Explosion-Proof With Terminals
Actuator
Switch
conduit
sensing face
sensing face
5.75''
14.61cm
5.27''
13.39cm
0.24''
0.61cm
0.83''
2.11cm
0.42''
1.07cm
5.75''
14.61cm
5.26''
13.36cm
0.24''
0.61cm
0.64''
1.63cm
2.03''
5.16cm
0.64''
1.63cm
2.33''
5.92cm
1.10''
2.79cm
0.28''
0.71cm
1.12''
2.84cm
1.49''
3.78cm
0.22''
0.56cm
dia.
1.51''
3.84cm
2800T Series
Applications
• Explosion-proof; UL listed for hazardous location classes:
- Class I Group C, D
- Class II Group E, F, and G
- Class I Group B housing available
• Options include remote test, resettable current limiting devise,
custom modifications available
• Switch has pry-tamper plate
General Specifications
Enclosure UL Explosion Proof, Die Cast Aluminum
Temperature Range -40°F to -180°F (-40°C to 80°C)
Environmental Hermetically Sealed Reed Switch
NEMA Rating 1, 2, 3, 5, 12
Protection Class IP 64
Response Time 1 msec max.
Life Cycles
Conduit Connection 1/2" Thread NPT
UL Listed
Encapsulated in Polyurethane
100,000 Under Full Load,
10,000,000 Under Dry Circuit
All Models
Order Information Electrical Specifications
1
Part Number
Configuration (AC/DC) (AC/DC) (AC/DC) Nominal Type
Contact
2807T-M SPDT 3W/VA 30V 0.25A 0.18" (0.5cm) to 0.62" (1.6cm) #6 Screw
2845T-M N.O. 7.5W/VA 100V 0.5A 1.0" (2.5cm) #6 Screw
2847T-M SPDT 3W/VA 30V 0.25A 1.0" (2.5cm) #6 Screw
Warning— Each electrical rating is an individual maximum and cannot be exceeded!
1
Configuration with actuator away from the switch
2
Proximity of ferrous materials usually reduces sense range — typically by 50%. The shape and type of material cause a wide diversity of effects.
Testing is required to determine actual sense range for specific applications. As measured on a nonferrous surface.
Gap distances are nominal make distance ± 20%. Gap Specifications are for switch to make. Break distance is approximately 1.1 to 1.5 times make.
Load Rating Switching Voltage Switching Current Sense Range2 Terminal
POSITION SENSORS