Description
The 341-BT Series 300 DPST safety interlock switch is designed for use with safety
monitored relays or monitored circuits. To achieve the optimum Series 300 defeat
resistant feature of the 341-BT, both the switch circuit (Circuit 1) and the tamper
circuit (Circuit 2) must be connected. An optional third circuit can be provided to
indicate at the panel which guard is open.
Notes:
1. Environmental: Pollution Degree II
2. Correct use of this control device is an essential part of proper machine cycle
control.
3. Failure to follow ALL instructions could lead to serious bodily injury or death.
4. Maintenance to be done by qualified personnel only
5. The connecting cables between the INT devices and the switches must be located in
an IP 23 type enclosure (minimum).
6. The mounting for the switch and the actuator magnet must be accomplished per
this specification.
7. Non-removable hardware must be used for installation.
8. The housing of the 300-BT Series GuardSwitches must be connected to the PE
(Primary Earth) ground circuit via a lock washer on the mounting screw. The PE
ground symbol must be placed adjacent to the screw.
To verify switch operation with an ohmmeter:
Set range at 20 mega ohms (switches with triac output, set ohm range at 20 kilo
ohms). For a normally open switch, the meter will read a high impedance with the
actuator away. It will read very high to infinity range (triac switches will read high kilo
ohm to infinity range) with the actuator within sense range. You will see the opposite
reading for a normally closed switch.
Dimensions
0.19''
0.48cm
2.13"
5.41cm
1.75"
4.45cm
0.86"
2.18cm
0.22"
0.56cm dia.
2.74cm
1. 08"
0.57"
1.45cm
0.28cm
0.11"
GuardSwitch™ Series 300
Safety Interlock Switch
341-BT-06(J)(K)
341-BT
341-BT-12(J)(K)
341-BT-20K
343-BT
341-BT-25J
341-B3T-06J
341-B3T-12J
341-B3T-20J
341-B3T-25J
Installation
Use non-removable screws, bolts, or nuts to mount the switch and actuator. Do not
over-torque mounting hardware.
1. Position the switch and actuator so the labels are reading in the same direction
(See Figure 1.)
2. Mount the switch on the stationary frame of the machine and mount the actuator
on the moveable guard, door or gate. Keep the switch and actuator within the
listed sense range. (See Ordering Information.)
See Figure 2 for recommended mounting configurations.
3. Mounting on a ferrous material will effect the sense range a minimum of 50%.
However, a 1/4" non-ferrous spacer positioned under the actuator and/or switch
should restore most of the lost sense range.
4. For best protection against operator defeat, mount with non-removable screws,
bolts or nuts (see Accessories).
5. Caution! When not used with a GE INT safety relay, particular care must be taken to
determine the actual load of the switch circuit. High voltage transients from coils,
motors, contactors, and solenoids must be considered. Transient protection, such
as back-to-back zener diodes (TransZorb
such loads to ensure that maximum ratings of the switch are not exceeded. Not
recommended to be used with tungsten filament loads because of high current
inrush surges. Line capacitance and load capacitance must be considered.
Excessive line capacitance can be caused by cable lengths over 50' when using a
maximum 48 VAC.
®
341-B3T-30J
341-BLT-06(J)(K)
341-BLT-12(J)(K)
341-B3LT-06J
341-B3LT-12J
341-B________
343-B________
) or an RC network, is recommended for
continued
A resistor can be added in series to limit the inrush current (at least 48 Ohms for
24V applications). The resistor can be added in series just before the load. The
voltage drop and the power rating of the resistor must be considered. Voltage
2
drop = I•R; Watts = I
R (I = maximum continuous current of the load).
6. When mounting the switch on an ungrounded machine, ground the switch housing
by connecting your ground lead to one of the switch mounting screws.
Figure 1
sensing face
sensing face
Mounting Configurations
Figure 2
Perpendicular
Actuation
Door
Actuation
Pivot Actuation
Parallel Actuation
CIR.1
CIR.2
CIR.3
BLK
WHT
BLUE
RED
BRN
ORG
Circuits
without LED
S1
S2 S3
S5
BLK
CIR.
1
WHT
S4
CIR.
CIR.
2
3
BLUE
D1
RED
BRN
ORG
Circuits
with optional LED
S1
Optional LED
D2
S2 S3
S5
S4
*Circuits shown with magnet actuator away from switch.
S1, S5 Normally open reed switch, closed when actuator is within 0.38"
S2, S3 Normally open reed switches, will close if misaligned or tampered with
a standard magnet
S4 Biased closed reed switch, open when actuator is between 0.12" and 0.38"
S5 Normally open reed switch, closed when actuator is within 0.38".
N.O. circuit: Black and white wires.
N.C. biased tamper circuit: Red and blue wires.
N.O. monitor circuit: Orange and brown wires.
Best Best Not Recommended
Good
The parallel actuation can result in on/off/on signal if the actuator passes by the
switch rather than coming to rest in proximity to it. This is NOT a recommended
configuration for safety interlock applications.
Wiring Diagram for Category 3
Inputs shown with safety gates/guards in closed position. One Series 300-BT GuardSwitch™ required for each safety gate.
(–)
INT-03-230: 230V AC
INT-03-120: 120V AC
INT-03-024: 24V DC
(+)
Required Fast or
Slow-Acting Fuse:
(250V, 5x20 mm F)
INT-03-230: 40mA
INT-03-120: 80mA
INT-03-024: 1/4A
RESET
L1 L2 1 2 X1 X2 Y1 Y2
–
+
Safety Monitor Relay
INT-03
SAFE AUX.
A
BCD
N.O. N.C.
OUTPUTS
EFG
W
B
H
L
T
K
*300-BLT-
*Or other DPST GuardSwitch
(See the 300-BT Series installation instructions)
Series Circuit
R
B
E
L
D
U
W
H
T
R
B
E
L
D
K
*300-BLT-
B
L
U
Parallel Circuit
R
W
B
E
H
L
D
T
K
*300-BLT-
B
L
U
Required Fast or SlowActing Fuses: 4A (250V,
5x20 mm F
GE Security Industrial
230 VAC
60 VDC
LOADS
Note – The LED on the BLT model will be ON when the guard is open
Fuses: 1 A (250 v)
Multiple DPST GuardSwitches – Shown with actuators in position, all guards closed.
120 VAC
30 VDC
The L.E.D of the BLT model will be on when the guard is open. If multiple guards
are open, L.E.D will be dimmer. The maximum number of GuardSwitches that can
be used is 50, although troubleshooting and line resistance must be considered.
(Do not exceed 30 Ohms of combined contact and line resistance. Each GuardSwitch
will have less than 0.5 Ohms of resistance.)