3.6m)
391-BLT-06(J) DPST: 1 N.O., 1 N.C. w/LED 0.3"(0.8cm) 0.6"(1.5cm) 1.2"(3.0cm) 6' (1.8m)
391-BLT-12(J)(K) DPST: 1 N.O., 1 N.C. w/ LED 0.3"(0.8cm) 0.6"(1.5cm) 1.2"(3.0cm) 12' (3.6m)
391-B3LT-12(J) TPST: 2 N.O., 1 N.C. w/LED 0.3"(0.8cm) 0.6"(1.5cm) 1.2"(3.0cm) 12' (3.6m)
391-B3LT-20(J) TPST: 2 N.O., 1 N.C. w/LED 0.3"(0.8cm) 0.6"(1.5cm) 1.2"(3.0cm) 20' (6.1m)
1
CONTACT
2
SENSE RANGE
3
SENSE RANGE
3
BREAK LEAD LENGTH
Accessories
PART NUMBER TAMPER PROOF SCREWS & SCREWDRIVER
1953 #6 x 3/4"L Tampruf Roundhead Screw
1954 #8 x 1-1/2"L Tampruf Roundhead Screw
1955 Tampruf® Screwdriver
1956 Tampruf® 1/4" Drive Bit for #6 and #8 screws
Warning— Each electrical rating is an individual maximum and cannot be exceeded!
1
The part numbers 391 and 393 are the same in all respects except the cable exits 391 left and 393 right. Not all models available in 393.
2
Configuration with actuator away from the switch
3
Proximity of ferrous materials usually reduces sense range — typically by 50%. The shape and type of material cause a wide diversity of effects. Testing is required to determine actual sense range for specific applications.